Panasonic CS-KN9XKD-3 Скачать руководство пользователя страница 9

9

English

Safety Precautions

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected. This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
speci

fi

 cation, damage to seals, incorrect 

fi

 tting 

of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s speci

fi

 cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts speci

fi

 ed 

by the manufacturer. Unspeci

fi

 ed parts by 

manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked 

fl

 ame) shall not be used.

7. The following leak detection methods 

are deemed acceptable for all refrigerant 
systems

• No leaks shall be detected when using 

detection equipment with a sensitivity of 
5 grams per year of refrigerant or better 
under a pressure of at least 0.25 times the 
maximum allowable pressure (>1.04 MPa, 
max 4.15 MPa), for example, a universal 
sniffer.

• Electronic leak detectors may be used 

to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is con

fi

 rmed.

• Leak detection 

fl

uids are also suitable for use 

with most refrigerants, for example, bubble 
method and 

fl

uorescent method agents. The 

use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked 

fl

 ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

Содержание CS-KN9XKD-3

Страница 1: ...erating Instructions Air Conditioner Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit nanoe G AVS ACXF55 31180 ...

Страница 2: ...of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or 24 hour 2 Press SET to confirm AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL SLEEP AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING FAN SPEED QUIET POWERFUL SLEEP...

Страница 3: ...s only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the operation POWER When the unit is ON disappears from the remote control display 3 Press TEMP UP TEMP DOWN to select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press for a...

Страница 4: ...install the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit met...

Страница 5: ... Do not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoi...

Страница 6: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and ce...

Страница 7: ...llow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size wit...

Страница 8: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations u...

Страница 9: ...erant in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 6 Detection of flammable refrigerants Under no circumstances shall potential sources of i...

Страница 10: ... minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extreme care shall be taken not to over fill the refrigerating system Prior to recharging the system it shall be ...

Страница 11: ...ders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are...

Страница 12: ...L exit setting nanoe G AVS Indicators POWER TIMER AVS nanoe G Lateral direction FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically according to the operation mode QUIET This operation reduces airflow noise FAN SPEED QUIET nanoe G starts automatically when the unit is turned on with OFF ON OFF ON This operation can be turned ON or OFF manually by pressing This operation can...

Страница 13: ...on until the sleep timer reaches 0 0h To maximise comfort while sleeping SLEEP Note SLEEP POWERFUL FAN SPEED QUIET POWERFUL Can be selected at the same time Can be activated in all modes Cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 Select TIMER ON or TIMER OFF Example OFF at 22 00 OFF 2 Set the time 3 Confirm the setting SET To cancel the timer press ...

Страница 14: ...rizontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Automatic Voltage Switcher AVS When power supply is unstable where the AC voltage supplied is below 185 V or above 260 V AVS will switch off the outdoor unit to protect the compressor During this condit...

Страница 15: ...filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Remove from the unit Insert into the unit To Learn More Cleaning the Air Conditioner Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an autho...

Страница 16: ...ensation occurs on cold pipes and the condensed water may drip from the outdoor unit Discoloration of some plastic parts Discoloration is subjected to the types of materials used in plastic parts It is accelerated when exposed to heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due ...

Страница 17: ...minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units will be not used for an extended period Activate nanoeTM G operation for 2 3 hours as an alternative to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug the unit Remove the batteries from th...

Страница 18: ...ed in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbo...

Страница 19: ...19 English Memo Information ...

Страница 20: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 31180 SZ0621 0 ...

Отзывы: