Suspension
After determining the number and exact position of appliances and hangers,you have to provide for hanging them at a minimum of 400
mm (hanging chains for example). This is necessary, so it does not hinder the length change, which increases during thermal expansion,
hereby appliances does not deform. Install hangers under the roof structure, under buttresses or scaffolding among columns or nearby
wall. The suspension of appliances have to be executed by hanger located on the fan side of burner and combination brackets.
The minimal mounting height
Minimum pitch and maximum angle of combustion and radiant tubes, always 0°!
Example for location of suspensions
ZENIT
Tube
location
Minimum installation height for input power
10 kW 15 kW 20 kW 25 kW 30 kW 35 kW 40 kW 45 kW 50 kW 55 kW 60 kW
„U”
form
Horizontal
3.4 m
3.7 m
4.0 m
4.2 m
4.4 m
4.6 m
4.9 m
5.2 m
5.4 m
5.7 m
5.9 m
30°
3.0
m
3.2
m
3.4
m
3.7
m
3.9
m
4.1
m
4.3
m
4.6
m
4.8
m
5.0
m
5.3
m
„I” form
Horizontal
3.2
m
3.5
m
3.7
m
4.0
m
4.2
m
4.5
m
4.7
m
5.0
m
5.2
m
5.4
m
5.6
m
30°
2.7
m
3.0
m
3.2
m
3.4
m
3.6
m
3.9
m
4.1
m
4.3
m
4.5
m
4.7
m
4.9
m