 Safety Precautions

2-3. Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 

during work, to ensure the technician is aware 

of potentially 

fl

 ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with 

fl

 ammable 

refrigerants, i.e. non sparking, adequately 

sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 

and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/

spill, isolate immediate hazard area and keep 

unauthorised personnel out.

2-4. Presence of 

fi

 re extinguisher

• If any hot work is to be conducted on the 

refrigerating equipment or any associated 

parts, appropriate 

fi

re extinguishing 

equipment shall be available at hand.

• Have a dry powder or CO

2

 

fi

 re extinguisher 

adjacent to the charging area.

2-5. No ignition sources

• No person carrying out work in relation to a 

refrigerating system which involves exposing 
any pipe work that contains or has contained 

fl

ammable refrigerant shall use any sources 

of ignition in such a manner that it may lead to 
the risk of 

fi

re or explosion. He/She must not 

be smoking when carrying out such work.

• All possible ignition sources, including 

cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, 
repairing, removing and disposal, during 
which 

fl

 ammable refrigerant can possibly be 

released to the surrounding space.

• Prior to work taking place, the area around 

the equipment is to be surveyed to make 
sure that there are no 

fl

 ammable hazards or 

ignition risks.

• “No Smoking” signs shall be displayed.

2-6. Ventilated area

• Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the 
system or conducting any hot work.

• A degree of ventilation shall continue during 

the period that the work is carried out.

• The ventilation should safely disperse any 

released refrigerant and preferably expel it 
externally into the atmosphere.

2-7. Checks to the refrigerating equipment

• Where electrical components are being 

changed, they shall be 

fi

 t for the purpose and 

to the correct speci

fi

 cation.

• At all times the manufacturer’s maintenance 

and service guidelines shall be followed.

• If in doubt consult the manufacturer’s 

technical department for assistance.

• The following checks shall be applied to 

installations using 

fl

 ammable refrigerants.

 

- The actual refrigerant charge is in 

accordance with the room size within 
which the refrigerant containing parts are 
installed.

 

- The ventilation machinery and outlets 

are operating adequately and are not 
obstructed. 

 

- If an indirect refrigerating circuit is being 

used, the secondary circuit shall be 
checked for the presence of refrigerant.

 

- Marking to the equipment continues to be 

visible and legible. Markings and signs that 
are illegible shall be corrected.

 

- Refrigerating pipe or components are 

installed in a position where they are 
unlikely to be exposed to any substance 
which may corrode refrigerant containing 
components, unless the components 
are constructed of materials which are 
inherently resistant to being corroded or 
are properly protected against being so 
corroded.

2-8. Checks to electrical devices

• Repair and maintenance to electrical 

components shall include initial safety checks 
and component inspection procedures.

• Initial safety checks shall include but not limit 

to:-

 

- That capacitors are discharged: this 

shall be done in a safe manner to avoid 
possibility of sparking. 

 

- That there no live electrical components 

and wiring are exposed while charging, 
recovering or purging the system. 

 

- That there is continuity of earth bonding.

• At all times the manufacturer’s maintenance 

and service guidelines shall be followed.

• If in doubt consult the manufacturer’s 

technical department for assistance.

• If a fault exists that could compromise safety, 

then no electrical supply shall be connected to 
the circuit until it is satisfactorily dealt with.

• If the fault cannot be corrected immediately 

but it is necessary to continue operation, an 
adequate temporary solution shall be used.

• The owner of the equipment must be 

informed or reported so all parties are advised 
thereinafter.

Содержание CS-KN9XKD-3

Страница 1: ...erating Instructions Air Conditioner Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit nanoe G AVS ACXF55 31180 ...

Страница 2: ...of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or 24 hour 2 Press SET to confirm AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL SLEEP AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING FAN SPEED QUIET POWERFUL SLEEP...

Страница 3: ...s only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the operation POWER When the unit is ON disappears from the remote control display 3 Press TEMP UP TEMP DOWN to select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press for a...

Страница 4: ...install the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit met...

Страница 5: ... Do not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoi...

Страница 6: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and ce...

Страница 7: ...llow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size wit...

Страница 8: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations u...

Страница 9: ...erant in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 6 Detection of flammable refrigerants Under no circumstances shall potential sources of i...

Страница 10: ... minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extreme care shall be taken not to over fill the refrigerating system Prior to recharging the system it shall be ...

Страница 11: ...ders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are...

Страница 12: ...L exit setting nanoe G AVS Indicators POWER TIMER AVS nanoe G Lateral direction FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically according to the operation mode QUIET This operation reduces airflow noise FAN SPEED QUIET nanoe G starts automatically when the unit is turned on with OFF ON OFF ON This operation can be turned ON or OFF manually by pressing This operation can...

Страница 13: ...on until the sleep timer reaches 0 0h To maximise comfort while sleeping SLEEP Note SLEEP POWERFUL FAN SPEED QUIET POWERFUL Can be selected at the same time Can be activated in all modes Cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 Select TIMER ON or TIMER OFF Example OFF at 22 00 OFF 2 Set the time 3 Confirm the setting SET To cancel the timer press ...

Страница 14: ...rizontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Automatic Voltage Switcher AVS When power supply is unstable where the AC voltage supplied is below 185 V or above 260 V AVS will switch off the outdoor unit to protect the compressor During this condit...

Страница 15: ...filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Remove from the unit Insert into the unit To Learn More Cleaning the Air Conditioner Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an autho...

Страница 16: ...ensation occurs on cold pipes and the condensed water may drip from the outdoor unit Discoloration of some plastic parts Discoloration is subjected to the types of materials used in plastic parts It is accelerated when exposed to heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due ...

Страница 17: ...minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units will be not used for an extended period Activate nanoeTM G operation for 2 3 hours as an alternative to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug the unit Remove the batteries from th...

Страница 18: ...ed in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbo...

Страница 19: ...19 English Memo Information ...

Страница 20: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 31180 SZ0621 0 ...

Отзывы: