3-18
3.7 Memory backup battery
3.7.1
Installation of memory backup battery
(For FP-e unit with a calendar timer function)
Although FP-e units with a calendar timer have a built-in lithium battery, a lithium battery connector is not
connected to an FP-e unit connector. Follow the procedure as shown below to connect them.
1. Open the battery cover on the top of the FP-e
unit.
2. Connect the lithium battery connector to the
FP-e unit connector.
3. Place a lithium battery in the battery holder in
the FP-e unit.
4. Close the battery cover.
Note:
A calendar timer is available only when a battery is installed.
Install a new battery within a minute after removing the old battery.
3.7.2
System register setting
(For FP-e unit with a calendar timer function)
- Setting the battery error alarm
In the system register default settings, “No.4 Alarm Battery Error” is set to “OFF.” When using the battery,
set system register No. 4 of the control unit so that the battery error alarm is turned on.
PLC Configuration setting dialog box
- Setting procedure using FPWIN GR
1. Select “PLC Configuration” on the “Option
(O)” menu, and click on “Action on Error” tab.
2. Turn on “No. 4 Alarm Battery Error” check
box.
- Specifying the hold area
In order to use backup functions such as data registers, settings must be entered for system registers
Nos. 6 to 12.
For hold area setting using FPWIN GR, select “PLC Configuration” on the “Option (O)” menu, and click
on “Hold/Non-hold.”
Note:
Be sure to install a lithium battery when changing the hold area with the system register
or using the calendar timer function.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание AFPE214325
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 14: ...1 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 56: ...4 12 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 60: ...5 4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 66: ...6 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 67: ...Chapter 7 I I O Monitor Mode Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 69: ...Chapter 8 PID Control Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 80: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 81: ...Chapter 9 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 97: ...Chapter 10 Dimensions Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 98: ...10 2 10 1 Dimensions Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 99: ...Chapter 11 Appendix Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 228: ...11 130 11 7 ASCII Codes Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...