18

CAUTIONS

 

 This product has been developed / produced for industrial use only.

 

 Make sure that the power supply is OFF while wiring and adding the units.

 

 Take care that if a voltage exceeding the rated range is applied, or if an AC power 

supply is directly connected, the product may get burnt or damaged.

 

 Take care that short circuit of the load or wrong wiring may burn or damage the 

product.

 

 Do not run the wires together with high-voltage lines or power lines or put them in 

the same raceway. This can cause malfunction due to induction.

 

  

 

 Verify that the supply voltage variation is within the rating.

 

 If power is supplied from a commercial switching regulator, ensure that the frame 

ground (F.G.) terminal of the power supply is connected to an actual ground.

 

 In case noise generating equipment (switching regulator, inverter motor, etc.) is 

used in the vicinity of this product, connect the frame ground (F.G.) terminal of the 
equipment to an actual ground.

 

 Do not use during the initial transient time (approx. 1 sec.) after the power supply 

is switched ON.

 

 Make sure to use the quick-connection cable (optional) for the connection of the 

controller. Extension up to total 50m (if 9 to 16 units are connected in cascade: 
20m) is possible with 0.3mm

2

, or more, cable.

However, in order to reduce noise, make the wiring as short as possible.

 

 Make sure that stress by forcible bend or pulling is not applied to the sensor cable 

joint.

 

 This product is suitable for indoor use only.

 

 Avoid dust, dirt, and steam.

 

 Take care that the product does not come in contact with oil, grease, organic sol-

vents, such as thinner, etc., strong acid or alkaline.

 

  $  %-

sive gases.

 

 Never disassemble or modify the product.

 

 This product adopts EEPROM. Settings cannot be done 100 thousand times or 

more, because of the EEPROM’s lifetime.

19

INTENDED PRODUCTS FOR CE MARKING

 

 The models listed under “

17

SPECIFICATIONS

” come with CE Marking.

{ *

15

ERROR INDICATION

Error indication

Cause

Remedy

EEPROM is broken or reached the 
end of its working life.

;

EEPROM writing error.

Load of the comparative output 1 is 
short-circuited causing an overcur-
$

Turn OFF the power and check the load.

Load of the comparative output 2 is 
short-circuited causing an overcur-
$

Disconnection error of the pressure 
sensor head.

Check the connection state of the pressure sensor head.

Communication error when the 
controllers are mounted closely.

Verify that there is no loose or clearance between controllers.

Communication error between the 
upper communication unit and a 
controller.

Verify that there is no loose or clearance between the upper 
communication unit and the controller connected right after the 
upper communication unit.

The applied pressure exceeds the 
upper limit of the displayed pres-
sure range.

Applied pressure range should be brought within the rated pres-
sure range.

The applied pressure exceeds the 
lower limit of the displayed pressure 
range.

When other error massage is displayed, contact us.

16

OPTICAL COMMUNICATIONS

 

 When the data bank loading / saving, or copy setting is conducted via optical 

communications, cascade the sub controllers right side to the main controller as 
follows. 

 

 If a sub controller is under any of the following conditions, the data bank loading / 

saving, or copy setting cannot be carried out.

| In case the digital display is blinking
| In case PRO mode is being set
| In case the communication enable / disable setting is set to communication dis-

able “ 

.”

 

 When communication protocol of a sub controller is set to communication halt  

“ 

,” the data bank loading / saving, or copy setting cannot be carried out 

to sub controllers subsequent to the mentioned controller.

 

 The pressure sensing operation stops during optical communication.

Communication direction

Sub controllers

Main controllers

17

SPECIFICATIONS

Type

Compound / Vacuum pressure type

Positive pressure type

Model No.

DPS-401

DPS-402

Applicable pressure sensor

Compound pressure type 

DPH-101

!

Vacuum pressure type 

DPH-103

!

Positive pressure type 

DPH-102

!

Pressure type

Gauge pressure

Rated pressure range

-100.0 to 100.0kPa

0 to -101kPa

0 to 1.000MPa

Display / setting pressure 
range

-199.9 to 199.9kPa
101.3 to -101.3kPa

-1.050 to 1.050MPa

Supply voltage

12 to 24V DC ±10%

Power consumption (Note 1)

Normal operation: 650mW or less (current consumption 25mA or less at 24V supply voltage)
Eco mode: 500mW or less (current consumption 20mA or less at 24V supply voltage)

Pressure sensor head supply 
voltage

Same as the supply voltage

Pressure sensor head input

Input voltage range: 1 to 5V DC (within the rated pressure range)

Comparative output
(Comparative output 1 / 2)

NPN open-collector transistor

| Maximum sink current: 50mA (Note 2)
| Applied voltage: 30V DC or less (between comparative output and 0V)
| Residual voltage: 1.5V or less (Note 3) [at 50mA (Note 2) sink current]

Output operation

Selectable either NO or NC, with key operation

Hysteresis

Min. 0 digit, changeable at hysteresis setting

Repeatability

Compound pressure type: Within ±0.2% F.S. digits (±4 digits)
Vacuum / positive pressure type: Within ±0.2% F.S. digit (±2 digits)

Response time

?@QX*@QQX*? *@ *?Q *@Q *?QQ @QQ 6

Ambient temperature

-10 to +50ºC (If 8 to 16 units are mounted closely: -10 to +45ºC) (No dew condensa-
tion or icing allowed), Storage: -20 to +70ºC

Ambient humidity

35 to 85% RH, Storage: 35 to 85% RH

Temperature characteristics

Within ±0.5% F.S. (at +25ºC reference)

Material

Enclosure: Heat-resistant ABS, Protective cover: Polycarbonate
Jog switch: ABS, MODE key: Acrylic

Weight

Approx. 20g (main body only)

Notes: 1) Excluding current consumption of the applicable pressure sensor head.
 

2) 25mA max. if 5, or more controllers are connected together.

 

3) In case of using the quick-connection cable (cable length 5m) (optional).

 

4) The cable for controller connection is not supplied as an accessory. Make sure to use the quick-connection 

cables (optional) given below.

 

 

Main cable (4-core):

 

 

CN-74-C1

 (cable length 1m), 

CN-74-C2

 (cable length 2m), 

CN-74-C5

 (cable length 5m)

 

 

Sub cable (2-core):

 

 

CN-72-C1

 (cable length 1m), 

CN-72-C2

 (cable length 2m), 

CN-72-C5

 (cable length 5m)

@#               

pressure sensor head, refer to the instruction manual enclosed with the pressure sensor head.

http://panasonic-electric-works.net/sunx

2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan 
Phone: +81-568-33-7861  FAX: +81-568-33-8591

Europe Headquarter: Panasonic Electric Works Europe AG

Rudolf-Diesel-Ring 2, D-83607 Holzkirchen, Germany
Phone: +49-8024-648-0

US Headquarter: Panasonic Electric Works Corporation of America

629 Central Avenue New Providence, New Jersey 07974 USA
Phone: +1-908-464-3550

PRINTED IN JAPAN

© Panasonic Electric Works SUNX Co., Ltd. 2011 

Содержание DPS-400 Series

Страница 1: ...tion signal 4 CONTROLLER CASCADING Make sure that the power supply is OFF while adding or removing the series connection type In case 2 or more the series connection types are connected in cascade make sure to mount them on a DIN rail The maximum 11 the controllers using sub cables CN 72 C added to a controller using a main cable CN 74 C When connecting 2 or more in cascade use the sub cable for t...

Страница 2: ...g mode are not inadvertently changed If operating the jog switch or MODE key after key lock is set is indi cated on the digital display Setting of key lock Press down for 3 sec or more Automatic Release of key lock Press down for 3 sec or more Automatic Peak bottom hold function 6 6 Set the digital display to lock OFF while pressure value is indi cated on the digital display red After setting pres...

Страница 3: ... to ON in RUN mode Time period hold setting Hold OFF Peak bottom value in the digital display refreshing condition can be displayed Hold ON Peak bottom value in the hold condition can be displayed Display adjustment Forcibly sets the pressure value indicated on the digital display to zero Threshold value changes in conjunction with the pressure value Display adjustment OFF Display adjustment ON PR...

Страница 4: ...ny of the following conditions the data bank loading saving or copy setting cannot be carried out In case the digital display is blinking In case PRO mode is being set In case the communication enable disable setting is set to communication dis able When communication protocol of a sub controller is set to communication halt the data bank loading saving or copy setting cannot be carried out to sub...