
DigitalFlow™ XGS868i Startup Guide
65
Appendix C. Measuring P and L Dimensions
Appendix C. Measuring P and L Dimensions
C.1 Introduction
When programming the PIPE menu in the Model XGS868’s
User Program, the path length (P) and the axial dimension
(L) must be entered. These parameters are determined by measurements on the actual transducer installation, with
P equal to the face-to-face distance between the transducers and L equal to the axial distance between the centers
of the transducer faces.
The accuracy of the programmed P and L values is critical to precise flow rate measurements. If Panametrics
supplies the flowcell for the system, the correct values will be included in the documentation supplied with the
system. For transducers installed on an existing pipe (see Figure 22 on page 66), P and L must be measured at the
site. This appendix provides instructions for properly determining these dimensions.
C.2 Measuring P and L
Whenever possible, physically measure the face-to-face distance (P) and the axial distance (L) between the centers
of the flat faces of the transducers. Refer to Figure 22 on page 66 for an illustration of the proper distances to
measure, in a typical installation.
In some situations only one of the required distances can be directly measured. When this happens, a knowledge of
the installation angle (
) of the transducers, permits the second distance to be calculated from Equation C-1 below:
As an example, assume that the transducer installation angle is known to be 45° and the L distance is measured to
be 10.00 inches. Then, the P distance is calculated to be P = 10.00/0.707 = 14.14 inches.
With a Bias 90° transducer installation, it sometimes happens that the only known parameters are the transducer
angle (
) and the centerline distance between the transducer bodies (CL). In these cases, it is still possible to
calculate P and L by combining Equation C-1 above with the additional Equation C-2 below (see Figure 22 on
page 66):
Standard Panametrics 90° transducers have the face offset from the centerline of the body by 0.6 inches. Thus, a pair
of transducers has a total offset of 1.2 inches, as indicated in Equation C-2 above. For example, suppose that the
transducer installation angle is 30° and CL is measured to be 12.00 inches. Then, P = 12.00 – 1.2 = 10.80 inches and L =
10.80 x 0.866 = 9.35 inches.
cos
L
P
---
=
P
CL 1.2
–
=
Содержание DigitalFlow XGS868i
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 48: ...DigitalFlow XGS868i Startup Guide 40...
Страница 60: ...Chapter 3 Operation 52 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 66: ...Appendix A CE Mark Compliance 58 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 72: ...Appendix B Data Records 64 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 78: ...Index 70 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 80: ...Warranty 72 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 82: ...74 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 84: ...76 DigitalFlow XGS868i Startup Guide no content intended for this page...
Страница 85: ......