15.4.22 F99 (Output Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an output over-current (DC peak current value at IPM Prevention
Control) is detected by checking the current that flows in the inverter DC peak sensing circuitry.
Malfunction Caused
Faulty outdoor unit PCB
Faulty
compressor
Troubleshooting
Checking the power transistor.
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using
the tester.
For the UVW, make measurement at the Faston terminal on the board of the relay connector.
Tester’s negative terminal
Power transistor (+)
UVW
Power transistor (-)
UVW
Tester’s positive terminal
UVW
Power transistor (+)
UVW
Power transistor (-)
Normal resistance
Several k
Ω
to several M
Ω
Abnormal resistance
0 or
∞
Содержание CS-CE12NKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Страница 14: ...14 5 2 Outdoor Unit ...
Страница 15: ...15 6 Refrigeration Cycle Diagram ...
Страница 16: ...16 7 Block Diagram ...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 18: ...18 8 2 Outdoor Unit ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit ...
Страница 22: ...22 10 2 Outdoor Unit ...
Страница 45: ...45 15 3 Error Codes Table ...
Страница 46: ...46 ...
Страница 74: ...74 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU CE9NKE ...
Страница 75: ...75 ...
Страница 76: ...76 ...
Страница 77: ...77 ...
Страница 78: ...78 17 1 2 CU CE12NKE ...
Страница 79: ...79 ...
Страница 80: ...80 ...
Страница 81: ...81 ...