Appendix A. Connecting to an Intelligent Controller

Before making the initial settings for the Communication Adaptor, check to ensure the below
operations are complete.

(1) Is the air conditioner test operation complete?
(2) Is the wiring for the air conditioner and the Communication Adaptor complete?

To set, follow steps 1 to 5 below in sequence.

This is a required setting.

Set the address for the Communication Adaptor control wire.
For the Intelligent Controller internal board, the address is 0. Set a value between 1
and 7 for the external adaptor, ensuring no value is used twice.
Refer to the number (2) “Adaptor number setting procedure” in section  4  “Setting
the Communication Adaptor board”.
*

Refer to Table 1 [1].

Complete!

(1) Adaptor number setting

(2) Inter-unit control wiring

connection setting

(3) Number of Communication

Adaptor units in one link
setting

(4) Minimum pulse input

detection time setting

(5) Interface Adaptor connection

setting

This setting is required for two or more Communication Adaptors.

Two links can be connected to a Communication Adaptor.
For links without an air conditioner or other such connection, set the LINK to “off”.
The Intelligent Controller can be connected to only four links that are set to be active.
Refer to the number (3) “Setting the inter-unit control wiring connection on/off” in
section  4  “Setting the Communication Adaptor board”.
*

Refer to Table 1 [2].

This setting is required only for using an Intelligent Controller in conjunction
with a AMY Software.

When adding another Communication Adaptor to the inter-unit control wiring,
the adaptor address for the added unit needs to be changed.
*

Refer to Table 1 [4] and [5].

This setting is not required if pulse input (P1, P2, P3) is not used.

Use a pulse meter whose minimum pulse width is normally at least 100 msec.
If and only if a pulse meter 30 msec or higher must be used, use this setting.
*

Refer to Table 1 [6].

By not using a Interface Adaptor, the configuration confirmation time can be shortened.

Not using this setting will not affect operation of the device.

*

Refer to Table 1 [7].

85464369352011

Printed in Japan

Содержание CZ-CFUNC2

Страница 1: ...ons or attachments are not secure Depending on the installation conditions and location an earth leakage breaker may be required If an earth leakage breaker is not installed there is a danger of electric shock or fire The installation location requires the use of a circuit breaker Failure to use a circuit breaker may result in electric shock or fire Circuit breaker must be incorporated in the fixe...

Страница 2: ...ure to ground only one end of the shielding The overall length of each line should be 1 km or less Do not run the communication line through the same conduit as the power supply use the same cable as the power supply or run close to the power supply line maintain at least 30 cm separation Do not run the LINK1 and LINK2 signal lines through the same conduit use the same cable for wiring or run them...

Страница 3: ...s a maximum restriction of seven units 7 Make sure that high voltage ex 230 V AC lines are not connected to the Communication Adaptor control wire or the inter unit control wiring terminals If high voltage AC is accidentally applied to the inter unit control wiring terminals a fuse will blow to protect the controller board If this happens disconnect the AC line and connect the U2 terminal wire of ...

Страница 4: ... 2 Adaptor number setting procedure Hold down the HOME key for at least two seconds so the initial display shows as follows no 00 After 2 seconds AdP dt Press the UP key five times so the following display appears no 05 This automatically switches to the below display after 2 more seconds Operation is not necessary FirSt Press the SET key so the below display appears Only the green monitor LED is ...

Страница 5: ...irm Only the green monitor LED is on 4 Other settings With the display status showing as in number in section 2 Adaptor number setting procedure press the UP and DOWN keys to select the setting items shown in the table below Set as needed The setting procedure is the same as above Press the SET key for at least 1 second press the UP and DOWN keys to change then press the SET key at least one secon...

Страница 6: ... the air conditioner is on and any LINK not connected is off For solo installation pulse meter dedicated use x 3 LINK1 and 2 both set to off 1 Ano xx 3 Base unit settings Always use 0 the initial value 2 AdYu x 3 Cont x 4 CAn1 x 5 CAn2 x 6 PUL xx 7 LoCA x 8 SCAn x 4 Settings for the number of Communication Adaptor units in one link part 1 x 0 to 7 x 0 First Communication Adaptor in the LINK1 link ...

Страница 7: ...that may be susceptible to electrical noise use a two conductor shielded cable with one line grounded with a cross section at least 0 5 mm2 Do not apply external voltages to the input terminals About 10 mA of 5 V DC voltage is applied to the contact point for input terminal detection The output terminal allowable contact voltage and current are 30 V DC and 0 5 A All stop input All operation input ...

Страница 8: ...is setting is required for two or more Communication Adaptors Two links can be connected to a Communication Adaptor For links without an air conditioner or other such connection set the LINK to off The Intelligent Controller can be connected to only four links that are set to be active Refer to the number 3 Setting the inter unit control wiring connection on off in section 4 Setting the Communicat...

Отзывы: