34
12.5.2 OFF Timer Control
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time.
12.6 Auto Restart Control
1 When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
2 This type of control is not applicable during ON/OFF Timer setting.
3 This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
12.7 Indication Panel
LED POWER/DEICE
TIMER
Color Green Blue
Orange
Light ON
Operation ON
Deice Operation
Time Setting ON
Light OFF
Operation OFF
Time Setting OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, operation mode judgment, or ON timer
sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
Содержание CS-CE12NKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Страница 14: ...14 5 2 Outdoor Unit ...
Страница 15: ...15 6 Refrigeration Cycle Diagram ...
Страница 16: ...16 7 Block Diagram ...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 18: ...18 8 2 Outdoor Unit ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit ...
Страница 22: ...22 10 2 Outdoor Unit ...
Страница 45: ...45 15 3 Error Codes Table ...
Страница 46: ...46 ...
Страница 74: ...74 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU CE9NKE ...
Страница 75: ...75 ...
Страница 76: ...76 ...
Страница 77: ...77 ...
Страница 78: ...78 17 1 2 CU CE12NKE ...
Страница 79: ...79 ...
Страница 80: ...80 ...
Страница 81: ...81 ...