INSTALLATION

INSTALLATION

INCOMING COLD SUPPLY

M

DC

DC

DC

TO
EXTERNAL
TAP

SINK

WATER SOFTENER (IF NECESSARY)

WM or DWM

WHB

W.C.

DC

DC

SH

DHW

WHB

WC

BATH

SCV

SCV

P&T

ERV/NRV

PRV

DCV

Note:  
Cold supplies to single taps must be 

taken from the mains cold water 

system.
Cold supplies to mixer taps must be 

taken from the balanced cold water 

connection on the combination 

valve.

General Restrictions

a.  The highest hot or cold water draw off point should not exceed 10 metres above 

the Pressure Reducing Valve.

b.   An ascending spray type bidet or any other appliance with a Class 1 back-syphonage 

risk requiring a type A air gap should not be used.  

c.   Aquarea should not be used where steam is the primary heating medium, or in a 

situation where maintenance is likely to be neglected.

d.  Unvented cylinders are not suitable  for use with solid fuel boilers.

e. 

If the supply to the mixer fittings (other than a dual outlet type) is not taken 

from the balanced supply the system will become over pressurized and cause 

the pressure relief valve to discharge.  Over time this could also cause the 

premature failure of the appliance itself which will not be covered by the 

warranty.

f.   In larger properties with a number of bathrooms/en-suites and long pipe runs 

we would recommend that the balance cold supply is provided with its own 

pressure reducing valve and is not taken from the balanced cold connection on 

the combination valve.  In this case it will also be necessary to fit a small expansion 

vessel on the balanced cold water system to accommodate the pressure rise caused 

by the increase in temperature of the balanced cold water.

g.   Check the performance requirements of the terminal fittings with regard to flow/

pressure are suitable.

Shower Fittings

Aerated taps are recommended to prevent splashing. Any type of shower mixing valve 

can be used as long as both the hot and cold supplies are mains fed.  However, all 

mains pressure systems are subject to dynamic changes particularly when other hot 

and cold taps/showers are opened and closed, which will cause changes in the water 

temperature at mixed water outlets such as showers.  For this reason and because 

these are now no more expensive than a manual shower we strongly recommend 

the use of thermostatic showers with this appliance.  These must be used in 3 storey 

properties where the impact on pressure/temperature of opening another tap in the 

system is greater than normal. The shower head provided must also be suitable for 

mains pressure supplies.

Pipe Layout

In all mains pressure installations it is important 

to remember that the incoming cold supply 

must be shared between all terminal fittings.  It 

is important that a 22mm supply is brought to 

the appliance and a 22mm take-off is continued 

at least to the bath.  If there are two baths, 28mm 

pipework should be considered.  One metre of 

smaller diameter pipework, or flow restrictors, 

should be provided on the final connection to 

all outlets so as to balance the water available.  

In any event the distribution pipework should 

generally be in accordance with BS EN 806-1 to 5.

Plastic Pipework

This appliance is suitable for use with 

plastic pipework as long as the material 

is recommended for the purpose by the 

manufacturer and is installed fully in accordance 

with their recommendations.

Secondary Hot Water Circulation

Some models are fitted with a secondary 

return tapping as standard (see table 1 for 

details).  If fitted, an extra expansion vessel 

may be necessary.  A non-return valve MUST 

be FITTED near the return connection.  No valve 

or terminal fitting should be installed between 

the non return valve and the cylinder. All pipes 

kept hot by the secondary circulation should 

be insulated.

Содержание Aquarea Tank Duo GH 200

Страница 1: ...esign Installation Servicing Instructions Models covered in this manual Aquarea Duo 200 300 litres Aquarea Duo Pre plumbed 200 300 litres Unvented cylinders specifically designed to work with a heat pump ...

Страница 2: ...se of the appliance by a person responsible for their safety Children should be supervised at all times to ensure they do not play with the appliance This information is provided to assist generally in the selection of equipment Responsibility for selection and specification of our equipment must however remain that of our customer and any experts or consultants concerned with the installation s P...

Страница 3: ...Opening temperature of P T Relief Valve 92 95 C Energy cut out thermostat setting 82 C Max working pressure Primary heat exchanger Indirect models 6 bar Immersion heater rating 3kW 240V AC All cylinders are manufactured in accordance with the requirements of BS EN 12897 The tundish must be positioned so that it is visible to the occupant and is away from electrical devices Components supplied with...

Страница 4: ...ze volume litres 24 35 Expansion vessel initial charge pressure bar 3 3 Height mm 1992 2030 Diameter mm 550 630 Buffer vent A mm 2000 2037 Buffer connections B mm 1657 1752 T P relief valve C mm 1235 1330 Hot supply D mm 1190 1330 Heat pump flow E mm 1440 1510 Secondary return F mm 1127 1170 Control thermostat x2 G mm 495 560 Heat pump return H mm 265 310 Immersion heater J mm 220 240 Cold feed K ...

Страница 5: ...5 Expansion vessel initial charge pressure bar 3 3 Height mm 1992 2030 Diameter mm 550 630 Buffer vent A mm 2000 2037 Buffer connections B mm 1657 1752 Cold feed C mm 1110 1205 Hot supply D mm 1190 1330 Tundish E mm 690 825 Secondary return F mm 1127 1170 Heat pump flow G mm 963 1000 Control thermostat x2 H mm 495 560 Immersion heater J mm 220 240 Heat pump return K mm 390 433 Primary heat exchang...

Страница 6: ...urn compression 11 Control thermostat 22mm dual pocket 12 HP return 28mm plain pipe 13 Immersion heater 1 female 14 Cold feed 22mm plain pipe 15 Three port motorised valve Part G3 loose components supplied in a separate box A Combination inlet group incorporating pressure reducing valve strainer check valve balance cold take off point expansion relief valve and expansion vessel connection points B...

Страница 7: ... dual pocket 12 HP return 1 compression 13 Immersion heater 1 female 14 Three port motorised valve 15 Combination inlet group incorporating pressure reducing valve strainer check valve balance cold take off point expansion relief valve and expansion vessel connection points 16 Auto bypass 17 System pressure gauge 18 Filling loop Part G3 loose components supplied in a separate box A Potable expansi...

Страница 8: ...ion heater for backup and sterilisation purposes The multi pass arrangement of the coil enables high flow rates to be passed through it withlowpressurelosses Theimmersionheaterisusuallycontrolledbytheheatpump control system which determines when it needs to run based upon the parameters selected by the commissioning engineer The product is supplied with a full divert 3 port valve as the energy cut...

Страница 9: ...mended for new systems or to some lesser standard where practical constraints dictate The pipe connecting the heat pump flow to the appliance must not be less than 22mm copper or equivalent Further guidance on converting heat loss limits to insulation thickness for specific thermalconductivitiesisavailableinTIMSA HVACguidanceforachievingcompliance with Part L of the Building Regulations INSTALLATI...

Страница 10: ...eat Pump Selection Guide 1 Flow rates in various units for comparison with heat pump manufacturers data m3 h 0 50 0 75 1 00 1 25 1 50 1 75 2 00 2 25 2 50 2 75 3 00 3 25 3 50 3 75 4 00 4 25 l min 8 33 12 50 16 67 20 83 25 00 29 17 33 33 37 50 41 67 45 83 50 00 54 17 58 33 62 50 66 67 70 83 l sec or kg s 0 14 0 21 0 28 0 35 0 42 0 49 0 56 0 63 0 69 0 76 0 83 0 90 0 97 1 04 1 11 1 18 2 Velocity in pi...

Страница 11: ...ings Aeratedtapsarerecommendedtopreventsplashing Anytypeofshowermixingvalve can be used as long as both the hot and cold supplies are mains fed However all mains pressure systems are subject to dynamic changes particularly when other hot and cold taps showers are opened and closed which will cause changes in the water temperature at mixed water outlets such as showers For this reason and because t...

Страница 12: ...the discharge be of metal and a Be at least one pipe size larger than the nominaloutletsizeofthesafetydeviceunless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i e discharge pipes between 9m and 18m equivalent resistance length should be at leasttwosizeslargerthanthenominaloutlet size of the safety device between 18 and 27m at least 3 sizes larger and so on Ben...

Страница 13: ...ccupiedby blind infirmordisabledpeople considerationshouldbegiventotheinstallation of an electronically operated device to warn when discharge takes place Safety The safety devices supplied or fitted on an Aquarea are selected for their suitability for the temperatures and pressures involved They must not be changed removed or by passedanditisessentialthatonlygenuinereplacementpartssuppliedorappro...

Страница 14: ... having a contact separation at least 3mm see diagram above Danger of electrocution before making any adjustments to the thermostat isolate the immersion heater from the mains electricity supply at the fuse spur unit The immersion heater thermostats incorporate a manual reset safety overheat cut out thermostat Should this operate investigate the cause for the operation cut out before pressing the ...

Страница 15: ...port B Power is supplied to the 3 port valve when in cylinder charging mode Therefore the cylinder cannot be heated if there is no power to the valve The cylinder tank sensor sends accurate temperature information to the remote control unit this information coupled with the program times controls the cylinder charging If the cylinder is not heated quickly enough the Boost immersion heater will fun...

Страница 16: ... N L N COOL HEAT N CLOSE OPEN 2 3 4 5 6 Lead wire cord 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Booster Heater Cord Solar Three way Valve Cable Tank OLP Cable Tank Sensor Cable External Controller Cable Solar Pump Station Cable Room Thermostat Tank temperature sensor AB B To the heating system AB A To the tank Spannungslos Valve de energized Valve energized 3 way valve C 1 C 1 2 Dual Aqau S...

Страница 17: ...n cause damage unless the appliance is adequately flushed and refilled with the mains water immediately on completion of the disinfection procedure Damage caused through a failure to do this adequately will not be covered by the warranty For the above reasons we recommend the use of a non chlorine dased disinfectant such as Fernox LP Sterox as manufactured by Cookson Electronics when carrying out ...

Страница 18: ...re in the system stabilises This is quite normal with these types of systems and does not indicate a fault In some areas the water will initially appear cloudy but will quickly clear when left to stand This is nothing to be concerned about and is due to aeration of the water WARNING Ifwaterisseenflowingthroughthetundish thisindicatesafaultcondition which needs action If the discharge is hot and co...

Страница 19: ...ipes from temperature and expansion relief valves are free from obstruction and blockage and are not passing any water 5 Check the condition and if necessary descale the heat exchangers in hard water areas 6 Check that water pressure downstream of pressure reducing valve is within the manufacturers limits 7 Check operation of motorised valve 8 Check the pressure on the air side of the expansion ve...

Страница 20: ...electrical ensure that the immersion heaters are isolated from the mains before re setting the energy cut out If the immersion heater s need replacing this should be done with the units supplied from Aquarea See page 14 for more details Discharge From Relief Valves If cold water is discharging from the expansion relief valve into the tundish check the pressure on the expansion vessel when cold and...

Страница 21: ...tion valve clean YES YES YES YES NO NO NO Clear obstructions Is system free from restrictions blockages YES NO Is pressure reducing valve in combination valve working Clean or replace as required Is expansion vessel charge pressure correct Replace ERV TPRV Replace PRV END START Is pressure downstream of pressure reducing valve correct Is valve seal and seat clean undamaged Is heater operating at l...

Страница 22: ...r 1 SG021 5 flexible hose 1 SG024 6 24 litre expansion vessel 1 XG192 7 35 litre expansion vessel 1 XG193 8 Wall mounting bracket for 35 litre expansion vessel 1 XG058 9 3 port valve 1 XC015 10 Junction wiring box 12 way 1 XG129 11 Control and overheat limit thermostat 1 XG213 12 15mm x 22mm tundish 1 XG207 13 TWA sensor 1 GT529 14 1 2 Automatic air vent 1 GT015 15 1 immersion blank 1 FT467 16 50m...

Страница 23: ...d House 40 New Road Stourbridge West Midlands DY8 1PA TELEPHONE 01384 442611 FAX 01384 442612 Water Savings Water Related Costs Can Be Reduced By Good Plumbing Practice TAPS MIXERS SHOWERS Unregulated 25 30 l m Regulated 10 12 l m Over 20 l m 5 6 or 8 l m 2 tap half open Fitted with regulator Unregulated 4 Fixing Options For Taps Mixers 1 MK Range Combined Regulators Aerator forscrewingontoTaps Mi...

Страница 24: ...ure you have a good hold e Taking the lead for team lifts As more than one person is required for these products ensure that one person is taking the lead This may be you so ensure that each person that is helping is made aware of the weight and of the items listed within this assessment Make sure you and any others helping know the route you intend to take that it is clear of any obstructions Nev...

Страница 25: ...ddress in UK or Ireland free of charge during the first year after delivery by us ii thereafter at a charge of one twenty fifth of the then current list price during the second year after delivery by us and increasing by a further one twenty fifth on the second and subsequent anniversary of delivery by us ACTION IN THE EVENT OF FAILURE We will require the return of a cylinder which develops a leak...

Страница 26: ...ate will then be issued to the customer Heating and Hotwater Industry Council HHIC www centralheating co uk demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference Failure to install and commission this equipment to the manufacturer s instructions may invalidate the warranty but does not affect statutory rights Customer name T...

Страница 27: ...ame Telephone No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date Engineer name Company name Telephone No Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Comments...

Страница 28: ... the latest design and installation manuals available from our technical support team or on our website It is an offence to copy or adapt this document without consent of the owner Panasonic UK Panasonic House Willoughby Road Bracknell Berkshire RG12 8FP Tel 01344 853182 Fax 01344 853021 Technical 01344 853393 uk aircon salesadmin eu panasonic com www aircon panasonic co uk ...

Отзывы: