Panasonic CS-WU12VKY Series Скачать руководство пользователя страница 8

8

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 

ensuring that this will not exceed the 

permissible voltage and current permitted for 

the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 

presence of a fl ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts 

specifi ed by the manufacturer. Unspecifi ed 

parts by manufacturer may result ignition of 

refrigerant in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 

vibration, sharp edges or any other adverse 

environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 

sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching 

or detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked fl ame) shall not be used.

7. Leak detection methods

• Electronic leak detectors shall be used 

to detect fl ammable refrigerants, but the 

sensitivity may not be adequate, or may 

need re-calibration.

(Detection equipment shall be calibrated in a 

refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 

refrigerant used.

• Leak detection equipment shall be set at 

a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant 

employed and the appropriate percentage of 

gas (25 % maximum) is confi rmed.

• Leak detection fl uids are suitable for use with 

most refrigerants but the use of detergents 

containing chlorine shall be avoided as the 

chlorine may react with the refrigerant and 

corrode the copper pipe-work.

• If a leak is suspected, all naked fl ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated 

(by means of shut off valves) in a part of the 

system remote from the leak. Oxygen free 

nitrogen (OFN) shall then be purged through 

the system both before and during the 

brazing process.

8. Removal and evacuation

• When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 

procedures shall be used.

However, it is important that best practice is 

followed since fl ammability is a consideration.

The following procedure shall be adhered to:

remove refrigerant -> purge the circuit with inert 

gas -> evacuate -> purge again with inert gas -> 

open the circuit by cutting or brazing

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be “fl ushed” with OFN to 

render the unit safe.

• This process may need to be repeated several times.

• Compressed air or oxygen shall not be used 

for this task.

• Flushing shall be achieved by breaking the 

vacuum in the system with OFN and continuing 

to fi ll until the working pressure is achieved, 

then venting to atmosphere, and fi nally pulling 

down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the fi nal OFN charge is used, the system 

shall be vented down to atmospheric pressure 

to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any ignition sources and there is 

ventilation available.

9. Charging procedures

• In addition to conventional charging procedures, 

the following requirements shall be followed.

 -Ensure that contamination of different 

refrigerants does not occur when using 

charging equipment.

 -Hoses or lines shall be as short as possible to 

minimize the amount of refrigerant contained 

in them.

 -Cylinders shall be kept upright.

 -Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

 -Label the system when charging is complete 

(if not already).

 -Extreme care shall be taken not to over fi ll the 

refrigeration system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior to 

leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 

and discharging the refrigerant.

To avoid fi re or explosion, dissipate static 

electricity during transfer by grounding and 

bonding containers and equipment before 

charging/discharging.

Safety precautions

C

M

Y

CM

MY

CY

CMY

K

ACXF55-2303̲OL.ai   8   11/14/2018   10:08:24 AM

ACXF55-2303̲OL.ai   8   11/14/2018   10:08:24 AM

Содержание CS-WU12VKY Series

Страница 1: ... Thank you for purchasing Panasonic Air Conditioner Installation instructions attached Before operating the unit please read these operating instructions thoroughly and keep them for future reference C SLEEP SLEEP POWERFUL POWERFUL nanoe G nanoe G PURIFIER PURIFIER C M Y CM MY CY CMY K ACXF55 2303 OL ai 1 11 14 2018 10 08 09 AM ACXF55 2303 OL ai 1 11 14 2018 10 08 09 AM ...

Страница 2: ...C M Y CM MY CY CMY K ACXF55 2303 OL ai 2 11 14 2018 10 08 22 AM ACXF55 2303 OL ai 2 11 14 2018 10 08 22 AM ...

Страница 3: ...m from the remote control receiver of the indoor unit FAN DRY Safety precautions 4 9 How to use 10 11 Cleaning instructions 12 Troubleshooting 13 BEE Regulation 14 Information 15 To confirm Press SET or CLOCK again Please note that the OFF indication is as follows POWER FAN nanoe G CHECK CHECK C M Y CM MY CY CMY K ACXF55 2303 OL ai 3 11 14 2018 10 08 23 AM ACXF55 2303 OL ai 3 11 14 2018 10 08 23 A...

Страница 4: ...e that refrigerant may not contain an odour highly recommended to ensure suitable flammable refrigerant gas detectors are present operating and able to warn of a leak Please consult authorised dealer or specialist to clean the internal parts repair install remove and reinstall the unit Improper installation and handing will cause leakage electric shock or fire Confirm with authorised dealer or spe...

Страница 5: ...ls Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrigerant R32 model always replace the conventional piping and flare nuts with the R32 and R410A piping and flare nuts on the outdoor unit side For R32 and R410A the same flare nut on the outdoor...

Страница 6: ...eir competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed o...

Страница 7: ...ce which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures Initial safety checks shall include but ...

Страница 8: ...n When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following procedure shall be adhered to remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazing The refriger...

Страница 9: ...gerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recover...

Страница 10: ... OFF ON the hidden temperature display Hidden display is ON by default when unit is switched on When the display is turn OFF by remote controller It will turn ON automatically for few seconds upon receiving any command from remote or in case of mains power reset To select operation mode AUTO For your convenience COOL To enjoy cool air DRY To dehumidify the environment Unit run with optimised setti...

Страница 11: ... before the actual set time in order to achieve the desired temperature on time Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick guide TIMER 50 30 This operation is to achieve faster cooling This operation stops automatically after 1 hours If AUTO air swing is set the louver swings up down automatically nanoe G start...

Страница 12: ...ning has to be carried out at regular intervals A dirty unit may cause malfunction Please consult authorised dealer Switch off the power supply and unplug before cleaning Do not touch the aluminium fin sharp parts may cause injury Do not use benzine thinner or scouring powder Use only soap pH 7 or neutral household detergent Do not use water hotter than 40 C Indoor unit Wipe the unit gently with a...

Страница 13: ...not functioning properly The unit stops and the TIMER indicator blinks Use remote control to retrieve error code Press for 5 seconds Press for 5 seconds to quit checking Press until you hear 4 beep sound then write down the error code Turn the unit off and reveal the error code to authorised dealer 2 1 3 4 operation but if problem persist please consult authorised dealer with error code For certai...

Страница 14: ...ep c After hearing a beep sound from the Indoor Unit immediately release the Auto OFF ON button on Indoor Unit All this should be done within 5 seconds Turn on the main power supply to unit Testing Guidelines Cooling Test Mode for Full Load 100 and Half Load 50 1 Mode Select COOL 2 Temperature a 16 ºC for Full Load 100 3 Air Swing S 4 Fan speed et vane position to 3rd step from top b 17 ºC for Hal...

Страница 15: ...nasonic com in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should be handed over only to authorized recycler for disposal 3 4 5 6 Keep the product in isolated area after it becomes non functional un repairable so as to prevent its accidental breakage Provid...

Страница 16: ...urce there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel should be handling this equipment with reference to the Installation Instructions This symbol shows that there is information included in the Operation Instructions and or Installation Instructions C M Y CM MY CY CMY K ACXF55 2303 OL ai 16 11...

Отзывы: