25
10.3.4 Connect the cable to the Outdoor Unit
1
Remove the control board cover from the unit by loosening the screw.
2
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4x
1.5mm
2
flexible cords, type designation 245 IEC 57 or heavier cord.
3
Secure the cable onto the control board with the holder (clamper).
4
Attach the control board cover back to the original position with the screw.
5
For wiring stripping and connection requirement, refer to instruction 10.2.4 of indoor unit.
10.3.5 Pipe
Insulation
1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please warp the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.
Содержание CS-YE12MKE
Страница 11: ...11 5 Dimensions 5 1 Indoor Unit 121 49 Unit mm ...
Страница 12: ...12 5 2 Outdoor Unit Unit mm ...
Страница 13: ...13 6 Refrigeration Cycle Diagram CS CU YE9MKE CS CU YE12MKE CS CU YE18MKE COOLING HEATING ...
Страница 14: ...14 7 Block Diagram CS CU YE18MKE CS CU YE9 12MKE ...
Страница 15: ...15 8 Wiring Diagram CS YE9MKE CS YE12MKE ...
Страница 16: ...16 CU YE9MKE CU YE12MKE ...
Страница 17: ...17 CS YE18MKE ...
Страница 18: ...18 CU YE18MKE ...
Страница 22: ...22 10 2 3 Indoor Unit Installation ...
Страница 40: ...40 14 2 3 Error Codes Table ...
Страница 44: ...44 16 Exploded View and Replacement Pars List 16 1 Indoor Unit CS YE9MKE CS YE12MKE CS YE18MKE ...
Страница 46: ...46 16 2 Outdoor Unit CU YE9MKE CU YE12MKE CU YE18MKE ...