Panasonic CS-RZ25WKRW Скачать руководство пользователя страница 11

11

English

e) If a vacuum is not possible, make a manifold 

so that refrigerant can be removed from 
various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over fi ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been fi lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.To avoid fi re or 
explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains fl ammable 
refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of fl ammable 
refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that fl ammable refrigerant does not 
remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

Safety precautions

ACXF55-28780_SS0720-0.indd   11

25/6/2020   11:10:08 AM

Содержание CS-RZ25WKRW

Страница 1: ...ckaged in the indoor unit and removed by the installer before installation Kindly consult authorised dealer for connectivity validity Operating Instructions Air Conditioner Model No Indoor Unit Outdoo...

Страница 2: ...time Press and hold for approximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm SET Flexibility to connect Single Split System or Multi Split System Air Conditioner to su...

Страница 3: ...nit They are subject to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode AUTO HEAT COOL FAN DRY 1 Press OFF ON OFF ON to start stop the operation...

Страница 4: ...usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean...

Страница 5: ...d animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or...

Страница 6: ...taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants a...

Страница 7: ...12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a...

Страница 8: ...re 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenanc...

Страница 9: ...ected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operati...

Страница 10: ...with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refrigerant cylinde...

Страница 11: ...er of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the...

Страница 12: ...aving without sacrificing comfort To switch between POWERFUL ECO POWERFUL ECO Upper direction Do not adjust the flap by hand Lateral direction For lateral direction it is manually adjustable as shown...

Страница 13: ...ll activate in sequence Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick Guide 2 sets of ON and OFF timers are availab...

Страница 14: ...em which HEAT mode has been locked if operation mode other than HEAT is selected the indoor unit stops and the POWER indicator blinks COOL Provides efficient comfort cooling to suit your needs DRY Uni...

Страница 15: ...BT DBT WBT DBT WBT COOL Max 32 89 6 23 73 4 46 114 8 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 15 5 0 16 3 2 DBT...

Страница 16: ...r filter Attach air filter Insert into the unit Anti bacterial filter Anti bacterial filter Clean the filter whenever necessary Wash rinse the filter gently with water to avoid damage to the filter Dr...

Страница 17: ...ue to damp smell emitted by the wall carpet furniture or clothing Cracking sound during operation Changes of temperature caused the expansion contraction of the unit Water flowing sound during operati...

Страница 18: ...select COOL HEAT operation After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F HEAT 14 C 25 2 F The units ar...

Страница 19: ...sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdo...

Страница 20: ...ows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Inst...

Отзывы: