 Safety precautions

WARNING

This appliance is fi lled with R32 
(mild fl ammable refrigerant). 

If the refrigerant is leaked and exposed to 
an external ignition source, there is a risk 
of fi re.

Indoor unit and outdoor unit

The appliance shall be installed, and/or 
operated in a room with fl oor area larger 
than Amin (m²) and keep away from ignition 
sources, such as heat/sparks/open fl ame or 
hazardous areas such as gas appliances, gas 
cooking, reticulated gas supply systems or 
electric cooking appliances, etc.(Refer to Table 
A of Installation instructions table for Amin (m²))

Be aware that refrigerant may not contain an 
odour, highly recommended to ensure suitable 
fl ammable refrigerant gas detectors are 
present, operating and able to warn of a leak.

Keep any required ventilation openings clear of 
obstruction.

Do not pierce or burn as the appliance is 
pressurized. Do not expose the appliance to 
heat, fl ame, sparks, or other sources of ignition. 
Else it may explode and cause injury or death.

Precaution for using R32 refrigerant

The basic installation work procedures are the same as 
conventional refrigerant (R410A, R22) models.

Since the working pressure is higher than that 
of refrigerant R22 models, some of the piping 
and installation and service tools are special. 
Especially, when replacing a refrigerant R22 
model with a new refrigerant R32 model, 
always replace the conventional piping and 
fl are nuts with the R32 and R410A piping and 
fl are nuts on the outdoor unit side. 
For R32 and R410A, the same fl are nut on the 
outdoor unit side and pipe can be used.

The mixing of different refrigerants within 
a system is prohibited. Models that use 
refrigerant R32 and R410A have a different 
charging port thread diameter to prevent 
erroneous charging with refrigerant R22 and 
for safety. 
Therefore, check beforehand. [The charging port 
thread diameter for R32 and R410A is 1/2 inch.]

 

Must always ensure that foreign matter (oil, 
water, etc.) does not enter the piping. Also, 
when storing the piping, securely seal the 
opening by pinching, taping, etc. (Handling of 
R32 is similar to R410A.)
• Operation, maintenance, repairing and 

refrigerant recovery should be carried 
out by trained and certifi ed personnel in 
the use of fl ammable refrigerants and as 
recommended by the manufacturer. Any 
personnel conducting an operation, servicing 
or maintenance on a system or associated 
parts of the equipment should be trained and 
certifi ed.

• Any part of refrigerating circuit (evaporators, 

air coolers, AHU, condensers or liquid 
receivers) or piping should not be located in 
the proximity of heat sources, open fl ames, 
operating gas appliance or an operating 
electric heater.

• The user/owner or their authorised 

representative shall regularly check the 
alarms, mechanical ventilation and detectors, 
at least once a year, where as required by 
national regulations, to ensure their correct 
functioning.

• A logbook shall be maintained. The results 

of these checks shall be recorded in the 
logbook.

• In case of ventilations in occupied spaces 

shall be checked to confi rm no obstruction.

• Before a new refrigerating system is put 

into service, the person responsible for 
placing the system in operation should 
ensure that trained and certifi ed operating 
personnel are instructed on the basis of the 
instruction manual about the construction, 
supervision, operation and maintenance of 
the refrigerating system, as well as the safety 
measures to be observed, and the properties 
and handling of the refrigerant used.

• The general requirement of trained and 

certifi ed personnel are indicated as below:

a) Knowledge of legislation, regulations 

and standards relating to fl ammable 
refrigerants; and,

b) Detailed knowledge of and skills in 

handling fl ammable refrigerants, personal 
protective equipment, refrigerant leakage 
prevention, handling of cylinders, charging, 
leak detection, recovery and disposal; and,

c) Able to understand and to apply in practice 

the requirements in the national legislation, 
regulations and Standards; and,

d) Continuously undergo regular and further 

training to maintain this expertise.

e) Air-conditioner piping in the occupied 

space shall be installed in such a way 
to protect against accidental damage in 
operation and service.

ACXF55-28780_SS0720-0.indd   6

25/6/2020   11:10:07 AM

Содержание CS-MRZ16WKR

Страница 1: ...ackaged in the indoor unit and removed by the installer before installation Kindly consult authorised dealer for connectivity validity Operating Instructions Air Conditioner Model No Indoor Unit Outdoor Unit Single Split CS RZ25WKRW CS RZ35WKRW CS RZ42WKRW CS RZ50WKRW CS MRZ16WKR CS MRZ20WKR CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR Outdoor Unit Multi Split CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z...

Страница 2: ... time Press and hold for approximately 5 seconds to show time in 12 hour am pm or 24 hour indication 2 Confirm SET Flexibility to connect Single Split System or Multi Split System Air Conditioner to suit your needs For complete product features please refer to catalogue AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL ECO SLEEP AIR CONDITIONER ON O...

Страница 3: ...unit They are subject to change without notice for future improvement B Basic operation 2 Press MODE to select the desired mode AUTO HEAT COOL FAN DRY 1 Press OFF ON OFF ON to start stop the operation POWER Please note that the indication is on display to start the unit 3 Select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press and hold for approximately 10 seconds...

Страница 4: ... usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit method or using incompatible material may cause product damage burst and serious injury Do not install the unit in a potentially explosive or fl...

Страница 5: ...od animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoid injury etc Do not touch the sharp aluminium fin sharp parts may cause injury Do not switch ON the indoor unit when waxing the floor After waxing aerate the room prop...

Страница 6: ...g taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and certified Any part of refri...

Страница 7: ... 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant ...

Страница 8: ...ere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigeran...

Страница 9: ...nected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation Particular attention shall be paid to the following to ensure that by working on ele...

Страница 10: ... with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent person recovery equipment and cylinders conform to the approp...

Страница 11: ...ber of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are evacuated and if possible cooled before reco...

Страница 12: ...saving without sacrificing comfort To switch between POWERFUL ECO POWERFUL ECO Upper direction Do not adjust the flap by hand Lateral direction For lateral direction it is manually adjustable as shown To adjust airflow direction AIR SWING Upper direction Lateral direction exit setting Indicator POWER TIMER ECO AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIE...

Страница 13: ...ill activate in sequence Timer operation is based on the clock set in the remote control and repeats daily once set For clock setting please refer to Quick Guide 2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the ...

Страница 14: ...tem which HEAT mode has been locked if operation mode other than HEAT is selected the indoor unit stops and the POWER indicator blinks COOL Provides efficient comfort cooling to suit your needs DRY Unit operates at low fan speed to give a gentle cooling operation FAN To circulate air in the room Energy saving temperature setting Operating the unit within the recommended temperature range may save ...

Страница 15: ...WBT DBT WBT DBT WBT COOL Max 32 89 6 23 73 4 46 114 8 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 15 5 0 16 3 2 DBT Dry bulb temperature WBT Wet bulb temperature 1 CU RZ25WKR CU RZ35WKR CU RZ42WKR CU RZ50WKR 2 CU 2Z52VBR CU 3Z54VBR CU 4Z71VBR CU 4Z80VBR CU 5Z100VBR ACXF55 28780_SS0720 0 indd 15 25 6 2020 11 10 09 ...

Страница 16: ...ir filter Attach air filter Insert into the unit Anti bacterial filter Anti bacterial filter Clean the filter whenever necessary Wash rinse the filter gently with water to avoid damage to the filter Dry the filter thoroughly under the shade away from fire or direct sunlight Replace the filter every 10 years or replace any damaged filter Part no CZ SA22P Aluminium fin Front panel Air filters Indoor...

Страница 17: ...due to damp smell emitted by the wall carpet furniture or clothing Cracking sound during operation Changes of temperature caused the expansion contraction of the unit Water flowing sound during operation Refrigerant flow inside the unit Mist emerges from indoor unit Condensation effect due to cooling process Outdoor unit emits water steam Condensation or evaporation occurs on pipes Discoloration o...

Страница 18: ...o select COOL HEAT operation After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F HEAT 14 C 25 2 F The units are not going to be used for a long period of time Activate HEAT mode for 2 3 hours to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug...

Страница 19: ...e sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand code H 39 Abnormal indoor operating unit or standby units Diagnostic display Abnormality Protection control H 41 Abnormal wiring or piping connection H 50 Ventilation fan motor lock...

Страница 20: ...hows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows type of flammable refrigerant contained in the system This symbol shows that a service personnel should be handling this equipment with reference t...

Отзывы: