– 14 –
MAC9512086C2
CS-A181KE
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
•
Fan speed rotates in the range of Hi to Me.
•
Deodorizing Control.
Operation Details
Cooling Operation Time Diagram
*
1 Fan Speed is Hi until the compressor stops (when the room temperature reaches
setting temperature).
*
2 Fan Speed is Me after the compressor restarts.
<Description of operation>
d – g
:
Time Delay Safety Control (waiting for 3 minutes)
g – h
:
60 sec. Forced Operation
h – o
:
7 min. Time Saved Control
q – t
:
Anti Freezing Control
v – y
:
Outdoor Fan Control
Indoor
Fan
Comp.
SLo
SLo
SLo
SLo
ON
ON
OFF
stop
stop
stop
30"
stop
30"
160"
1
40"
40"
20"
✕
...
.
2
✕
...
.
a b c d e f g h i j k l m n o p q r s t u v w x y z
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
4 Way Valve
2 Way Valve (A241K)
1’
3’
1’
7’
1’
4’
1.5˚C
ON
OFF
Comp.
Intake Air
Temperature
Comp.
Set Temp.
Indoor
Heat
Exchanger
Temp.
10
°
C
2
°
C
Hi
Hi
Hi Lo Lo Lo Hi
Outdoor Air
Temperature
31˚C
29˚C
Operation
Stop