background image

117 

CU-PS9NKH CU-PS12NKH 

REF. NO. 

PART NAME & DESCRIPTION 

QTY. 

Malaysia 

REMARK 

1 CHASSIS 

ASSY 

CWD50C1727 

CWD50K2107 

 

ANTI - VIBRATION BUSHING 

CWH501038 

CWH50077 

 

3 COMPRESSOR 

1  5SS072XGA21 

5RS092XCE21 

NUT - COMPRESSOR MOUNT 

CWH56000J 

 

 

SOUND PROOF MATERIAL 

CWG302497 

 

SOUND PROOF MATERIAL 

CWG302496 

 

6a 

SOUND PROOF MATERIAL 

CWG302700 

CWG302564 

 

FAN MOTOR BRACKET 

CWD541075 

CWD541074 

 

8 FAN 

MOTOR 

CWA951702 

 O 

SCREW - FAN MOTOR BRACKET 

CWH551217 

 

 

10 

SCREW - FAN MOTOR MOUNT 

CWH55252J 

 

 

11 PROPELLER 

FAN 

ASSY 

CWH03K1020 

 

 

12 

NUT - PROPELLER FAN 

CWH56053J 

 

 

13 CONDENSER 

CWB32C2974 

CWB32C2972 

 

14 

CAPILLARY TUBE ASSY 

CWB15K1297 

CWB15K1302 

 

15 STRAINER 

CWB11025 

 

 

16 HOLDER 

COUPLING 

CWH351047 

 

 

17 3-WAY 

VALVE 

(GAS) 

CWB011580 

CWB011677 

18 2-WAYS 

VALVE 

(LIQUID) 

CWB021463 

 O 

19 

SOUND PROOF BOARD 

CWH151185 

 

 

20 TERMINAL 

COVER 

CWH171041 

CWH171039A 

 

21 

NUT - TERMINAL COVER 

CWH7080300J 

 

22 

SENSOR CO-COMP TEMP 

CWA50C2205 

 O 

24 

SENSOR CO-AIR TEMP AND PIPE TEMP 

CWA50C2502 

 O 

25 

TERMINAL BOARD ASSY 

CWA28K1036J 

 O 

26 

ELECTRONIC CONTROLLER - MAIN 

CWA73C6302R 

CWA73C6303R 

27 

ELECTRONIC CONTROLLER - NF 

CWH14C7640 

CWH14C6052 

28 

CONTROL BOARD COVER-TOP 

CWH131324 

 

 

29 

CABINET SIDE PLATE CO. 

CWE04C1149 

 

 

30 

CABINET SIDE PLATE (LEFT) 

CWE041205A 

 

 

31 

CABINET FRONT PLATE CO. 

CWE06K1059 

 

 

32 

CABINET TOP PLATE 

CWE031041A 

 

 

33 

CONTROL BOARD COVER CO. 

CWH13C1186 

 

 

34 

DISCHARGE MUFFLER (EXP VALVE) 

CWB121010 

 

 

35 

PLATE - C. B. COVER TERMINAL 

CWH131325 

 

 

36 PLATE 

SPRING 

CWH71044 

 

37 BAG 

CWG861216 

 

 

38 BASE 

BOARD-COMPLETE 

CWG62C1046 

 

 

39 

SHOCK ABSORBER (LEFT) 

CWG712435 

 

 

40 

SHOCK ABSORBER (RIGHT) 

CWG712437 

 

 

41 C.C.CASE 

CWG567536 

CWG567537 

 

 
(Note) 

š

  All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488). 

š

  “O” marked parts are recommended to be kept in stock. 

 
 
 
 
 
 
 
 
 
 
 

Содержание CS-PS9NKH

Страница 1: ...y the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be serv...

Страница 2: ...trol 54 11 6 Random Auto Restart Control 54 11 7 Indication Panel 54 12 Protection Control 55 12 1 Restart Control Time Delay Safety Control 55 12 2 30 Seconds Forced Operation 55 12 3 Total Running C...

Страница 3: ...ire 9 This equipment is strongly recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakd...

Страница 4: ...5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a...

Страница 5: ...9 1 28k Starting Current A 3 7 5 0 Type Hermetic Motor Hermatic Motor Motor Type Brushless 6 poles Brushless 6 poles Compressor Output Power W 500 650 Type Cross flow fan Cross flow fan Material ASG2...

Страница 6: ...ted Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 15 x 17 2 x 15 x 17 Indoor Heat Exchanger Size W x H x L mm 610 x 315 x 25 4 610 x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue coa...

Страница 7: ...650 Type Cross flow fan Cross flow fan Material ASG20K1 ASG20K1 Motor Type Transistor 8 poles Induction 4 poles Input Power W 47 0 50 0 47 0 50 0 Output Power W 40 24 Lo rpm 680 720 Me rpm 840 900 In...

Страница 8: ...0 x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue coated Fin Type Louver Fin Slit Fin Row x Stage x FPI 1 x 19 x 17 2 x 23 x 17 Outdoor Heat Exchanger Size W x H x L mm 25 4 x 482 6 x 5...

Страница 9: ...900 900 Type Cross flow fan Cross flow fan Material ASG20K1 ASG30K1 Motor Type Transistor 8 poles Transistor 8 poles Input Power W Output Power W 40 40 Lo rpm 850 930 Me rpm 1090 1120 Indoor Fan Spee...

Страница 10: ...10 x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 23 x 17 1 x 31 x 19 Outdoor Heat Exchanger Size W x H x L mm 25 4 x 504 x 693...

Страница 11: ...ut Power W 900 900 Type Cross flow fan Cross flow fan Material ASG20K1 ASG30K1 Motor Type Transistor 8 poles Transistor 8 poles Input Power W Output Power W 40 40 Lo rpm 850 930 Me rpm 1090 1120 Indoo...

Страница 12: ...10 x 315 x 25 4 Fin Material Aluminium Blue coated Aluminium Blue coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 23 x 17 1 x 31 x 19 Outdoor Heat Exchanger Size W x H x L mm 25 4 x 504 x 693...

Страница 13: ...13 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...

Страница 14: ...14 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9NKH CS PS12NKH CS PS18NKH...

Страница 15: ...15 4 1 2 CS PS24NKH...

Страница 16: ...16 4 2 Outdoor Unit 4 2 1 CU PS9NKH CU PS12NKH 4 2 2 CU PS18NKH...

Страница 17: ...17 4 2 3 CU PS24NKH...

Страница 18: ...18 5 Refrigeration Cycle Diagram 5 1 CS PS9NKH CU PS9NKH CS PS12NKH CU PS12NKH...

Страница 19: ...19 5 2 CS PS18NKH CU PS18NKH CS PS24NKH CU PS24NKH...

Страница 20: ...20 6 Block Diagram 6 1 CS PS9NKH CU PS9NKH...

Страница 21: ...21 6 2 CS PS12NKH CU PS12NKH...

Страница 22: ...22 6 3 CS PS18NKH CU PS18NKH...

Страница 23: ...23 6 4 CS PS24NKH CU PS24NKH...

Страница 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS PS9NKH CS PS18NKH CS PS24NKH...

Страница 25: ...25 7 1 2 CS PS12NKH...

Страница 26: ...26 7 2 Outdoor Unit 7 2 1 CU PS9NKH Resistance of Compressor Windings MODEL CU PS9NKH CONNECTION 5SS072XGA21 U V 3 034 U W 3 021 V W 3 009...

Страница 27: ...27 7 2 2 CU PS12NKH Resistance of Compressor Windings MODEL CU PS12NKH CONNECTION 5RS092XCE21 U V 1 152 U W 1 152 V W 1 152...

Страница 28: ...28 7 2 3 CU PS18NKH Resistance of Compressor Windings MODEL CU PS18NKH CONNECTION 5RD132XDA21 U V 1 152 U W 1 152 V W 1 152...

Страница 29: ...29 7 2 4 CU PS24NKH Resistance of Compressor Windings MODEL CU PS24NKH CONNECTION 5RD132XBA21 U V 1 897 U W 1 907 V W 1 882...

Страница 30: ...30 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9NKH CS PS18NKH CS PS24NKH...

Страница 31: ...31 8 1 2 CS PS12NKH...

Страница 32: ...32 8 2 Outdoor Unit 8 2 1 CU PS9NKH...

Страница 33: ...33 8 2 2 CU PS12NKH...

Страница 34: ...34 8 2 3 CU PS18NKH...

Страница 35: ...35 8 2 4 CU PS24NKH...

Страница 36: ...36 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board 9 1 1 1 CS PS9NKH CS PS18NKH CS PS24NKH...

Страница 37: ...37 9 1 1 2 CS PS12NKH 9 1 2 Indicator Printed Circuit Board...

Страница 38: ...38 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9 12NKH...

Страница 39: ...39 9 2 1 2 CU PS18NKH...

Страница 40: ...40 9 2 1 3 CU PS24NKH...

Страница 41: ...41 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9NKH CU PS12NKH...

Страница 42: ...ed installation height for indoor unit shall be at least 2 5 m 10 1 2 Outdoor Unit If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the conden...

Страница 43: ...ligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Putting measuring tape at position as shown in the diagram above The hol...

Страница 44: ...2 3 Indoor Unit Installation 10 2 3 1 For the right rear piping 10 2 3 2 For the right and right bottom piping 10 2 3 3 For the embedded piping This can be used for left rear piping and bottom piping...

Страница 45: ...e existing wire from concealed wiring or otherwise is too short o In unavoidable case joining of power supply cord between isolating devices and terminal board of air conditioner shall be done by usin...

Страница 46: ...se grille door by tighten with screw and close the front panel Note Isolating Devices Disconnecting means should have minimum 3 0 mm contact gap Ensure the colour of wires of outdoor unit and the term...

Страница 47: ...47 10 2 5 Wire Stripping And Connecting Requirement...

Страница 48: ...tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with to...

Страница 49: ...he gauge moves from 0 cmHg 0 MPa to 76 cmHg 0 1 MPa Then evacuate the air approximately ten minutes 4 Close the Low side valve of the charging set and turn off the vacuum pump Make sure that the needl...

Страница 50: ...to instruction 10 2 4 of the indoor unit Earth wire shall be Yellow Green Y G in colour and longer than the other AC wires for safety reason 10 3 5 Piping Insulation 1 Please carry out insulation at...

Страница 51: ...supplied to the unit 11 1 2 Cooling Operation 11 1 2 1 Thermostat control Compressor is OFF when intake Air Temperature Internal Setting Temperature 0 5 C Compressor is ON after waiting for 3 minutes...

Страница 52: ...Medium Lower 1 pattern 10s Feedback control o Immediately after the fan motor is started feedback control is performed once every second o During fan motor on if fan motor feedback 2550 rpm or 50 rpm...

Страница 53: ...1 2 3 4 5 Automatic 5 35 Cooling Manual 5 12 5 20 27 5 35 Automatic 5 35 Dry Manual 5 12 5 20 27 5 35 Automatic vertical airflow direction can be set using remote control the vane swings up and down...

Страница 54: ...ncelled 2 To cancel the previous timer setting press CANCEL button 3 To activate the previous timer setting press SET button 4 If main power supply is switched off the Timer setting will be cancelled...

Страница 55: ...r 5 seconds the frequency instructed will be increased However if total outdoor unit running current exceeds Y value compressor will be stopped immediately for 3 minutes Model PS9 PS12 PS18 PS24 Opera...

Страница 56: ...s 30 5 C Remote Control setting 16 C and Hi Fan Speed Control contents o Compressor stops and restart after 3 minutes o If the conditions above happened 2 times within 20 minutes the unit will Stop op...

Страница 57: ...or Compressor stops for freeze prevention control o Either one of the conditions above occurs 5 times in 60 minutes Control contents o Operation stops o Timer LED blinks and H99 indicated 12 13 Dew P...

Страница 58: ...d be selected The indoor unit will only operate when received signal with same transmission code from remote control This could prevent signal interference when there are 2 or more units installed nea...

Страница 59: ...on unit a beep sound is heard as confirmation of transmission code change 13 2 2 RESET RC Button To clear and restore the remote control setting to factory default o Press once to clear the memory 13...

Страница 60: ...Mpa kg cm 2 G Outlet air Temperature C Cooling Mode 0 9 1 2 9 12 12 16 Condition Indoor fan speed High Outdoor temperature 35 C at cooling mode Compressor operate at rated frequency Different in the i...

Страница 61: ...w Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or strainer Short circuit in the indoor unit Heat radiation deficiency of the out...

Страница 62: ...2 3 To Display Memorized Error Code Protective Operation 1 Turn power on 2 Press the CHECK button on the remote control 3 will be displayed on the remote control display Note Display only for No sign...

Страница 63: ...tion protection Insufficient refrigerant Air filter dirty F11 4 way valve switching failure 4 occurrences within 30 minutes 4 way valve v coil F90 System and compressor microcomputer communication err...

Страница 64: ...transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdo...

Страница 65: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 66: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 67: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Страница 68: ...ons A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 1 14A for continuously 20 seconds Malfunction Caused CT de...

Страница 69: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Страница 70: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 71: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 72: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Страница 73: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Страница 74: ...uring heating operation the temperature detected by the indoor pipe temperature sensor is above 60 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat...

Страница 75: ...n control takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Dete...

Страница 76: ...unction Decision Conditions When cooling operation when indoor pipe temperature or indoor heat exchanger temperature sensor is above 45 C Malfunction Caused Faulty connector connection Faulty indoor p...

Страница 77: ...eration of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power...

Страница 78: ...cooling and heating operation running current 0 65A I 1 65A During cooling indoor intake indoor pipe 4 C Malfunction Caused Refrigerant shortage refrigerant leakage Poor compression performance of com...

Страница 79: ...lfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disco...

Страница 80: ...detected by the outdoor pipe temperature sensor Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow Outdoor pipe temperature rise due to defective of outdo...

Страница 81: ...ture data 100 C is detected by the IPM temperature sensor Malfunction Caused IPM overheats due to short circuit of hot discharge air flow IPM overheats due to defective of outdoor fan motor IPM overhe...

Страница 82: ...n of cooling and heating when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve clo...

Страница 83: ...rent Control is detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over current...

Страница 84: ...door unit PCB Troubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a live part make...

Страница 85: ...fficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 15 1 CS PS9 12 18NKH 15 1 1 Indoor Electronic Controllers Cross Flow Fan and Indoor Fan Motor R...

Страница 86: ...86 Figure 3 Figure 4 15 1 3 To remove discharge grille Figure 5 11 Pull out to remove the drain hose from the discharge grille 12 Then pull the discharge grille downward gently to dismantle it...

Страница 87: ...and indoor fan motor Figure 7 Figure 8 13 Remove 4 screws holding the control board then pull out the control board 16 Remove the bearing by pulling it out gently 15 Remove the screw from the evapora...

Страница 88: ...val of cross flow fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 18 Remove the cross flow fan from the unit by pulling it to the l...

Страница 89: ...discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 15 2 CS PS24NKH 15 2 1 Indoor Electronic Controllers Cross Flow Fan and Indoor Fa...

Страница 90: ...90 15 2 3 To remove power electronic controller Figure 13 Figure 14 15 2 4 To remove discharge grille Figure 15...

Страница 91: ...91 15 2 5 To remove control board Figure 16 15 2 6 To remove cross flow fan and indoor fan motor Figure 17 Figure 18...

Страница 92: ...92 Figure 19 Figure 20...

Страница 93: ...800 16 000 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Outlet Air Tempeature C 230 2 200 2 300 2 400 2 500 2 600 2 700 2 800 2 900 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Out...

Страница 94: ...2 800 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 3 600 3 650 3 700 3 750 3 800 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Current A 1 080 1 085 1 090 1 095 1 100 3 4 5 6...

Страница 95: ...39 40 41 42 43 Outdoor Air Temperature C Outlet Air Temperature C 220 240 2 200 2 300 2 400 2 500 2 600 2 700 2 800 2 900 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling C...

Страница 96: ...750 2 800 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 1 080 1 085 1 090 1 095 1 100 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 14 800 14 900...

Страница 97: ...38 39 40 41 42 43 Outdoor Air Temperature C Outlet Air Tempeature C 230 3 100 3 200 3 300 3 400 3 500 3 600 3 700 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity k...

Страница 98: ...3 600 3 700 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 4 900 4 950 5 000 5 050 5 100 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Current A 1 000 1 005 1 010 1 015 3 4 5 6...

Страница 99: ...6 37 38 39 40 41 42 43 Outdoor Air Temperature C Outlet Air Temperature C 220 240 3 100 3 200 3 300 3 400 3 500 3 600 3 700 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling...

Страница 100: ...3 700 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Cooling Capacity kW 1 000 1 005 1 010 1 015 1 020 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 14 300 14 400 14 50...

Страница 101: ...39 40 41 42 43 Outdoor Air Temperature C Outlet Air Tempeature C 230 4 300 4 500 4 700 4 900 5 100 5 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 6 200 6...

