Safety precautions

6. Detection of fl ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked fl ame) shall not be used.

7.  The following leak detection methods 

are deemed acceptable for all refrigerant 
systems.

• No leaks shall be detected when using 

detection equipment with a sensitivity of 5 
grams per year of refrigerant or better under a 
pressure of at least 0.25 times the maximum 
allowable pressure (>1.04MPa, max 
4.15MPa), for example, a universal sniffer.

• Electronic leak detectors may be used 

to detect fl ammable refrigerants, but the 
sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is confi rmed.

• Leak detection fl uids are also suitable for use 

with most refrigerants, for example, bubble 
method and fl uorescent method agents. The 
use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked fl ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected.This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
specifi cation, damage to seals, incorrect fi tting 
of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 
fl ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s specifi cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a fl ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts specifi ed 

by the manufacturer. Unspecifi ed parts by 
manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

ACXF55-28780_SS0720-0.indd   9

25/6/2020   11:10:07 AM

Содержание CS-MRZ16WKR

Страница 1: ...ackaged in the indoor unit and removed by the installer before installation Kindly consult authorised dealer for connectivity validity Operating Instructions Air Conditioner Model No Indoor Unit Outdoor Unit Single Split CS RZ25WKRW CS RZ35WKRW CS RZ42WKRW CS RZ50WKRW CS MRZ16WKR CS MRZ20WKR CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR Outdoor Unit Multi Split CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z...

Страница 2: ... time Press and hold for approximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm SET Flexibility to connect Single Split System or Multi Split System Air Conditioner to suit your needs For complete product features please refer to catalogue AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL ECO SLEEP AIR CONDITIONER ON O...

Страница 3: ...unit They are subject to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode AUTO HEAT COOL FAN DRY 1 Press OFF ON OFF ON to start stop the operation POWER Please note that the indication is on display to start the unit 3 Select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for approximately 10 seconds...

Страница 4: ... usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit method or using incompatible material may cause product damage burst and serious injury Do not install the unit in a potentially explosive or fl...

Страница 5: ...od animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoid injury etc Do not touch the sharp aluminium fin sharp parts may cause injury Do not switch ON the indoor unit when waxing the floor After waxing aerate the room prop...

Страница 6: ...g taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and certified Any part of refri...

Страница 7: ... 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant ...

Страница 8: ...ere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigeran...

Страница 9: ...nected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensure that by working on ele...

Страница 10: ... with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent person recovery equipment and cylinders conform to the approp...

Страница 11: ...ber of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are evacuated and if possible cooled before reco...

Страница 12: ...saving without sacrificing comfort To switch between POWERFUL ECO POWERFUL ECO Upper direction Do not adjust the flap by hand Lateral direction For lateral direction it is manually adjustable as shown To adjust airflow direction AIR SWING Upper direction Lateral direction exit setting Indicator POWER TIMER ECO AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIE...

Страница 13: ...ill activate in sequence Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick Guide 2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the ...

Страница 14: ...tem which HEAT mode has been locked if operation mode other than HEAT is selected the indoor unit stops and the POWER indicator blinks COOL Provides efficient comfort cooling to suit your needs DRY Unit operates at low fan speed to give a gentle cooling operation FAN To circulate air in the room Energy saving temperature setting Operating the unit within the recommended temperature range may save ...

Страница 15: ...WBT DBT WBT DBT WBT COOL Max 32 89 6 23 73 4 46 114 8 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 15 5 0 16 3 2 DBT Dry bulb temperature WBT Wet bulb temperature 1 CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR 2 CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z80VBR CU 5Z100VBR ACXF55 28780_SS0720 0 indd 15 25 6 2020 11 10 09 ...

Страница 16: ...ir filter Attach air filter Insert into the unit Anti bacterial filter Anti bacterial filter Clean the filter whenever necessary Wash rinse the filter gently with water to avoid damage to the filter Dry the filter thoroughly under the shade away from fire or direct sunlight Replace the filter every 10 years or replace any damaged filter Part no CZ SA22P Aluminium fin Front panel Air filters Indoor...

Страница 17: ...due to damp smell emitted by the wall carpet furniture or clothing Cracking sound during operation Changes of temperature caused the expansion contraction of the unit Water flowing sound during operation Refrigerant flow inside the unit Mist emerges from indoor unit Condensation effect due to cooling process Outdoor unit emits water steam Condensation or evaporation occurs on pipes Discoloration o...

Страница 18: ...o select COOL HEAT operation After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F HEAT 14 C 25 2 F The units are not going to be used for a long period of time Activate HEAT mode for 2 3 hours to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug...

Страница 19: ...e sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand code H 39 Abnormal indoor operating unit or standby units Diagnostic display Abnormality Protection control H 41 Abnormal wiring or piping connection H 50 Ventilation fan motor lock...

Страница 20: ...hows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows type of flammable refrigerant contained in the system This symbol shows that a service personnel should be handling this equipment with reference t...

Отзывы: