![Panasonic CS-F14DD3E5 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/panasonic/cs-f14dd3e5/cs-f14dd3e5_service-manual_256929039.webp)
1. Brazing for piping.
a. Execute brazing before tightening the flare nut.
b. Brazing must be executed while blowing nitrogen gas.
(This prevents generation of oxidized scale in copper
pipe.)
2. When there is a lot of brazings for long piping, install a
strainer midway of the piping. (The strainer is locally
supplied.)
3. Use clean copper pipe with inner wall surface free from mist
and dust. Blow nitrogen gas or air to blow off dust in the
pipe before connection.
4. Form the piping according to its routing. Avoid bending and
bending back the same piping point more than three times.
(This will result in hardening of the pipe).
5. After deforming the pipe, align centers of the union fitting of
the indoor unit and the piping, and tighten them firmly with
wrenches.
6. Connect pipe to the service valve or ball valve which is
located below the outdoor unit.
7. After completed the piping connection, be sure to check if
there is gas leakage in indoor and outdoor connection.
Flare nut fastening torque N.m (kgf.cm)
ø6.35 mm 18 (180)
ø12.7 mm
55 (560) ø19.05 mm
100
(1020)
ø9.52 mm 42 (430) ø15.88 mm 65 (660)
•
The unit has two drainage holes at both side.
The drainage hole without connection needs seal and thermal
insulation with accessories.
•
Always lay the drain with downward inclination (1/50 to 1/100).
Prevent any upward flow or reverse flow in any part.
•
5mm or thicker formed thermal insulator shall always be
provided for the drain pipe.
•
Confirm the red mark of the union (thin side) is always at
lower direction after connecting piping.
Liquid side piping
Gas side piping
CS-F14~18DD3E5
ø6.35
ø12.7
CS-F24~50DD3E5
ø9.52 mm
ø15.88 mm
10.3.4. Refrigerant piping
•
Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit. (Additional charging,
etc.)
Vaccum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.
CAUTION
Use two wrenches and tighten with regular torque.
10.3.5. Indoor unit drain piping
39
Содержание CS-F14DD3E5
Страница 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...
Страница 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...
Страница 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...
Страница 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...
Страница 12: ...6 3 CU B18DBE5 12 ...
Страница 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...
Страница 14: ...7 2 CU B14DBE5 14 ...
Страница 15: ...7 3 CU B18DBE5 15 ...
Страница 17: ...8 2 Remote control display 17 ...
Страница 18: ...8 3 Remote control panel 18 ...
Страница 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...
Страница 86: ...86 ...
Страница 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...
Страница 88: ...13 3 Discharge and suction pressure 13 3 1 Saturation temperature of discharge and suction pressure COOLING 88 ...
Страница 89: ...HEATING 89 ...
Страница 91: ...91 ...
Страница 93: ...93 ...
Страница 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...
Страница 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...
Страница 98: ...13 7 Operating characteristics S C Starting Current R C Running Current IPT Power Consumption 98 ...
Страница 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...
Страница 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...
Страница 102: ...CU B14DBE5 CU B18DBE5 102 ...
Страница 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...
Страница 105: ...15 2 Outdoor unit OUTDOOR UNIT PRINTED CIRCUIT BOARD MAIN 105 PHAAM Printed in Malaysia SFYW0605 01 ...