25

(EN)

• 

Use only a single wiring or stranded wiring.

• 

Wiring tip arrangement.

•  Arrange the external output wiring as well.

Connecting External Equipment

 

„

External Input Wiring

 

z

Type of wiring

Use a flexible wiring of 0.5 to 0.75 mm

2

.

 

z

Total Wire Length

100 m or less

If a longer length is needed,use a relay.

 

„

ConnectionSpecifications

COM

   1

   2

   3

 

„

External Output Wiring

 

z

Exteranl output wiring specification is the same as exteranal input wiring .

 

z

When outputting the operation status or alarm status, a 12 V DC external power 

source for relays is required.

• Recommended product: COSEL PBA10F-12 

• 

Allowable wattage: 15 W or less

 

z

Use the following specifications for DC power wiring.

• Type of wiring: Use a flexible wiring of 0.5 to 0.75 mm

2

• 

Arrange the power line as short as possible.

 

„

ConnectionSpecifications

Attention

   4

   6

   7

   8

+

-

   5

Status 

output

Voltage contact “a”

Static (Relay output)
• 

Contact allowable 

voltage:

Max. DC12 V

• 

Contact allowable 

current:

Max. 100 mA

• 

Minimum application 

load:DC5 V 1 mA

Common (COM)

DC power + 

(DC 12 V +)

DC power - 

(DC 12 V -)

Alarm output 

(OUT 1)

Operation Output 

(OUT 2)

DC power 

(12 V)

Coil

Relay

Relay

Controller side

External equipment side

Condition

Circuit example

Terminal

Terminal name

Condition

DC Power 

input

Non-voltage contact 
“a” Static or Pulse 

There is a polarity.

(Make sure that the 

polarity (+/-) is correct 
before connecting.)

• 

Power Supply  

for relays 

(Supply 12 V DC 

externally)

Controller side

External equipment side

Condition

Circuit example

Terminal

Terminal name

Condition

Control 

input

Non-voltage contact “a”

Static or Pulse

• 

Contact allowable 

voltage: 

DC5 V ± 10%

• 

Contact allowable 

current: 

Max. 10 mA

Input 1 (IN 1)

Input 2 (IN 2)

Common (COM)

• 

Pulse width: 

300 msec or 

more

• 

Rated coil voltage: 

12 V DC

Wiring

9 mm~10 mm

ENGLISH

Содержание CZ-CAPRA1

Страница 1: ...a 10 lezen PORTUGUÊS 62 68 Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação Em particular é necessário ler as informações na secção Precauções de segurança na página 11 TÜRKÇE 69 75 Kuruluma başlamadan önce Kurulum Talimatlarını baştan sona okuyun Özellikle 12 sayfadaki Güvenlik Önlemleri kısmını okumanız gerekecektir POLSKI 76 82 Przed przystąpieniem do instala...

Страница 2: ...rred due to the unauthorised installation methods are not covered by the product warranty z z This controller shall be installed in accordance with National Wiring Regulations z z Read the installation instructions of devices to be connected as well z z When relocating or repairing this controller provide the Installation Instructions to the servicing personnel WARNING z z Turn off the circuit bre...

Страница 3: ...5 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a parti...

Страница 4: ...ng operations from the central control device can be performed z z Operations to start stop the room air conditioner switch the operation mode and set the temperature fan speed and fan direction up down z z Monitoring the operation status and abnormality of room air conditioner z z Prohibiting the remote control operation of room air conditioner z z Using ON OFF contact of external connection can ...

Страница 5: ...21 z zBasic Wiring Diagram 22 z zMounting and Wiring 23 z zConnecting External Equipment 25 z zSetup 26 CONTENTS Dimensions RAC connection wiring 1 5P White 4P Red Length 1 9 m Screw 4 M3 8 x 16 Installation Instructions 1 Clamper 3 70 120 32 5 mm 108 35 Installation Precautions Installation Location z z Avoid the following locations for installation Location where the controller will be splashed ...

Страница 6: ...Normal Blinking Abnormal OFF No power is supplied from the room air conditioner 2 2 1 While pushing the push button by using a round bar or finger insert the external I O wiring securely from the wiring insertion slot 2 Pull the external I O wiring lightly and confirm it does not come off Be sure to set the termination plug 1 If using one outdoor unit set the termination resistor to SHORT at one l...

Страница 7: ...e wiring coat 2 Cover with the tape 3 Attach ring pressure terminal Shield mesh Strip Shield mesh Insulation tape Attention Ground the shield on both sides of shield wiring otherwise an operation error from noise may occur Shield wiring Ground Ground Mounting and Wiring Method 1 Connect the RAC connection wiring supplied to the room air conditioner For attachment removal of the front panel grille ...

Страница 8: ...connecting external equipment Connect the external I O wiring P 25 Cut here with a nipper and remove the burr with a file As shown in step 4 or 5 pass the clamper supplied through the hole and fix the wiring z z When the settings are complete P 26 attach the top case Case fixing screws Top case Bottom case Clamper supplied Pass through the hole Clamper supplied Functional ground FG Pass through th...

Страница 9: ...short as possible Connection Specifications Attention 4 6 7 8 5 Status output Voltage contact a Static Relay output Contact allowable voltage Max DC12 V Contact allowable current Max 100 mA Minimum application load DC5 V 1 mA Common COM DC power DC 12 V DC power DC 12 V Alarm output OUT 1 Operation Output OUT 2 DC power 12 V Coil Relay Relay Controller side External equipment side Condition Circui...

Страница 10: ...uit Remote control operation is prohibited Open circuit Remote control operation is permitted OFF ON Input 1 Start stop signal Pulse Open circuit Short circuit 300 ms or more With Open the start stop status is reversed Start Stop Input 2 Signal Static prohibiting remote control Short circuit Remote control opera tion is prohibited Open circuit Remote control operation is permitted Be sure to turn ...

Отзывы: