8.5.12. Anti Cold Draft Control
•
This operation is to prevent the Cold Draft during Heating mode operation.
•
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
•
For the first 30 sec. from compressor OFF (Termo OFF), Indoor fan speed will operate accordingly to the Indoor heat exchanger
temperature as shown below:
•
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
•
Anti Cold Draft Control will stop when:
−
Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
−
30 Minutes Time Save Control activates.
8.5.13. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
•
Normal Deicing
Deice operations detection commences after 60 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Read Switch) senses the outdoor piping temperature drops to -4°C (TRS CLOSE) or less for 50
sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
•
Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
•
Deicing ends when
1. 12 minutes after deicing operation starts;
2. The outdoor piping temperature rises to 12°C.
•
After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
24
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD
Содержание CS-A18DKD
Страница 11: ...4 2 Outdoor Unit 4 2 1 CU A18DKD CU A24DKD 11 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 12: ...5 Refrigeration Cycle Diagram 12 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 13: ...6 Block Diagram 13 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 14: ...7 Wiring Diagram CS A18DKD CU A18DKD CS A24DKD CU A24DKD 14 ...
Страница 25: ...Normal Deicing Time Diagram Overload Deicing Time Diagram 25 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 35: ...9 Operating Instructions 35 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 36: ...36 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 37: ...37 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 38: ...38 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 39: ...39 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 40: ...40 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 45: ...3 For the embedded piping 45 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 70: ...14 Technical Data 14 1 Thermostat characteristics 70 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 71: ...14 2 Operation characteristics 71 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 72: ...72 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 81: ...81 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...
Страница 83: ...19 2 Remote Control 83 CS A18DKD CU A18DKD CS A24DKD CU A24DKD ...