Panasonic CS-KN9XKD-3 Скачать руководство пользователя страница 7

7

English

Safety Precautions

f)  Precautions shall be taken to avoid 

excessive vibration or pulsation to 
refrigerating piping.

g) Ensure protection devices, refrigerating 

piping and 

fi

ttings are well protected 

against adverse environmental effects 
(such as the danger of water collecting and 
freezing in relief pipes or the accumulation 
of dirt and debris).

h) Expansion and contraction of long runs 

piping in refrigerating systems shall be 
designed and installed securely (mounted 
and guarded) to minimize the likelihood 
hydraulic shock damaging the system.

i)  Protect the refrigerating system from 

accidental rupture due to moving furniture 
or reconstruction activities.

j)  To ensure no leaking, 

fi

eld-made 

refrigerant joints indoors shall be 
tightness tested. The test method shall 
have a sensitivity of 5 grams per year of 
refrigerant or better under a pressure of at 
least 0.25 times the maximum allowable 
pressure (>1.04 MPa, max 4.15 MPa). No 
leak shall be detected.

1. Installation (Space)

• Product with 

fl

ammable refrigerants, shall 

be installed according to the minimum room 
area, Amin (m²) mentioned in Table A of the 
Installation Instructions.

• In case of 

fi

 eld charge, the effect on 

refrigerant charge caused by the different pipe 
length has to be quanti

fi

 ed, measured and 

labelled.

• Must ensure the installation of pipe-work shall 

be kept to a minimum. Avoid use dented pipe 
and do not allow acute bending.

• Must ensure that pipe-work shall be protected 

from physical damage.

• Must comply with national gas regulations, 

state municipal rules and legislation. Notify 
relevant authorities in accordance with all 
applicable regulations.

• Must ensure mechanical connections be 

accessible for maintenance purposes.

• In cases that require mechanical ventilation, 

ventilation openings shall be kept clear of 
obstruction.

• When disposal of the product, do follow to the 

precautions in #12 and comply with national 
regulations.
Always contact to local municipal of

fi

 ces for 

proper handling.

2. Servicing
2-1. Service personnel

• The system is inspected, regularly supervised 

and maintained by a trained and certi

fi

 ed 

service personnel who is employed by the 
person user or party responsible.

• Ensure the actual refrigerant charge is in 

accordance with the room size within which 
the refrigerant containing parts are installed.

• Ensure refrigerant charge not to leak.
• Any quali

fi

 ed person who is involved with 

working on or breaking into a refrigerant 
circuit should hold a current valid certi

fi

 cate 

from an industry-accredited assessment 
authority, which authorizes their competence 
to handle refrigerants safely in accordance 
with an industry recognised assessment 
speci

fi

 cation.

• Servicing shall only be performed 

as recommended by the equipment 
manufacturer. Maintenance and repair 
requiring the assistance of other skilled 
personnel shall be carried out under the 
supervision of the person competent in the 
use of 

fl

 ammable refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

2-2. Work

• Prior to beginning work on systems containing 

fl

 ammable refrigerants, safety checks are 

necessary to ensure that the risk of ignition 

is minimised. For repair to the refrigerating 

system, the precautions in #2-2 to #2-8 must be 

followed before conducting work on the system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 

fl

 ammable gas or vapour being present while 

the work is being performed.

• All maintenance staff and others working in the 

local area shall be instructed and supervised 

on the nature of work being carried out.

• Avoid working in con

fi

 ned spaces. Always 

ensure away from source, at least 2 meter of 

safety distance, or zoning of free space area 

of at least 2 meter in radius.

• Wear appropriate protective equipment, including 

respiratory protection, as conditions warrant.

• Keep all sources of ignition and hot metal 

surfaces away.

Содержание CS-KN9XKD-3

Страница 1: ...erating Instructions Air Conditioner Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit nanoe G AVS ACXF55 31180 ...

Страница 2: ...of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm or 24 hour 2 Press SET to confirm AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE FAN SPEED QUIET POWERFUL SLEEP AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING FAN SPEED QUIET POWERFUL SLEEP...

Страница 3: ...s only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the operation POWER When the unit is ON disappears from the remote control display 3 Press TEMP UP TEMP DOWN to select the desired temperature TEMP Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press for a...

Страница 4: ...install the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any specified refrigerant type Using refrigerant type other than the specified may cause product damage burst and injury etc Do not use means to accelerate the defrosting process or to clean other than those recommended by manufacturer Any unfit met...

Страница 5: ... Do not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other objects This may cause quality deterioration etc Do not use any combustible equipment in front of the airflow outlet to avoid fire propagation Do not expose plants or pet directly to airflow to avoi...

Страница 6: ...al the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer Any personnel conducting an operation servicing or maintenance on a system or associated parts of the equipment should be trained and ce...

Страница 7: ...llow to the precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible Ensure the actual refrigerant charge is in accordance with the room size wit...

Страница 8: ...ternally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations u...

Страница 9: ...erant in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 6 Detection of flammable refrigerants Under no circumstances shall potential sources of i...

Страница 10: ... minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extreme care shall be taken not to over fill the refrigerating system Prior to recharging the system it shall be ...

Страница 11: ...ders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Recovery cylinders are...

Страница 12: ...L exit setting nanoe G AVS Indicators POWER TIMER AVS nanoe G Lateral direction FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically according to the operation mode QUIET This operation reduces airflow noise FAN SPEED QUIET nanoe G starts automatically when the unit is turned on with OFF ON OFF ON This operation can be turned ON or OFF manually by pressing This operation can...

Страница 13: ...on until the sleep timer reaches 0 0h To maximise comfort while sleeping SLEEP Note SLEEP POWERFUL FAN SPEED QUIET POWERFUL Can be selected at the same time Can be activated in all modes Cannot be selected at the same time To set the timer ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 Select TIMER ON or TIMER OFF Example OFF at 22 00 OFF 2 Set the time 3 Confirm the setting SET To cancel the timer press ...

Страница 14: ...rizontal flap is fixed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Automatic Voltage Switcher AVS When power supply is unstable where the AC voltage supplied is below 185 V or above 260 V AVS will switch off the outdoor unit to protect the compressor During this condit...

Страница 15: ...filters gently with water to avoid damaging the surface Dry the filters thoroughly under a shade away from fire or direct sunlight Replace any damaged filters Remove air filter Attach air filter Remove from the unit Insert into the unit To Learn More Cleaning the Air Conditioner Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an autho...

Страница 16: ...ensation occurs on cold pipes and the condensed water may drip from the outdoor unit Discoloration of some plastic parts Discoloration is subjected to the types of materials used in plastic parts It is accelerated when exposed to heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due ...

Страница 17: ...minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents COOL 8 C 14 4 F The units will be not used for an extended period Activate nanoeTM G operation for 2 3 hours as an alternative to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug the unit Remove the batteries from th...

Страница 18: ...ed in combination with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbo...

Страница 19: ...19 English Memo Information ...

Страница 20: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 31180 SZ0621 0 ...

Отзывы: