e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over fi ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been fi lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.To avoid fi re or 
explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains fl ammable 
refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of fl ammable 
refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that fl ammable refrigerant does not 
remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

Safety precautions

Содержание CS-Z20VKR

Страница 1: ...The included Installation Instructions should be kept and read by the installer before installation Remote control is packaged in the indoor unit and removed by the installer before installation Model No Indoor Unit Outdoor Unit CS Z20VKR CS Z25VKR CS Z35VKR CS Z42VKR CS Z50VKR CS Z60VKR CS Z71VKR CS Z80VKR CU Z20VKR CU Z25VKR CU Z35VKR CU Z42VKR CU Z50VKR CU Z60VKR CU Z71VKR CU Z80VKR ACXF55 2238...

Страница 2: ...e indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press and set the time Press and hold for approximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm ON OFF SET CANCEL FAN SPEED MODE AIR SWING TEMP A B ...

Страница 3: ...er from the actual unit They are subject to change without notice for future improvement B Basic operation 1 Press MODE to select the desired mode AUTO HEAT COOL FAN i AUTO X DRY 2 Press OFF ON to start stop the operation POWER Please note that the indication is on display to start the unit 3 Select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for app...

Страница 4: ...age of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit method or using incompatible material may cause product damage burst and serious injury Do not install the unit in a potentially explosive or flamm...

Страница 5: ...s plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoid injury etc Do not touch the sharp aluminium fin sharp parts may cause injury Do not switch ON the indoor unit when waxing the floor After waxing aerate the room properly befo...

Страница 6: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and ce...

Страница 7: ...llow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size wit...

Страница 8: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations u...

Страница 9: ... supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensu...

Страница 10: ...ommenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent person recovery equipment and cylin...

Страница 11: ...nsure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are evacuated and if p...

Страница 12: ...cally after 4 hours QUIET To enjoy quiet operation This operation reduces airflow noise To improve humidity and moisture level This operation reduces air dryness and provides you with a comfortable living environment during COOL mode only When vertical airflow direction is set to AUTO it stops at lower position to avoid cold air contact However you can adjust the flap direction manually MILD DRY T...

Страница 13: ...of ON and OFF timers are available to turn ON or OFF the unit at different preset times How to use The unit controls set temperature according to room temperature to accelerate room cooling After max 4 hours the set temperature is shifted according to activity detection Fan speed is fixed at AUTO fan speed selection is prohibited During unit is off press will turn on the unit with i AUTO X mode i ...

Страница 14: ...and shift to the upper position after reaches set temperature and the vertical flap swing according to activity detection If manual is set the horizontal flap and vertical flap are fixed at the predetermined position In HEAT mode If AUTO is set the horizontal flap is fixed at the predetermined position The vertical flap swings left right after the temperature rises Auto restart control If power is...

Страница 15: ...Dry the filters thoroughly under shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Insert into the unit Aluminium fin Front panel Air filters Indoor unit Wipe the unit gently with a soft dry cloth Coils and fans should be clean for at least every 6 months by an authorised dealer Human activity sensor Do not hit or violently press or poke it wit...

Страница 16: ...pansion contraction of the unit Water flowing sound during operation Refrigerant flow inside the unit Mist emerges from indoor unit Condensation effect due to cooling process Outdoor unit emits water steam Condensation or evaporation occurs on pipes Louder noise at outdoor unit during early operation of i AUTO X The compressor and fan rotate at higher speed to boost cooling performance during init...

Страница 17: ...t vents Use Auto OFF ON button to select COOL HEAT operation After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F HEAT 14 C 25 2 F The units are not going to be used for a long period of time Activate HEAT mode for 2 3 hours to remove moisture left in the internal parts thoroughly to prevent mould growth Turn...

Страница 18: ...ming pool sensor H 32 Outdoor heat exchanger temperature sensor 2 abnormality H 33 Indoor outdoor misconnection abnormality H 34 Outdoor heat sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand code Diagnostic display ...

Страница 19: ...cal symbol In this case it complies with the requirement set by the Directive for the chemical involved Information WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows type of fl...

Страница 20: ...Printed in Malaysia ACXF55 22380 FA0319 0 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2019 ...

Отзывы: