Operation chart
Note: The set values shift in the same manner during the EASY mode or the window comparator mode.
The detected pressure value at auto-reference input becomes “zero” when the
setting of the analogue voltage / current output selection function is changed
or the power is turned ON again.
The auto-reference input value can be checked when setting the threshold value
in RUN mode. Refer to “
Threshold value setting
” in “
RUN MODE
” for details.
13
REMOTE ZERO-ADJUSTMENT FUNCTION
The remote zero-adjustment function forcibly sets the pressure value to “zero”
when the external signal is input.
The setting value is not corrected when remote zero-adjustment is input. Make
sure that the pressure and set value during remote zero-adjustment do not exceed
the set pressure range.
Operation chart
Notes: 1) The setting values shift in the same manner during the EASY mode or the window comparator mode.
2) The remote zero-adjustment function is applicable only to the comparative output set at the external
input relation selection. Unset comparative output operates based on the atmospheric pressure.
The remote zero-adjustment value is cleared when the setting of the analogue
voltage / current output selection is changed or the power is turned ON again,
and normal operation based on the atmospheric pressure is resumed.
#\^ _#; #
value in RUN mode. Refer to the threshold value setting in “
RUN MODE
”
14
CURRENT VALUE HOLD FUNCTION
During turning ON the external input, it display continuously current pressure value.
Even if holding the display, it is possible to determine output and to change
threshold value.
In case display is held, actual value is not displayed. be sure that impressed
$; .
15
PEAK / BOTTOM HOLD FUNCTION
In case setting peak / bottom hold 1 setting, displays peak value and bottom
value in same time after setting.
In case of setting peak / bottom hold 2 setting, displays both peak value and
bottom value in same time in conjunction with output.
In case power is ON (OFF), hold the display until next output is ON (OFF). the
set value in conjunction with output.
However, in case of setting window comparator, it operate as peak / bottom hold 1 setting.
For setting method, refer to “
Peak / bottom hold function
” in “
RUN MODE
.”
16
CAUTIONS
This product has been developed / produced for industrial use only.
Make sure that the power supply is OFF while wiring.
Take care that if a voltage exceeding the rated range is applied, or if an AC
power supply is directly connected, the product may get burnt or damaged.
Take care that wrong wiring will damage the sensor.
Do not run the wires together with high-voltage lines or power lines or put them
in the same raceway. This can cause malfunction due to induction.
If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicin-
ity of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground.
Do not use during the initial transient time (0.5 sec.) after the power supply is switched on.
Extension up to total 100m (emitter and receiver each for thru-beam type), or less,
is possible with 0.3mm
2
, or more of conductor cross-section area cable. However,
to reduce noise, make the wiring as short as possible. If using this product as
complaint model with CE mark, the power supply line must be 30m or less.
Brinks alternately
External input ON
During normal operation
(each comparative output set to N.O.)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60
Displayed value (kPa)
1
2
10
20
Set value (kPa)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60
Displayed value (kPa)
P(a)
1
’
10
20
Set value (kPa)
2
’
30
During auto-reference input
(each comparative output set to N.O.)
Detected pressure at auto-reference input: 10kPa
Output mode: Hysteresis mode
During remote zero-adjustment input
(each comparative output set to N.O.)
Detected pressure at remote zero-adjustment input: 10kPa
Output mode: Hysteresis mode
Output
ON
OFF
0
0
10
10
20
20
30
30
40
40
50
50
60
-10
1
’
10
20
2
’
During normal operation
(each comparative output set to N.O.)
Output
ON
OFF
0
0
10
10
20
20
30
30
40
40
50
50
60
60
1
2
10
20
Applied pressure (kPa)
Displayed value (kPa)
Set value (kPa)
Applied pressure (kPa)
Displayed value (kPa)
Set value (kPa)
<
Bottom hold 2
>
ON
Bottom
value
OFF
OFF
Start
Current
value
Set
value
ON
<Peak hold 2>
Set
value
Start
ON OFF ON
ON
OFF
Peak value
Current
value
OFF
Make sure that stress by forcible bend or pulling is not applied directly to the
sensor cable joint.
This sensor is suitable for indoor use only.
Avoid dust, dirt, and steam.
Take care that the product does not come in contact with water, oil, grease, or
organic solvents, such as, thinner, etc.
Do not operate the keys with pointed or sharp objects.
Do not use this sensor in places having excessive vapor, dust, etc., or where it
may come in contact with corrosive gas, etc.
Never disassemble or modify the sensor.
This product use EEPROM. The EEPROM has lifetime and cannot set more
then 1 million times of setting.
17
ERROR INDICATION
When error is occurred, use the countermeasure listed blow.
Error
message
Cause
Corrective action
The controller and the pressure sensor
head are not correctly connected.
The pressure sensor head is damaged.
Connect the controller and the pressure sensor
head correctly.
Replace the pressure sensor head.
The load is short-circuited causing an over-
{
Turn the power OFF and check the load.
Pressure is applied during zero-point adjust-
ment.
Applied pressure at the pressure port should be
brought to atmospheric pressure and zero-point
adjustment should be done again.
External input is carried out outside the rated
pressure range.
Applied pressure range should be brought within
the rated pressure range.
Communication error
(Disconnection, faulty connection, etc.)
Check the wiring when using the copy function.
Communication error
(Incorrect model.)
Make sure that the system is configured of the
same models when using the copy function.
The applied pressure exceeds the upper limit
of the display pressure range.
Applied pressure range should be brought within
the rated pressure range.
The output is kept.
The applied pressure exceeds the lower limit
of the display pressure range.
When other error massage is displayed, contact us.
18
SPECIFICATIONS
Type
NPN output type
PNP output type
For inside of Japan
For outside of japan
For inside of Japan
For outside of japan
Model No.
DPC-L101Z
DPC-L101
DPC-L101Z-P
DPC-L101-P
Applicable pressure
sensor head
DPH-L113V
,
DPH-L113
,
DPH-L133
,
DPH-L114
,
DPH-L154
Rated pressure range
-0.1 to 1MPa / 0 to 1MPa / 0 to 3.5MPa / 0 to 10MPa / 0 to 50MPa
Set pressure range
-1.177 to 1.177MPa / -1.070 to 1.070MPa / -3.74 to 3.74MPa / -10.70 to 10.70MPa /
-53.5 to 53.5MPa
Supply voltage
12 to 24V DC ±10% Ripple P-P 10% or less
Power consumption
(Note 2)
Normal operation: 960mW or less (current consumption 40mA or less at 24V supply voltage)
ECO mode (STD): 720mW or less (current consumption 30mA or less at 24V supply voltage)
ECO mode (FULL): 600mW or less (current consumption 25mA or less at 24V supply voltage)
Sensor head supply voltage
Same as supply voltage
Input
Pressure sensor
head input
Input voltage range: 1 to 5V DC (within the rated pressure range)
External input
ON voltage: 0.4V DC or less
OFF voltage: 5 to 30V DC or open
# $!
Input time: 1ms or more
ON voltage: 5V to +V DC
OFF voltage: 0.6V DC or less or open
# $!"
Input time: 1ms or more
Comparative output
(Comparative output 1/2)
NPN open-collector transistor
Maximum sink current: 50mA
Applied voltage: 30V DC or less
(between comparative output and 0V)
Residual voltage: 1V or less
(at 50mA sink current)
PNP open-collector transistor
Maximum source current: 50mA
Applied voltage: 30V DC or less
(between comparative output and +V)
Residual voltage: 1V or less
(at 50mA source current)
Output operation
Selectable either N.O. or N.C., with key operation
Hysteresis
Minimum 1 digit
Repeatability
Within ±0.2% F.S.
Response time
5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms or 5,000ms
selectable with key operations
Analogue output
<Analogue voltage output>
Output voltage: 1 to 5V
# $"
Zero point: Within 1V ±0.5% F.S.
(
DPH-L113V
: Within 1.364V ±0.5% F.S.)
Span: Within 4V ±0.5% F.S.
Linearity: Within ±0.1% F.S.
<Analogue current output>
Output current: 4 to 20mA
= !@
Zero point: within 4mA ±1% F.S.
(
DPH-L113V
: within 5.455mA ±1% F.S.)
Span: Within 16mA ±1.5%F.S.
Linearity: Within ±0.1%F.S.
Ambient temperature
-10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60ºC
Ambient humidity
*'%8 *'%
Material
X@ =| &&
Mounting screw section: Brass (nickel-plated), Switch: Silicon rubber
Weight
(Main body only)
Approx. 25g
Accessories
CN-66A-C2
(Cable with a connector, 2m long) (Optional for J type): 1 pc.
Unit switching label: 1 pc.
Notes: 1) The cable with connector is not enclosed with models that have “-J” at the end of the model names.
2) Excluding the current consumption of analogue output current and applying pressure sensor head.
* ; &ZZ # Z
Z # Z;
19
CE MARKED PRODUCT
The models listed under “
SPECIFICATIONS
” come with CE
Marking. As for all other models, please contact us.
Contact for CE
Panasonic Marketing Europe GmbH Panasonic Testing Center
Winsbergring 15, 22525 Hamburg,Germany
http://panasonic.net/id/pidsx/global
PRINTED IN JAPAN
&"'&!