12. Protection
Control
12.1 Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
12.2 7 Minutes Time Save Control
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON temperature (A) and compressor OFF temperature (B) during the period.
This phenomenon is to reduce the built up humidity inside a room.
12.3 60 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON operation button at the remote control is permitted.
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full
cycle and return back to the outdoor unit.
12.4 Freeze Preventive Control
If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the
compressor turns off. The fan speed setting remains the same.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of
refrigerant in liquid form returning to the compressor.
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
Содержание CS-ZC15MKY-3
Страница 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 8: ...8 4 Dimensions 4 1 Indoor Unit Remote Control ...
Страница 9: ...9 4 2 Outdoor Unit ...
Страница 10: ...10 5 Refrigeration Cycle Diagram ...
Страница 11: ...11 6 Block Diagram ...
Страница 13: ...13 8 Electronic Circuit Diagram ...
Страница 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 15: ...15 9 1 2 Indicator Printed Circuit Board ...
Страница 18: ...18 10 2 3 Indoor Unit Installation 1 For the Right and Right Bottom Piping 2 For the Embedded Piping ...
Страница 34: ...34 ...
Страница 35: ...35 15 2 Evaporator Complete Indoor Propeller Fan and Indoor Fan Motor Removal Procedures ...
Страница 36: ...36 Caution Becareful the sharp edges of Fan Motor Bracket it may cause injury ...
Страница 37: ...37 16 Technical Data 16 1 Thermostat Characteristics Cooling ...
Страница 38: ...38 16 2 Operation Characteristics 16 2 1 CS ZC15MKY 3 CU ZC15MKY 3 ...
Страница 39: ...39 ...
Страница 40: ...40 16 2 2 CS ZC20MKY 3 CU ZC20MKY 3 ...
Страница 41: ...41 ...