15.4.18 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Air short circuit at indoor unit
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty outdoor unit fan motor
Excessive
refrigerant
Clogged expansion valve or strainer
Faulty outdoor pipe temperature sensor
Faulty outdoor unit PCB
Troubleshooting