Страница 102: ...11 12 13 14 15 16 17 18 19 20 Piping Length m Cooling Capacity kW 6 700 6 800 6 900 7 000 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Current A 1 020 1 030 1 040 1 050 1 060 3 4 5 6...

Страница 103: ...39 40 41 42 43 Outdoor Air Temperature C Outlet Air Temperature C 220 240 4 300 4 500 4 700 4 900 5 100 5 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 6...

Страница 104: ...19 20 Piping Length m Cooling Capacity kW 0 890 0 900 0 910 0 920 0 930 0 940 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Gas Side Piping Pressure MPa 14 800 14 900 15 000 15 100 1...

Страница 105: ...33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Outlet Air Tempeature C 230 5 500 5 700 5 900 6 100 6 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacit...

Страница 106: ...12 13 14 15 16 17 18 19 20 Piping Length m Cooling Capacity kW 8 500 8 600 8 700 8 800 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Current A 0 880 0 890 0 900 0 910 3 4 5 6 7 8 9 10...

Страница 107: ...0 41 42 43 Outdoor Air Temperature C Outlet Air Temperature C 220 240 5 500 5 700 5 900 6 100 6 300 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor Air Temperature C Cooling Capacity kW 7 600 8 100...

Страница 108: ...19 20 Piping Length m Cooling Capacity kW 0 840 0 850 0 860 0 870 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Gas Side Piping Pressure MPa 13 600 13 700 13 800 13 900 14 000 14 100...

Страница 109: ...Replacement Parts List 17 1 Indoor Unit 17 1 1 CS PS9NKH CS PS12NKH CS PS18NKH Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept...

Страница 110: ...1 CWE20C3236 27 BACK COVER CHASSIS 1 CWD933233 28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521096 35 HORI...

Страница 111: ...ETE 1 CWE20C3236 27 BACK COVER CHASSIS 1 CWD933233 28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521096 35 H...

Страница 112: ...112 17 1 2 CS PS24NKH Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 113: ...29 VERTICAL VANE 11 CWE241374 30 CONNECTING BAR RIGHT 1 CWE261263 31 CONNECTING BAR LEFT 1 CWE261260 33 AIR SWING MOTOR 1 CWA981241 O 34 CAP DRAIN TRAY 1 CWH521096 35 HORIZONTAL VANE COMPLETE 1 CWE24...

Страница 114: ...1138 29 VERTICAL VANE 11 CWE241374 30 CONNECTING BAR RIGHT 1 CWE261263 31 CONNECTING BAR LEFT 1 CWE261260 33 AIR SWING MOTOR 1 CWA981241 O 34 CAP DRAIN TRAY 1 CWH521096 35 HORIZONTAL VANE COMPLETE 1 C...

Страница 115: ...115 17 2 Outdoor Unit 17 2 1 CU PS9NKH CU PS12NKH Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 116: ...CWB021463 O 19 SOUND PROOF BOARD 1 CWH151185 20 TERMINAL COVER 1 CWH171041 CWH171039A 21 NUT TERMINAL COVER CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2205 O 24 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA5...

Страница 117: ...3 O 19 SOUND PROOF BOARD 1 CWH151185 20 TERMINAL COVER 1 CWH171041 CWH171039A 21 NUT TERMINAL COVER CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2205 O 24 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2502 O...

Страница 118: ...118 17 2 2 CU PS18NKH Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 119: ...1172 20 TERMINAL COVER 1 CWH171039A 21 NUT TERMINAL COVER 1 CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2205 O 24 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2764 O 25 TERMINAL BOARD ASSY 1 CWA28K1036J O...

Страница 120: ...CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2205 O 24 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2764 O 25 TERMINAL BOARD ASSY 1 CWA28K1036J O 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C6340R O 28 CONTROL BO...

Страница 121: ...121 17 2 3 CU PS24NKH Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service part...

Страница 122: ...WH151257 20 TERMINAL COVER 1 CWH171039A 21 NUT TERMINAL COVER 1 CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2185 O 27 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2769 O 28 REACTOR 1 G0C153J00005 29 TERMIN...

Страница 123: ...22 SENSOR CO COMP TEMP 1 CWA50C2185 O 27 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2769 O 28 REACTOR 1 G0C153J00005 29 TERMINAL BOARD ASSY 1 CWA28K1036J O 30 ELECTRONIC CONTROLLER MAIN 1 CWA73C6341R O...

Отзывы: