62
* The horizontal vane angle tolerance is /- 5 degree.
14.4.2 Horizontal
Airflow
The horizontal airflow direction louver can be adjusted manually by hand.
14.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
When “FAN SPEED/QUIET” button at remote control is pressed continuously until QUIET will be shown
on remote control display.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. POWERFUL button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. When FAN SPEED/QUIET button is pressed again and fan speed is change to Low.
e. +8/15°C Heat is activated.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
4. During quiet operation, if timer “on” activates, quiet operation maintains.
5. After off, when on back, quiet operation is memorised.
C. Control contents
1. Fan speed is changed to QLo.
Figure 2
Step 1
110° (Inner Vane),
115° (Outer Vane)
Closed Position
Reference
point
Stopper
Step 2
Step 3
Step 4
Step 5
β°