Protection Control
1.The compressor will not start for 3 minutes after the stop of the operation.
2.This control is not applicable if the power supply is turned off and turned on again.
A. Time Delay Safety Control
B. 30 Seconds Forced Operation
1.Once the compressor starts operation, it will not stop for 30 seconds.
2.However, it can be stopped using remote controller or Auto Switch on indoor unit.
C. Total Running Current Control
1.When the total outdoor unit running current(AC) exceeds I1 value, the frequency for
compressor will decline.
2. If the running current is less than I1 value for 10 seconds, the frequency for compressor
will increase.
3.However, if the total outdoor running current exceeds 17.0A, compressor will be stopped
immediately for 3 minutes.
Current Value (A)(I1)
38.5
37.5
A
B
D. IPM Protection Control
1.DC Peak Current Control
1>When electric current to IPM exceeds set value of DC17.3
1A,the compressor will stop. It will
restart after three minutes.
2>If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
3>Error code [F99] will be displayed.
2.Overheating Protection Control
When the IPM temperature rises to 90.0
, compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 85
.
Outdoor Piping Temp
PE9DKE
PE1DKE
A
4.5
6.1
B
4.4
6.0
4.0
5.0
4.0
5.0
COOL
HEAT
112
108
105
96
95
Comp OFF
8Hz/45Sec down.
113Hz
Free
Protection Control
E. Compressor Overheating Prevention Control
The frequency is also controlled by the temperature of the compressor.
97
Min.17Hz
CS-PE9DKE / CU-PE9DKE / CS-PE12DKE / CU-PE12DKE