Hysteresis mode

 

 The comparative output ON / OFF state can be controlled with randomly set hys-

teresis in this mode.

Pressure

Comparative 
output

0

2_SL

1_SL

ON

OFF

H (Hysteresis)

Forced ON output mode

 

 Sets forcibly the comparative output to ON.

Forced OFF output mode

 

 Sets forcibly the comparative output to OFF.

8

OPERATION PROCEDURE

 

 Be sure to set the comparative output 1 or the comparative output 2 before set-

ting each item.

 

 The items that can be set in the comparative output 1 and the comparative 

output 2 respectively are only Threshold value, NO / NC and Output mode. The 
items other than those are common.

However, in case of code setting, a combination of the comparative output 1 / 
2 can be set only for output mode. The items other than output mode are valid 
only for the comparative output 1.

 

 The changed contents are not stored if turning the power OFF while setting. 

*  6          8  
turning the power OFF.

RUN mode

PRO mode

Zero-adjustment mode

Refer to “

9

RUN MODE

Refer to “

14

PRO MODE

Refer to “

10

ZERO-ADJUSTMENT (FOR PRESSURE VALUE ONLY) MODE

Refer to “

11

NO / NC MODE

Refer to “

12

OUTPUT MODE

Refer to “

13

CUSTOM MODE

Output mode

NO / NC mode

CUSTOM mode

9

RUN MODE

 

 After the power is turned ON, the mode will be in the RUN mode and the MODE 

indicator: RUN (green) lights up. The digital display shows the threshold value 
(green) and the pressure value (red).

 

 The decimal point mark is used at “RUN mode.”

Threshold value setting

 

 In case of compound pressure type or positive pressure type, turn the jog switch to “+” side 

to increase the threshold value. While turn the jog switch to “-” side to decrease the thresh-
old value. In case of vacuum pressure type, turn the jog switch to “-” side to increase the 
threshold value. While turn the jog switch to “+” side to decrease the threshold value.

<Example> Compound pressure type
(In case of EASY mode)

 

Turn the jog switch

Press down the jog switch

(In case of window comparator mode or hysteresis mode)

 

 When setting output mode to the window comparator mode or hysteresis mode, turn 

the jog switch to show “ 

 ” or “ 

 ”. Turn the jog switch again to set the thresh-

old value. Press down the jog switch for 2 sec. or more to show “ 

 ” or “ 

 ”.

For the output mode, refer to “

12

OUTPUT MODE

.”

 

Turn the jog switch

Threshold value 1 setting

Threshold value 2 setting

Turn the jog switch

Press down 
for 2 sec. 
or more

Turn the jog switch

Press down the jog switch

Note:  Take care if the pressure sensor head is replaced after setting the threshold value, the set threshold value is changed.

(In case of forced ON output mode or forced OFF output mode)

 

Turn the jog switch

Forced ON output mode

Forced OFF output mode

Turn the jog switch

Press down the jog switch

Key lock function

 

 The key lock function prevents key operations so that the conditions set in each set-

ting mode are not inadvertently changed.

 

 If operating the jog switch or MODE key after key lock is set, “ 

 ” is indi-

cated on the digital display.

<Setting of key lock>

Press down for 3 sec. or more

Automatic

<Release of key lock>

Press down for 3 sec. or more

Automatic

Peak / bottom hold function

 

 ;6< 6 $

 

 Set the digital display to “ 

 ” (lock OFF) while pressure value is indi-

cated on the digital display (red). After setting, press the jog switch to show the 
peak / bottom value on the digital display (red). When the digital display is set to  
“ 

 ” (lock ON), the peak / bottom value is not indicated on the digital dis-

play (red) even if pressing the jog switch. For digital display setting, refer to 

<PRO 

2: Digital display setting>

 in “

14

PRO MODE

.”

 

 Sampling of the peak value and the bottom value begins right after pressing the jog switch.

 

 In case of compound pressure type or positive pressure type, the higher pressure 

side indicates the peak value, while the lower pressure side indicates the bottom 
value. In case of vacuum pressure type, the higher vacuum side indicates the 
peak value, while the lower vacuum side indicates the bottom value.

 

 Although the displays of the peak value and the bottom value are maintained, the 

values are not stored to EEPROM.

<Setting of peak / bottom hold function>

Press down the jog switch

Automatic

Automatic

Automatic

Automatic

Peak value

Bottom value

Displays sequentially

<Release of peak / bottom hold function>

Press down the jog switch

Automatic

Automatic

Automatic

Automatic

Peak value

Bottom value

Displays sequentially

Note:  When pressing the jog switch at any of the displays within the dashed area, the peak value and the bottom value 

are cleared and returns to RUN mode.

10

ZERO-ADJUSTMENT (FOR PRESSURE VALUE ONLY) MODE

 

 The zero-adjustment (only for pressure value) mode forcibly sets the pressure 

value to “zero” when the pressure port is opened.

 

 When the MODE indicator: ZERO (yellow) lights up, the zero-adjustment can be 

done only for pressure value.

 

 The zero-adjustment can be performed for compound pressure type: up to ±5kPa, for 

vacuum pressure type: up to ±5kPa, and for positive pressure type: up to ±0.05MPa.

Press down the jog switch

Automatic

Blinks 3 times

Note: Take care if the pressure sensor head is replaced after setting the zero-adjustment (for pressure value only) 

mode, the set pressure value “zero” is changed.

11

NO / NC MODE

 

 When MODE indicator: NO / NC (yellow) lights up, NO (normally open) / NC (normally 

closed) can be set.

 

 The comparative output 1 / 2 operation indicator (orange) lights up when NC (normally 

closed) is set.

 

Turn the jog switch

Press down the jog switch

12

OUTPUT MODE

 

 When MODE indicator: OUT (yellow) lights up, output mode can be set.

 

 The comparative output 1 / 2 operation indicator (orange) lights up when forced 

ON output mode is set.

Press down the jog switch

 

EASY mode

Window comparator mode

Forced OFF output mode

Hysteresis mode

Forced ON output mode

Note:  In case of the comparative output 2, the window comparator mode is not displayed.

Содержание DPS-400 Series

Страница 1: ...tion signal 4 CONTROLLER CASCADING Make sure that the power supply is OFF while adding or removing the series connection type In case 2 or more the series connection types are connected in cascade make sure to mount them on a DIN rail The maximum 11 the controllers using sub cables CN 72 C added to a controller using a main cable CN 74 C When connecting 2 or more in cascade use the sub cable for t...

Страница 2: ...g mode are not inadvertently changed If operating the jog switch or MODE key after key lock is set is indi cated on the digital display Setting of key lock Press down for 3 sec or more Automatic Release of key lock Press down for 3 sec or more Automatic Peak bottom hold function 6 6 Set the digital display to lock OFF while pressure value is indi cated on the digital display red After setting pres...

Страница 3: ... to ON in RUN mode Time period hold setting Hold OFF Peak bottom value in the digital display refreshing condition can be displayed Hold ON Peak bottom value in the hold condition can be displayed Display adjustment Forcibly sets the pressure value indicated on the digital display to zero Threshold value changes in conjunction with the pressure value Display adjustment OFF Display adjustment ON PR...

Страница 4: ...ny of the following conditions the data bank loading saving or copy setting cannot be carried out In case the digital display is blinking In case PRO mode is being set In case the communication enable disable setting is set to communication dis able When communication protocol of a sub controller is set to communication halt the data bank loading saving or copy setting cannot be carried out to sub...

Отзывы: