Item
Specifications
Upper limit / lower limit
comparison
Output if the value is outside the preset upper limit or lower limit.
Setting range: -32768 to +32767
Max. / Min. hold
Holding max. / min. values sampled
Disconnection detection
Disconnection detection is possible for the following ranges. Possible to
select auto or manual resetting
● 1 to 5 V range (Detection level: 0.7 V or less)
● 4 to 20 mA range (Detection level: 2.8 mA or less.)
(Note 1)
The full scale (F.S.) on the accuracy of an analog voltage input range from +1 to +5 V and that of an
analog current input range from +4 to +20 mA are 0 to +5 V and 0 to +20 mA, respectively.
(Note 2)
When a value exceeding the rated value ±2% is set, the output is rounded to a value equivalent to the
rated value ±2%.
10.2.2 Output Specifications of the Analog Output Unit
■
Output specifications
Item
Specifications
No. of output points
4ch
Output range
(resolution)
Voltage
-10 to +10 V DC (Resolution: 1/64,000)
0 to +10 V DC (Resolution: 1/32,000)
-5 to +5 V DC (Resolution: 1/64,000)
0 to +5 V DC (Resolution: 1/32,000)
+1 to +5 V DC (Resolution: 1/25,600)
Current
0 to +20 mA (Resolution: 1/32,000)
+4 to +20 mA (Resolution: 1/25,600)
Conversion speed
50 μs/4ch
Exceeding the rated range
Possible to output up to the rated value ± 2%
With the 0 to 20 mA range, the lower limit is not supported for exceeding
the rated range.
Total accuracy
±0.2%F.S. or less (at +25
℃
)
±0.4%F.S. or less (at 0 to +55
℃
)
Output impedance (voltage output)
0.5 Ω or less
Maximum output current (voltage
output)
10 mA
Output allowable load resistance
(current output)
500 Ω or less
Insulation method
Between output terminals and internal circuit: Photocoupler and isolated
DC/DC converter
Between channels: Non-nsulated
Conversion execution / non-
execution channel settings
Possible to make non-converted channel settings.
Clipping function
Upper and lower output limits can be set for digital input values.
Setting range: -32,640 to +32,640
10.2 Performance Specifications
10-4
WUME-GM1AIO-01
Содержание AGM1AD8
Страница 2: ... MEMO 2 WUME GM1AIO 01 ...
Страница 4: ... MEMO iv WUME GM1AIO 01 ...
Страница 8: ... MEMO viii WUME GM1AIO 01 ...
Страница 12: ... MEMO 1 4 WUME GM1AIO 01 ...
Страница 18: ... MEMO 2 6 WUME GM1AIO 01 ...
Страница 26: ... MEMO 3 8 WUME GM1AIO 01 ...
Страница 38: ... MEMO 4 12 WUME GM1AIO 01 ...
Страница 54: ...REFERENCE 4 2 Setting Parameters and Performing I O Mapping 5 6 Max Min Hold Function 5 16 WUME GM1AIO 01 ...
Страница 58: ... MEMO 5 20 WUME GM1AIO 01 ...
Страница 68: ... MEMO 6 10 WUME GM1AIO 01 ...
Страница 79: ...Digital input value Analog output value 640 or less Output at 0 9 V 8 1 Voltage Range WUME GM1AIO 01 8 5 ...
Страница 84: ... MEMO 9 4 WUME GM1AIO 01 ...
Страница 94: ... MEMO App 4 WUME GM1AIO 01 ...
Страница 95: ...Record of Changes Date Manual No Record of changes August 2021 WUME GM1AIO 01 1st edition WUME GM1AIO 01 ...
Страница 96: ... MEMO WUME GM1AIO 01 ...
Страница 97: ... MEMO WUME GM1AIO 01 ...
Страница 98: ...Panasonic Corporation 2021 August 2021 WUME GM1AIO 01 ...