10.2 Performance Specifications
10.2.1 Input Specifications of the Analog Input Unit
■
Input specifications
Item
Specifications
No. of input points
8 ch
Input range
(resolution)
Voltage
-10 to +10 V DC (Resolution: 1/64,000)
0 to +10 V DC (Resolution: 1/32,000)
-5 to +5 V DC (Resolution: 1/64,000)
0 to +5 V DC (Resolution: 1/32,000)
+1 to +5 V DC (Resolution: 1/25,600)
Current
0 to +20 mA (Resolution: 1/32,000)
+4 to +20 mA (Resolution: 1/25,600)
Conversion speed
50 μs/ch
Exceeding the rated range
Possible to output up to the rated value ± 2%
With the 0 to 20 mA range, the lower limit is not supported for exceeding the
rated range.
Total accuracy
±0.2%F.S. or less (at +25
℃
)
±0.4%F.S. or less (at 0 to +55
℃
)
Input impedance
Voltage input: Approximately 1 MΩ; current input: Approximately 250 Ω
Absolute max. input
Voltage input: -15 V to +15 V; current input: -30 mA to +30 mA
Insulation method
Between input terminals and internal circuit: Photocoupler and isolated
DC/DC converter
Between channels: Non-insulated
Execution / Non-execution
channel settings
Possible to make non-converted channel settings.
Input range selection
Possible to make settings on a channel-by-channel basis
Average
processing
Number of
averaging
times
Setting range of 2 to 60,000 times
Time
average
Time setting range of 1 to 1,500 ms
Moving
average
Setting range of 2 to 2,000 times
Offset / Gain settings
A desired value within the digital output range can be set for the offset
value.
Setting range: -3000 to +3000
A desired value within the digital output range can be set for the gain value.
Setting range: +9,000 to +11,000 (90% to 110%)
Scale conversion settings
A desired value within the digital output range can be set for the scale
conversion setting value.
Setting range: -32768 to +32767
10.2 Performance Specifications
WUME-GM1AIO-01
10-3
Содержание AGM1AD8
Страница 2: ... MEMO 2 WUME GM1AIO 01 ...
Страница 4: ... MEMO iv WUME GM1AIO 01 ...
Страница 8: ... MEMO viii WUME GM1AIO 01 ...
Страница 12: ... MEMO 1 4 WUME GM1AIO 01 ...
Страница 18: ... MEMO 2 6 WUME GM1AIO 01 ...
Страница 26: ... MEMO 3 8 WUME GM1AIO 01 ...
Страница 38: ... MEMO 4 12 WUME GM1AIO 01 ...
Страница 54: ...REFERENCE 4 2 Setting Parameters and Performing I O Mapping 5 6 Max Min Hold Function 5 16 WUME GM1AIO 01 ...
Страница 58: ... MEMO 5 20 WUME GM1AIO 01 ...
Страница 68: ... MEMO 6 10 WUME GM1AIO 01 ...
Страница 79: ...Digital input value Analog output value 640 or less Output at 0 9 V 8 1 Voltage Range WUME GM1AIO 01 8 5 ...
Страница 84: ... MEMO 9 4 WUME GM1AIO 01 ...
Страница 94: ... MEMO App 4 WUME GM1AIO 01 ...
Страница 95: ...Record of Changes Date Manual No Record of changes August 2021 WUME GM1AIO 01 1st edition WUME GM1AIO 01 ...
Страница 96: ... MEMO WUME GM1AIO 01 ...
Страница 97: ... MEMO WUME GM1AIO 01 ...
Страница 98: ...Panasonic Corporation 2021 August 2021 WUME GM1AIO 01 ...