(3) Setting the inter-unit control wiring connection on/off

Repeat steps   to   in section (2) “Adaptor number setting procedure” above. The following will display:

  (1.Ano.03) (When the adaptor number is 3)

Press the 

UP

 key once so the following display appears:

  (2.Adyu.0) (Factory setting)

Hold down the 

SET

 key for at least 1 second so the “0” part blinks, indicating that the setting can be changed. (The green and red monitor

LEDs are both on.)

Use the 

UP

 and 

DOWN

 keys to turn the inter-unit control wiring connection on or off as shown in the table below.

For example, to connect the inter-unit control wiring only to LINK1, press the 

UP

 key once. The following display will result:

  (2.AdYu.1)

Press the 

SET

 key for at least 1 second to confirm. (Only the green monitor LED is on.)

(4) Other settings

With the display status showing as in number   in section (2) “Adaptor number setting procedure”, press the 

UP

 and 

DOWN

 keys to select

the setting items shown in the table below.  Set as needed.
The setting procedure is the same as above.
(Press the 

SET

 key for at least 1 second, press the 

UP

 and 

DOWN

 keys to change, then press the 

SET

 key at least one second to confirm.)

Note

When configuring, do not set the same adaptor number more than once.
*

Use numbers between 1 and 7 for connecting to an Intelligent Controller.

Turn the inter-unit control wiring connection on/off as appropriate.
(Set to “Off” for LINKs with no connection.)
For connecting the inter-unit control wiring to only one link, use the
“LINK1” side.

Setting value

Inter-unit control wiring connection

0

LINK1: On, LINK2: On (factory setting)

1

LINK1: On, LINK2: Off

2

LINK1: Off, LINK2: On

3

LINK1: Off, LINK2: Off

1

2

3

1

1

2

3

3

3

4

Содержание CZ-CFUNC2

Страница 1: ...ons or attachments are not secure Depending on the installation conditions and location an earth leakage breaker may be required If an earth leakage breaker is not installed there is a danger of electric shock or fire The installation location requires the use of a circuit breaker Failure to use a circuit breaker may result in electric shock or fire Circuit breaker must be incorporated in the fixe...

Страница 2: ...ure to ground only one end of the shielding The overall length of each line should be 1 km or less Do not run the communication line through the same conduit as the power supply use the same cable as the power supply or run close to the power supply line maintain at least 30 cm separation Do not run the LINK1 and LINK2 signal lines through the same conduit use the same cable for wiring or run them...

Страница 3: ...s a maximum restriction of seven units 7 Make sure that high voltage ex 230 V AC lines are not connected to the Communication Adaptor control wire or the inter unit control wiring terminals If high voltage AC is accidentally applied to the inter unit control wiring terminals a fuse will blow to protect the controller board If this happens disconnect the AC line and connect the U2 terminal wire of ...

Страница 4: ... 2 Adaptor number setting procedure Hold down the HOME key for at least two seconds so the initial display shows as follows no 00 After 2 seconds AdP dt Press the UP key five times so the following display appears no 05 This automatically switches to the below display after 2 more seconds Operation is not necessary FirSt Press the SET key so the below display appears Only the green monitor LED is ...

Страница 5: ...irm Only the green monitor LED is on 4 Other settings With the display status showing as in number in section 2 Adaptor number setting procedure press the UP and DOWN keys to select the setting items shown in the table below Set as needed The setting procedure is the same as above Press the SET key for at least 1 second press the UP and DOWN keys to change then press the SET key at least one secon...

Страница 6: ... the air conditioner is on and any LINK not connected is off For solo installation pulse meter dedicated use x 3 LINK1 and 2 both set to off 1 Ano xx 3 Base unit settings Always use 0 the initial value 2 AdYu x 3 Cont x 4 CAn1 x 5 CAn2 x 6 PUL xx 7 LoCA x 8 SCAn x 4 Settings for the number of Communication Adaptor units in one link part 1 x 0 to 7 x 0 First Communication Adaptor in the LINK1 link ...

Страница 7: ...that may be susceptible to electrical noise use a two conductor shielded cable with one line grounded with a cross section at least 0 5 mm2 Do not apply external voltages to the input terminals About 10 mA of 5 V DC voltage is applied to the contact point for input terminal detection The output terminal allowable contact voltage and current are 30 V DC and 0 5 A All stop input All operation input ...

Страница 8: ...is setting is required for two or more Communication Adaptors Two links can be connected to a Communication Adaptor For links without an air conditioner or other such connection set the LINK to off The Intelligent Controller can be connected to only four links that are set to be active Refer to the number 3 Setting the inter unit control wiring connection on off in section 4 Setting the Communicat...

Отзывы: