background image

 • 

You can then switch between the display for the previous problem and the problem before that by pressing the UP (TIMER)
DOWN (TIMER) switches.

 • 

Press the CHECK switch once more to return to the normal display.

Example of previous problem display

Example of abnormality display before previous display

 • 

The display can be switched between the previous problem and the one before that by pressing the UP (TIMER) DOWN
(TIMER) switches.

 • 

After eliminating the cause of the problem, press the CHECK switch once more to return to the normal display.

62

Содержание CS-F14DD3E5

Страница 1: ...onic HA Air Conditioning M Sdn Bhd 11969 T All rights reserved Unauthorized copying and distribution is a violation of law CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 4 1 CS F14DD3E5 CS F18DD3E5 8 4 2 CU B14DBE5 CU B18DBE5 9 5 REFRIGERATION CYCLE 10 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 6 BLOCK DIAGRAM 11 6 1 CS F14DD3E5 CS F18DD3E5 11 6 2 CU B14DBE5 11 6 3 CU B18DBE5 12 7 WIRING ...

Страница 2: ...tallation 56 11 INSTALLATION SERVICING AIR CONDITIONER 63 11 1 Outline 63 11 2 Tools for installing servicing refrigerant piping 64 11 3 Refrigerant piping work 68 11 4 Installation transferring servicing 70 12 TROUBLE SHOOTING GUIDE 74 12 1 For standard installation 74 12 2 During twin operation 76 12 3 During group control operation 78 12 4 Test operation and self diagnosis 79 12 5 Emergency ope...

Страница 3: ...ution of test operation Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is on Because the unit is having automatic address setting during the first one minute 1 3 Caution during automatic address setting When main power supply switch is on the P C board will automatically memorized the connecting system Consequently when initial...

Страница 4: ...onditions in the building 2 1 3 Easy maintenance Equipped with a filter as standard The filter can be removed in three directions for easier maintenance 2 2 Outdoor unit Long pipe design with a maximum piping length of 30m Additional charging of refrigerant are not required for 20m of pipe length Flexible 4 way piping Centralized drain method gather multiple outdoor units drain pipes into a single...

Страница 5: ...units can be set automatically in twin systems No address setting is necessary Multiple indoor units can be operated simultaneously with a single remote control Note that individual operation is not possible Operating efficiency is improved and energy consumption is reduced 2 2 2 Low ambient cooling operation The unit can set for cooling even when the outdoor temperature drops to 10 C This is idea...

Страница 6: ...type 3 x 12 x 15 Corrugate fin type 1 x 36 x 21 Refrigerant Control Exp Valve Refrigerant Oil Charged cm3 FV50S 670 Refrigerant Charged R410A kg oz 1 1 38 8 Running Adjustment Control Switch Wired Remote Control Room Temperature Thermostat Noise Level dB A Cooling Hi 42 Lo 38 Cooling 49 Heating 50 Heating Hi 42 Lo 38 Power level dB Cooling Hi 58 Lo 54 Heating Hi 58 Lo 54 Cooling 65 Heating 66 Mois...

Страница 7: ...2 x 15 Corrugate fin type 1 x 36 x 21 Refrigerant Control Exp Valve Refrigerant Oil Charged cm3 FV50S 670 Refrigerant Charged R410A kg oz 1 35 47 6 Running Adjustment Control Switch Wired Remote Control Room Temperature Thermostat Noise Level dB A Cooling Hi 42 Lo 38 Cooling 49 Heating 50 Heating Hi 42 Lo 38 Power level dB Cooling Hi 58 Lo 54 Heating Hi 58 Lo 54 Cooling 65 Heating 66 Moisture Remo...

Страница 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...

Страница 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...

Страница 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...

Страница 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...

Страница 12: ...6 3 CU B18DBE5 12 ...

Страница 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...

Страница 14: ...7 2 CU B14DBE5 14 ...

Страница 15: ...7 3 CU B18DBE5 15 ...

Страница 16: ...CK button Press this button if the check display is flashing TIMER CLOCK SET buttons Used to set the timer operation and the current time Operation indicator Lights up when the unit in operation 8 WIRED REMOTE CONTROL OPERATING INSTRUCTIONS 8 1 Name and function of each part NOTES Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting c...

Страница 17: ...8 2 Remote control display 17 ...

Страница 18: ...8 3 Remote control panel 18 ...

Страница 19: ...e or hold the button to change the time faster If the UP or DOWN button is not pressed for 30 seconds during the day or time setting or if the SELECT button is pressed the setting at that moment is confirmed and setting will end 8 5 How to select the timer 2 types of Timer mode can be selected on the remote control Daily Timer Weekly Timer These timers cannot be operated simultaneously Select one ...

Страница 20: ...n to change the display to daily timer 2 ON Timer OFF Timer and select Time Press SELECT button ON Timer setting will be displayed Press UP or DOWN button to select the desired time Example ON 9 00 then press SET button to confirm the selected desired time Or press CANCEL button if you do not want any setting for ON Timer Then OFF Timer setting will be displayed Press UP or DOWN button to select t...

Страница 21: ... setting Press UP or DOWN button to select the day Then press SET button to delete triangle mark deselect or add triangle mark select Triangle mark on top of each day indicates the day to be selected Repeat these steps if you want to deselect or select many days To confirm the selected days press the SELECT button Individual day setting Press UP or DOWN button to select the day Then press SELECT b...

Страница 22: ...esday Then press SELECT button To set the time please refer to step 3 1st program press SET button twice confirm ON and 9 00 2nd program also press SET button twice Confirm OFF and 16 00 3rd program select OFF and desired time to 12 30 4th program select ON and desired time to 13 30 5th 6th program press CANCEL button To set C Saturday Individual day setting Follow the same step as above To set th...

Страница 23: ... 1 Cooling operation Cooling operation can be set using remote control This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control Cooling Operation Time Diagram 23 ...

Страница 24: ...oom When operation begins the fan speed is fixed at Low speed while cooling operation is running until reaches the remote control setting temperature 9 4 Auto operation Automatic Mode can be set using remote control This operation starts to judge the intake air temperature setting temperature and outdoor piping temperature Then the unit starts to operate at determined operation mode 9 5 Fan operat...

Страница 25: ...N Time 40 sec 50 sec 20 sec 120 sec 20 sec 40 sec 50 sec Cool Auto Off Lo Hi Lo Off Lo Off Lo Me Soft Dry Auto Off Lo Lo Lo Off Lo Off Lo Lo 9 6 2 Heating Indoor Fan Control Manual Fan Speed Operation starts at High Medium or Low speed set by remote control However when operation start or during operation fan speed control is limited due to prevent a cold draft for example when heating operation s...

Страница 26: ...etween room temperature and setting temperature compressor operation is decided and starts operation If temperature difference matches values shown below thermostat switches off Cool Mode 1 5 C Soft Dry Mode 2 5 C Heat Mode 3 5 C 9 7 2 Odour Cut Control Odour cut operation removes the odour generated at indoor heat exchanger by using drain water come out from indoor heat exchanger Press Odour butt...

Страница 27: ...re decrease cooling capacity will be reduced 9 7 6 Freeze Prevention Control During Cooling or Dry operation after compressor starts operation for 4 minutes the outdoor unit will stop its operation if indoor pipe temperature falls below 0ºC for 6 minutes After 3 minutes stops compressor restarts operation if indoor pipe temperature is 6ºC or more This phenomenon is to protect the indoor heat excha...

Страница 28: ...fan operates at High speed for 1 minute to remove the remaining heat 9 7 10 Crank Case Heater Control Crank case heater ON when the compressor is shutdown and discharge temperature is 20 C to prevents the refrigerant solving into compressor oil inside the compressor shell at cold condition 9 7 11 Pump Down To enable pump down operation at outdoor PCB set the DS1 to OFF position 28 ...

Страница 29: ...compressor is shut down And indoor unit is set to thermo off status After 6 occasions high pressure protection error is displayed all operations stopped except outdoor fan remaining heat removal control 9 8 3 Discharge Temperature Protection Control The discharge temperature protection control starts when abnormal compressor temperature 115 C is detected when outdoor unit is operating in cooling o...

Страница 30: ...Sec Detection condition Discharge Temperature 4 5 C or 201 8 C 5 Other than compressor start control and compressor ON Outdoor heat exchange 50 5 C or 103 7 C 5 Regularly During sensor disconnection sensor error is displayed all operations stops except outdoor fan remaining heat removal control 9 8 8 Four way Valve Error Detection Control The four way valve error detection control starts when Duri...

Страница 31: ...mpressor shutdown During this error low pressure switch error is displayed 9 9 Test run Test run is necessary after installation is completed To enable forced cooling test run at outdoor PCB set the DS1 to position below To enable forced heating test run at outdoor PCB set the DS1 to position below Press Test Run button for 1 second SW1 located at outdoor printed circuit board 31 ...

Страница 32: ...Lo 6 35 3 ways 12 7 3 ways 30 20 20 20 20 TYPE 0 CS F18DD3E5 A 10 1 2 Refrigerant additional charge The piping length exceeds 20 metres Before shipment this air conditioner is filled with the rated amount of refrigerant subject to 20m piping length The rated amount of refrigerant is indicated on the name plate But when the piping length exceeds 20m additional charge is required according to the fo...

Страница 33: ...tion of the centre gravity MODEL NAME OUTSIDE DIMENSIONS NET WEIGHT CENTRE OF GRAVITY WIDTH mm DEPTH mm HEIGHT mm kg X mm Y mm Z mm CU B14DBE5 900 320 795 55 560 150 320 CU B18DBE5 900 320 795 57 560 150 320 33 ...

Страница 34: ...ant leak occurring Please discuss with the place of purchase for advice on what measures may be necessary to prevent critical concentrations being exceeded If the refrigerant leaks and reaches critical concentration levels there is the danger that death from suffocation may result As to installation request the distributor or vendor to perform it Imperfection in installation caused by that having ...

Страница 35: ...prevent the occurrence of condensation Imperfection in piping work leads to water leakage and may cause the house and property etc to become wet Do not install the unit at the place where the possibility of inflammable gas leakage exists If such gas leakage should arise and the gas builds up around the unit such situation may lead to ignition Position the indoor unit outdoor unit power cords and i...

Страница 36: ...onsiderable amount of oil steam and flour adhere to the turbo fan the fin of the heat exchanger and the drain pump resulting in heat exchange reduction spraying dispersing of water drops drain pump malfunction etc In these cases take the following actions Make sure that the ventilation fan for smoke collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should...

Страница 37: ... for easy water drainage INSTALLATION OF DUCT 1 The duct of the air inlet could be installed by the three situations as shown in the illustration below a c Setting the filter Case of a Reverse the filter and not install the duct of the air inlet Case of b Remove the filter local arrangement and install the duct of the air inlet Case of c Change the panel bottom to install the duct of the air inlet...

Страница 38: ...wn in the illustration below 3 When the duct of air inlet will be installed install the duct flange side R L to the air inlet with accessories as shown in the illustration 4 The filter could be removed from any one of three directions as shown in the illustration below 38 ...

Страница 39: ...oor connection Flare nut fastening torque N m kgf cm ø6 35 mm 18 180 ø12 7 mm 55 560 ø19 05 mm 100 1020 ø9 52 mm 42 430 ø15 88 mm 65 660 The unit has two drainage holes at both side The drainage hole without connection needs seal and thermal insulation with accessories Always lay the drain with downward inclination 1 50 to 1 100 Prevent any upward flow or reverse flow in any part 5mm or thicker fo...

Страница 40: ... following procedure Heat insulation material to be prepared Adiabatic glass wool with thickness 10 to 20mm Stick glass wool on all air conditioners that are located in ceiling atmosphere In addition to the normal heat insulation thickness more than 8mm for refrigerant piping gas piping thick piping and drain piping add a further of 10mm to 30mm thickness material Wall seal When the outdoor unit i...

Страница 41: ...curely using specified cables and fix them securely so that external force of the cables may not transfer to the terminal connection section Imperfect connection and fixing leads to fire etc 1 Select a power source that is capable of supplying the current required by the air conditioner 2 Feed the power source to the unit via a distribution switch board designed for this purpose the switch should ...

Страница 42: ...trol or standard type should be set at No 16 at the indoor unit before turning the power on again All sets in the group which uses the same remote controller thermistor settings can be controlled by the same remote controller thermistor Up to a maximum of 16 indoor units can be connected at the time of group control Do not connect heat pump unit with cooling only unit Indoor unit No will be set au...

Страница 43: ...rature setting display At the start of the test operation it may take up to 1 minute for air conditioner number switching time and other displays to appear After operation modes have been selected stop the compressor for a moment Press the OFF ON button of the TEST RUN button once more to cancel test operation mode NOTE 1 These units are equipped with connection error prevention circuits If the un...

Страница 44: ...outside temperature suction temperature blow out temperature wind velocity wind volume voltage current presence of abnormal vibration and noise operating pressure piping temperature compressive pressure airtight pressure As to the structure and appearance check the following items 10 3 12 Hand over Teach the customer the operation and maintenance procedures using the operation manual air filter cl...

Страница 45: ...dor to perform it Imperfection in installation caused by that having been carried out by the customer himself may lead to water leakage electric shock fire etc Switch off all supplies before accessing any electrical part Carry out the installation work with reliability according to this manual for installation work Imperfection in installation leads to water leakage electric shock fire etc If refr...

Страница 46: ...from televisions and radios This is to avoid problem such as interference with picture and or sound However note that depending on the electromagnetic wave conditions interference may still occur even if the separation distance is more than 1 meter Drain piping should be made to ensure secure drainage according to the manual for installation work and carry out the thermal insulation to prevent the...

Страница 47: ...gap with brazing How to tape Seal terminal part of piping with vinyl tape 3 Vacuum pumping The purpose of vacuum pumping work is to remove and dry air inside the piping or nitrogen at air tightness test Perform the work carefully Caution Use the vacuum pump with the backflow prevention mechanism to prevent backflow of oil Vacuuming time 60 minutes or more Vacuum pump capacity 60 l min or more 4 Re...

Страница 48: ...ld air do not build up 3 There should not be animals or plants near the air outlet which could be adversely affected by hot or cold air coming out from the unit 4 The outlet air and operating noise should not be a nuisance to other occupants nearby 5 The location should be able to withstand the full weight and vibration of the outdoor unit and it should also be level and safe for the unit to be in...

Страница 49: ...on location as possible 2 If suspending the outdoor unit use a rope or belt and use cloth or wood as padding in order to avoid damaging the unit Installation 1 Read the Selecting the outdoor unit installation location section thoroughly before installing the outdoor unit 2 If installing the unit to a concrete base or other solid base use M10 or W3 8 bolts and nuts to secure the unit and ensure tha...

Страница 50: ... dust such as a saw and a magnet When waxing replace nitrogen inside the piping after removing dirt and dust In order to prevent oxidation scale from forming inside the piping The refrigerant pipes are of particular importance The installation work for refrigerant cycles in separate type air conditioners must be carried out perfectly 1 Refer to the table below for the pipe diameters equivalent len...

Страница 51: ...ng inside the pipe If using long pipe lengths with several joined pipe ends insert strainers inside the pipes Strainers are not supplied When tightening the flare nuts coat the flare both inside surfaces with a small amount of refrigerator oil and screw in about 3 4 turns at first by hand Refer to the following table for the tightening torques Be sure to use two spanners to tighten If the nuts are...

Страница 52: ...them securely so that external force of the cables may not transfer to the terminal connection section Imperfect connection and fixing leads to fire etc Connect the power supply wiring and indoor outdoor unit connection wiring according to the electrical circuit diagram instructions Clamp the wires securely to the terminal connections using cord clamps so that no undue force is placed on the wires...

Страница 53: ...DBE8 380V 415V 3N 15 15 15 4 mm2 59 0 1017 2 5 mm2 4 CU B34DBE5 CU J34DBE5 220V 240V 40 40 40 10 0 0374 CU B34DBE8 CU J34DBE8 380V 415V 3N 20 20 20 38 0 1017 CU B43DBE8 CU J43DBE8 380V 415V 3N 20 20 20 27 0 1017 CU B50DBE8 CU J50DBE8 380V 415V 3N 20 20 20 25 0 1017 NOTE 1 Where ground work earth is carried out do not connect the ground return to the gas pipe water line pipe grounded circuit of the...

Страница 54: ... Press and hold SW1 more than 1 second In DS1 under different setting condition outdoor unit will perform cooling test run or heating test run DS1 Operation mode 1 2 3 4 ON OFF x x Cooling test run ON ON x x Heating test run OFF OFF x x PUMP DOWN Must first select cooling mode When operation mode changes the compressor stops operation momentary Press SW1 again to cancel test run If outdoor tempera...

Страница 55: ... diagnosis function reports a problem but more than one problem has developed at the indoor and or outdoor units the problem display on the remote control unit may not match the LED display on the outdoor unit printed circuit board In such cases check both locations and remove the causes of the problems 10 4 12 As to making the inspection after completion of work fully understood At the time when ...

Страница 56: ...regarding wired remote controller setting up location Select a place where the remote controller can be operated easily after obtaining approval from the building s owner Install in a place which is away from direct sunlight and as free from humidity as possible Install in a place which is as flat as possible to avoid warping of the remote controller If installed to a wall an uneven surface damage...

Страница 57: ...emote controller wiring and installing the remote controller be sure to connect the cord to the connector CN1 Extending the remote control cable Solder a sheathed PVC cord or cable 0 5 2 mm2 with specifications among those given below to the remote controller end of the accessory remote control cable 10 m PVC round cabtire cord IEC 502 600V PVC insulated PVC sheathed round cable IEC 227 4 600V PVC...

Страница 58: ...stration below Route the remote control cable inside the lower case in accordance with the intended feeding out direction Refer to the illustration below Securely connect connector CN1 If it is not connected the remote controller will not operate NOTE After connecting the connector do not suspend the upper case by its own weight otherwise the connector cord may break If controlling using two remot...

Страница 59: ... operate the indoor unit The indoor unit can be operated with the last switch pressed having priority 1 Decide which is to be the master and which is to be the slave remote controller The master or slave states of the remote controller are set automatically The MASTER SLAVE setting switch can also be use to make the setting manually however if a manual setting is made that manual setting has prior...

Страница 60: ...rmistor can be switched between the thermistor at the indoor unit and the thermistor at the remote controller However do not switch to the remote controller thermistor if using two remote controllers 1 When operation is stopped press for 5 seconds continue the TEST RUN switch to display 00 will be LOCAL MODE 2 Press the UP TEMP DOWN TEMP switch to display 11 3 Press the SELECT switch to display 00...

Страница 61: ... appears on the remote controller display It is possible that the remote controller was connected while the main power was still turned on If such is the case carry out the following Set DIP switch SW2 No 1 to 4 The ON position and then turn on the main power If the display appears after about 30 seconds turn DIP switches 2 to 4 to OFF position 10 5 6 Self diagnosis function If CHECK is blinking o...

Страница 62: ...e more to return to the normal display Example of previous problem display Example of abnormality display before previous display The display can be switched between the previous problem and the one before that by pressing the UP TIMER DOWN TIMER switches After eliminating the cause of the problem press the CHECK switch once more to return to the normal display 62 ...

Страница 63: ...of this it can cause an oxygen deficiency if it leaks into a closed room since it collects in the lower area of the room It also generates toxic gas when it is directly exposed to a flame so it must be used in a well ventilated environment where it will not collect Table 1 Physical comparison of R410A and R22 R410A R22 Composition wt R32 R125 50 50 R22 100 Boiling point C 51 4 40 8 Vaporizing pres...

Страница 64: ...ave all repair work done by a specialist Incorrect repairs can result in a water leakage electric shock fire etc 11 2 Tools for installing servicing refrigerant piping 11 2 1 Necessary tools In order to prevent an R410A AC from mistakenly being charged with any other refrigerant the diameter of the 3 way valve service port on the outdoor unit has been changed Also to increase its ability to withst...

Страница 65: ...onal wrenches R410A wrenches For 1 4 opposite side x torque 17 mm x 18 N m 180 kgf cm 17 mm x 18 N m 180 kgf cm For 3 8 opposite side x torque 22 mm x 42 N m 420 kgf cm 22 mm x 42 N m 420 kgf cm For 1 2 opposite side x torque 24 mm x 55 N m 550 kgf cm 26 mm x 55 N m 550 kgf cm For 5 8 opposite side x torque 27 mm x 65 N m 650 kgf cm 29 mm x 65 N m 650 kgf cm Because the pressure is higher for the ...

Страница 66: ... halide torch that were used with CFC and HCFC cannot be used with R410A because there is no chlorine in the refrigerant The present R134a leak detector can be used but the detection sensitivity will be lower setting the sensitivity for R134a at 1 the level for R410A will drop to 0 6 For detecting small amounts of gas leakage use the electric gas leak detector for HFC refrigerant Detection sensiti...

Страница 67: ...gerant charging is done manually by opening and closing the valve 9 Refrigerant cylinders The R410A cylinders are labeled with the refrigerant name and the coating color of the cylinder protector is pink which is the color stipulated by ARI of the U S Cylinders equipped with a siphon tube are available to allow the cylinder to stand upright for liquid refrigerant charging 10 Charging orifice and p...

Страница 68: ...size before using When using a conventional flaring tool use the copper pipe gauge for clearance adjustment etc to ensure the correct A dimension see Fig 10 Fig 10 Flaring dimensions 11 3 1 Piping materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg 10m Do not use pipes that are crushed deformed or discolored especially the inside s...

Страница 69: ...and union b Align the flared surface with the axial center of the union c Use a torque wrench and tighten to the specified torque The tightening torque for R410A is the same as the conventional torque value for R22 Be careful because if the torque is too weak it may lead to a gas leak If it is too strong it may split the flare nut or make it impossible to remove the flare nut Table 15 R410A tighte...

Страница 70: ...y purged with nitrogen or dried with a vacuum pump 11 4 Installation transferring servicing 11 4 1 Inspecting gas leaks with a vacuum pump for new installations Using new refrigerant piping 1 From the viewpoint of protecting the global environment please do not release refrigerant into the atmosphere a Connect the projecting side pin pushing side of the charging hose for the manifold gauge to the ...

Страница 71: ...frigerating machine oil is different When replacing an R22 AC unit with an R410A AC unit the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil as described in items c and d of section About R410A Refrigerant In this case you should use new refrigerant piping rather than the existing piping 1 Pipin...

Страница 72: ... valve of the manifold gauge and purge the air 2 4 Watch the liquid refrigerant closely at this point 8 After adjusting the electronic scale to zero open the charging valve then open the valve Lo of the manifold gauge and charge with the liquid refrigerant 2 5 Be sure to read the operating instructions for the electronic scale 9 If you cannot charge the stipulated amount operate the unit in the co...

Страница 73: ...uit f No corrosion should occur from the brazed part 2 Prevention of Overheating Due to heating the interior and exterior surfaces of treated metal may oxidize Especially when the interior of the refrigerant circuit oxidizes due to overheating scale occurs and stays in the circuit as dust thus exerting a fatally adverse effect So make brazing at adequate brazing temperature and with minimum of hea...

Страница 74: ...rned on while the indoor outdoor transmission wires are not connected open circuit at A power line Symptom Indoor unit no power supply Remote control unit no power supply Outdoor unit LED2 4 6 on P C B flashes 2 The main power is turned on while the indoor outdoor transmission wires are not connected open circuit at B power transmission line Symptom Indoor unit no power supply Remote control unit ...

Страница 75: ... When remote control display shows power supply Clock setting and no timer setting When remote control display shows No power supply 75 ...

Страница 76: ...ity error 2 The main power is turned on while the transmission wires between the indoor units are not connected open circuit at section C Symptom Remote control unit check flashes Error code F30 01 connected indoor capacity error Indoor unit No 1 LED1 on P C B flashes Indoor unit No 2 no power supply Outdoor unit LED5 6 on P C B flashes connected indoor capacity error 3 The main power is turned on...

Страница 77: ... operation Symptom Remote control unit check flashes Error code F30 01 connected indoor capacity error Indoor unit LED1 on P C B flashes Outdoor unit LED6 7 on P C B flashes connected indoor capacity error Remedy 1 Turn off the main power 2 Connect the disconnected wire correctly 3 Turn on the main power 4 After 1 minute start the operation using the remote control Indoor unit operation will start...

Страница 78: ...r unit LED1 on P C B flashes Outdoor unit LED6 7 on P C B flashes 2 The main power is turned on while the remote control connection wire is not connected open circuit at section D Symptom Nothing abnormal appears on the remote control display Operation of indoor unit No 1 and No 2 is possible However indoor unit No 3 cannot be operated Remedy 1 Turn off the main power 2 Connect the disconnected wi...

Страница 79: ...nds past 12 hours 4 Check that the voltage is 10 of the rated voltage 198V 1 phase or 342V 3 phase or higher when starting the unit The unit will not operate if the voltage is less than 10 of the rated voltage 198V 1 phase or 342V 3 phase 5 If test operation continues for more than 30 minutes test operation finishes and shifts to normal operation 6 Test operation mode can be selected cooling mode ...

Страница 80: ...en the pipe temperature gas pipe will be displayed in the LCD of the remote control 4 Check that the pipe temperature in the display of the remote control starts dropping after operation has been continuing for some time 12 4 4 Self diagnosis function The wired remote control display and the self diagnosis LEDs green on the outdoor unit printed circuit board indicate where the abnormality has occu...

Страница 81: ...ck button while the display is flashing The timer display will change and an error code from F15 to F44 will appear in place of time the temperature setting display will also change to show the air conditioner No Press the timer set button while the error is displayed The F15 44 display will change to the detail display How to display the past error message If the CHECK display on the wired remote...

Страница 82: ...Resistance value kΩ 5 Temperature Indoor Outdoor C Room temperature thermistor Pipe temperature thermistor Discharge temperature thermistor Pipe temperature thermistor 20 158 5 211 3 528 3 47 9 10 87 5 116 7 291 8 27 1 5 66 1 88 2 220 5 20 7 0 50 5 67 3 168 3 15 9 5 38 9 51 9 129 8 12 4 10 30 3 40 4 100 9 9 8 15 23 8 31 7 79 2 7 7 20 18 8 25 1 62 7 6 2 25 15 20 50 5 30 12 1 16 1 40 2 4 40 8 10 6 2...

Страница 83: ... connection terminals or indoor unit power supplies indoor side 05 Indoor outdoor unit connection error problem Indoor outdoor unit connection wire indoor side 01 Indoor outdoor unit disconnection problem Indoor outdoor unit connection cable and connection terminals or outdoor unit power supplies outdoor side 05 Indoor outdoor unit connection problem Indoor outdoor unit connection wire outdoor sid...

Страница 84: ...luminates to indicate that the microprocessor on the printed circuit board is operating normally If the LED is switched off is flashing irregularly Check the power supply and turn it off and then back on again Master unit problem Slave unit problem 84 ...

Страница 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...

Страница 86: ...86 ...

Страница 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...

Страница 88: ...13 3 Discharge and suction pressure 13 3 1 Saturation temperature of discharge and suction pressure COOLING 88 ...

Страница 89: ...HEATING 89 ...

Страница 90: ...ity and power consumption 13 4 1 Cooling performance 13 4 1 1 CS F14DD3E5 CU B14DBE5 Model Cooling capacities are based on conditions CS F14DD3E5 CU B14DBE5 Single phase 50Hz 230V Cooling capacity Indoor temp 27 C D B 19 C W B 3 8 kW Outdoor temp 35 C D B Standard air volume 17 m3 min 90 ...

Страница 91: ...91 ...

Страница 92: ...ing Power Consumption 13 4 1 2 CS F18DD3E5 CU B18DBE5 Model Cooling capacities are based on conditions CS F18DD3E5 CU B18DBE5 Single phase 50Hz 230V Cooling capacity Indoor temp 27 C D B 19 C W B 5 0 kW Outdoor temp 35 C D B Standard air volume 17 m3 min 92 ...

Страница 93: ...93 ...

Страница 94: ...0Hz 230V Heating capacity Indoor temp 20 C D B 4 3 kW Outdoor temp 7 C D B 6 C W B Standard air volume 17 m3 min 13 4 2 2 CS F18DD3E5 CU B18DBE5 Model Heating capacities are based on conditions CS F18DD3E5 CU B18DBE5 Single phase 50Hz 230V Heating capacity Indoor temp 20 C D B 5 6 kW Outdoor temp 7 C D B 6 C W B Standard air volume 17 m3 min 94 ...

Страница 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...

Страница 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...

Страница 97: ...ection Heat pump model OFF A 8 5 12 RESET Automatic Automatic Discharge temp protection Discharge Compressor temperature OFF C 114 114 thermistor Th1 Liquid compress protection Crankcase heater Input power W 37 37 x 2 Compressor protection Internal protector OFF C 50Hz 160 ON C 50Hz 90 trip time 50Hz 3 10sec 35A Compressor protection OLP OFF C 50Hz 145 ON C 50Hz 69 trip time 50Hz 6 16sec 23 5A For...

Страница 98: ...13 7 Operating characteristics S C Starting Current R C Running Current IPT Power Consumption 98 ...

Страница 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...

Страница 100: ...s P42 T03790R 1 1 O 7 Filter P03 T01520R 1 1 O 8 Duct flange as Outlet P42 T03770R 1 1 O 9 Fan base as P45 T07690R 1 1 O 10 Casing Impeller as P45 T07950R 2 2 O 11 Fan motor P06 T05010R 1 1 O 12 Panel side R as P42 T03660R 1 1 O 13 Panel side L as P42 T03760R 1 1 O 14 Terminal board P06 T04970 1 1 15 Capacitor P06 T04380R 1 1 O 16 Transformer A40C1031 1 1 17 Remote control A75C2742 1 1 18 Thermist...

Страница 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...

Страница 102: ...CU B14DBE5 CU B18DBE5 102 ...

Страница 103: ...1 TERMINAL BOARD ASSY 1 CWA28K1085J 32 TERMINAL BOARD ASSY 1 CWA28K1076J 33 CAPACITOR FM 1 DS461205QP A DS461255QP A 34 CAPACITOR COMP 1 DS371306CPNA DS371506CPNA 35 HOLDER CAPACITOR 1 CWH30176 CWH30060 36 ELECTRONIC CONTROLLER MAIN 1 CWA73C1900 CWA73C1901 37 MAGNETIC RELAY 1 K6C2A9A00001 K6C4E8A00003 38 TRANSFORMER 1 CWA401060 39 TERMINAL COVER 1 CWH171011 CWH171012 40 NUT FOR TERMINAL COVER 1 CW...

Страница 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...

Страница 105: ...15 2 Outdoor unit OUTDOOR UNIT PRINTED CIRCUIT BOARD MAIN 105 PHAAM Printed in Malaysia SFYW0605 01 ...

Отзывы: