 Safety precautions

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant. 

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over fi ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant.To avoid fi re 
or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
recovered refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 

that: 

• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d) Pump down refrigerant system, if possible.

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since fl ammability is a consideration. 
The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to fi ll until the working pressure is 
achieved, then venting to atmosphere, and 
fi nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the fi nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump 

is not close to potential ignition sources and 
there is ventilation available.

OFN = oxygen free nitrogen, type of inert gas.

ACXF55-28780_SS0720-0.indd   10

25/6/2020   11:10:07 AM

Содержание CS-MRZ16WKR

Страница 1: ...ackaged in the indoor unit and removed by the installer before installation Kindly consult authorised dealer for connectivity validity Operating Instructions Air Conditioner Model No Indoor Unit Outdoor Unit Single Split CS RZ25WKRW CS RZ35WKRW CS RZ42WKRW CS RZ50WKRW CS MRZ16WKR CS MRZ20WKR CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR Outdoor Unit Multi Split CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z...

Страница 2: ... time Press and hold for approximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm SET Flexibility to connect Single Split System or Multi Split System Air Conditioner to suit your needs For complete product features please refer to catalogue AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL ECO SLEEP AIR CONDITIONER ON O...

Страница 3: ...unit They are subject to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode AUTO HEAT COOL FAN DRY 1 Press OFF ON OFF ON to start stop the operation POWER Please note that the indication is on display to start the unit 3 Select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for approximately 10 seconds...

Страница 4: ... usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit method or using incompatible material may cause product damage burst and serious injury Do not install the unit in a potentially explosive or fl...

Страница 5: ...od animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoid injury etc Do not touch the sharp aluminium fin sharp parts may cause injury Do not switch ON the indoor unit when waxing the floor After waxing aerate the room prop...

Страница 6: ...g taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and certified Any part of refri...

Страница 7: ... 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant ...

Страница 8: ...ere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigeran...

Страница 9: ...nected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensure that by working on ele...

Страница 10: ... with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent person recovery equipment and cylinders conform to the approp...

Страница 11: ...ber of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are evacuated and if possible cooled before reco...

Страница 12: ...saving without sacrificing comfort To switch between POWERFUL ECO POWERFUL ECO Upper direction Do not adjust the flap by hand Lateral direction For lateral direction it is manually adjustable as shown To adjust airflow direction AIR SWING Upper direction Lateral direction exit setting Indicator POWER TIMER ECO AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIE...

Страница 13: ...ill activate in sequence Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick Guide 2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the ...

Страница 14: ...tem which HEAT mode has been locked if operation mode other than HEAT is selected the indoor unit stops and the POWER indicator blinks COOL Provides efficient comfort cooling to suit your needs DRY Unit operates at low fan speed to give a gentle cooling operation FAN To circulate air in the room Energy saving temperature setting Operating the unit within the recommended temperature range may save ...

Страница 15: ...WBT DBT WBT DBT WBT COOL Max 32 89 6 23 73 4 46 114 8 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 15 5 0 16 3 2 DBT Dry bulb temperature WBT Wet bulb temperature 1 CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR 2 CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z80VBR CU 5Z100VBR ACXF55 28780_SS0720 0 indd 15 25 6 2020 11 10 09 ...

Страница 16: ...ir filter Attach air filter Insert into the unit Anti bacterial filter Anti bacterial filter Clean the filter whenever necessary Wash rinse the filter gently with water to avoid damage to the filter Dry the filter thoroughly under the shade away from fire or direct sunlight Replace the filter every 10 years or replace any damaged filter Part no CZ SA22P Aluminium fin Front panel Air filters Indoor...

Страница 17: ...due to damp smell emitted by the wall carpet furniture or clothing Cracking sound during operation Changes of temperature caused the expansion contraction of the unit Water flowing sound during operation Refrigerant flow inside the unit Mist emerges from indoor unit Condensation effect due to cooling process Outdoor unit emits water steam Condensation or evaporation occurs on pipes Discoloration o...

Страница 18: ...o select COOL HEAT operation After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F HEAT 14 C 25 2 F The units are not going to be used for a long period of time Activate HEAT mode for 2 3 hours to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug...

Страница 19: ...e sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand code H 39 Abnormal indoor operating unit or standby units Diagnostic display Abnormality Protection control H 41 Abnormal wiring or piping connection H 50 Ventilation fan motor lock...

Страница 20: ...hows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows type of flammable refrigerant contained in the system This symbol shows that a service personnel should be handling this equipment with reference t...

Отзывы: