Instructions for the Electrical Installer

 (CZ-CFUNC2)

For your safety

Read the following instructions carefully, and carry out secure installation and electrical work.
The precautions given in this manual consist of specific “Warnings” and “Cautions”. They provide important safety-related information. Be
sure to strictly observe all safety procedures. The labels and their meanings are as described below.

*

After installation is completed, perform a test run to check for operating trouble. Explain operating procedures to the customer following the
central control device Operation Manual and then request the customer to store this Instructions for the Electrical Installer together with the
central control device Operation Manual.

Warning

Be sure to arrange installation by the dealer where the system was purchased or by a professional installer. Electric shock or fire may result 
if an inexperienced person performs any installation or wiring procedures incorrectly.

Be sure that this unit is securely installed in accordance with this Instructions for the Electrical Installer. Electric shock or fire may result if 
any installation or wiring procedures are incorrectly performed.

Only a qualified electrician should attempt to connect this system, in accordance with the instructions in this manual. Insufficient electrical 
circuit capacity or incorrect installation may cause electric shock and fire.

Use the specified cables for the electrical connections, and connect the cables securely. Run and fasten the cables securely so that
external forces or pressure placed on the cables will not be transmitted to the connection terminals. Overheating or fire may result if
connections or attachments are not secure.

Depending on the installation conditions and location, an earth leakage breaker may be required. If an earth-leakage breaker is not
installed, there is a danger of electric shock or fire.

The installation location requires the use of a circuit breaker. Failure to use a circuit breaker may result in electric shock or fire.

Circuit breaker must be incorporated in the fixed wiring in accordance with the wiring regulations. The circuit breaker must be an approved 
10-16 A, having a contact separation in all poles.

Caution

Ground yourself to discharge static electricity before performing any wiring.

Warning

Caution

This symbol refers to a hazard or unsafe procedure or practice that can result in severe personal injury or
death.

This symbol refers to a hazard or unsafe procedure or practice that can result in personal injury or product or
property damage.

Installing

Note

Do not run the indoor/outdoor communication lines, input/
output lines, and power cables through the same conduit, or
twist those cables together, or place the cables near one
another. It can cause malfunction.
Install the main unit away from any sources of electrical
noise.
Avoid installing in any locations where the unit may come
into contact with water, or in any extremely humid locations.
Avoid installing in any location that is subject to excessive
vibration or physical impacts.

(1) After determining the attachment position, secure the

installation hardware as shown in the dimensions diagram. If
the included screws will not work for the installation, prepare
appropriate screws (such as metric ones) for use at the site.

(2) Attach the main unit and fasten the installation hardware as

illustrated.

(3) If the installation hardware is loose or appears like it will fall

out, remove the upper case on the unit and secure with
screws in the failsafe screw holes.

1

Power supply line

Содержание CZ-CFUNC2

Страница 1: ...ons or attachments are not secure Depending on the installation conditions and location an earth leakage breaker may be required If an earth leakage breaker is not installed there is a danger of electric shock or fire The installation location requires the use of a circuit breaker Failure to use a circuit breaker may result in electric shock or fire Circuit breaker must be incorporated in the fixe...

Страница 2: ...ure to ground only one end of the shielding The overall length of each line should be 1 km or less Do not run the communication line through the same conduit as the power supply use the same cable as the power supply or run close to the power supply line maintain at least 30 cm separation Do not run the LINK1 and LINK2 signal lines through the same conduit use the same cable for wiring or run them...

Страница 3: ...s a maximum restriction of seven units 7 Make sure that high voltage ex 230 V AC lines are not connected to the Communication Adaptor control wire or the inter unit control wiring terminals If high voltage AC is accidentally applied to the inter unit control wiring terminals a fuse will blow to protect the controller board If this happens disconnect the AC line and connect the U2 terminal wire of ...

Страница 4: ... 2 Adaptor number setting procedure Hold down the HOME key for at least two seconds so the initial display shows as follows no 00 After 2 seconds AdP dt Press the UP key five times so the following display appears no 05 This automatically switches to the below display after 2 more seconds Operation is not necessary FirSt Press the SET key so the below display appears Only the green monitor LED is ...

Страница 5: ...irm Only the green monitor LED is on 4 Other settings With the display status showing as in number in section 2 Adaptor number setting procedure press the UP and DOWN keys to select the setting items shown in the table below Set as needed The setting procedure is the same as above Press the SET key for at least 1 second press the UP and DOWN keys to change then press the SET key at least one secon...

Страница 6: ... the air conditioner is on and any LINK not connected is off For solo installation pulse meter dedicated use x 3 LINK1 and 2 both set to off 1 Ano xx 3 Base unit settings Always use 0 the initial value 2 AdYu x 3 Cont x 4 CAn1 x 5 CAn2 x 6 PUL xx 7 LoCA x 8 SCAn x 4 Settings for the number of Communication Adaptor units in one link part 1 x 0 to 7 x 0 First Communication Adaptor in the LINK1 link ...

Страница 7: ...that may be susceptible to electrical noise use a two conductor shielded cable with one line grounded with a cross section at least 0 5 mm2 Do not apply external voltages to the input terminals About 10 mA of 5 V DC voltage is applied to the contact point for input terminal detection The output terminal allowable contact voltage and current are 30 V DC and 0 5 A All stop input All operation input ...

Страница 8: ...is setting is required for two or more Communication Adaptors Two links can be connected to a Communication Adaptor For links without an air conditioner or other such connection set the LINK to off The Intelligent Controller can be connected to only four links that are set to be active Refer to the number 3 Setting the inter unit control wiring connection on off in section 4 Setting the Communicat...

Отзывы: