TYPE TUBE RADIANT HEATER 

Instructions for Installation and Servicing

Operation of automatic burner control (SIT 579 DBC)

WARNING! Before every maintenance the appliance must be detached from the electrical supply and 

the gas supply must be turned off! 

Disregard of these instructions can result in death, injury or property damage!

Carry out starting test and check the regular operation of appliance.

Checking of the regular operation.

Two kind of supervision should be fulfilled:

a)  Switch on the appliance, let it operate some minutes, then turn off the gas valve. The burner stops the operation. Wait for 6-8 

seconds,then turn on the gas valve once more, the appliance starts the operation again..

b)  Let it operate some minutes. Then take down the exhaust end of heat radiant tubes and close the vent opening. The differen

-

tial pressure switch switches over to OFF position from ON. The automation closes the solenoid valve and the appliance stops 

and red control lamp is lighting.

 

Remove the closing of tube and reset the original condition. Start the appliance again by interruption then reconnecting of 

mains voltage.

Check at the beginning of season

9.

     Maintenance

The ZENIT 

-type tube radiant heater appliance apart from the supervision and cleaning of radiant tubes (see: Maintenance supervi-

sion by the customer), do not need extra maintenances but to be able  to preserve the SAFETY OPERATION and LONG LIFETIME of 

appliance it is recommended to have yearly supervision done by qualified service department.

Maintenances

Maintenance supervision must include the following:

Maintenance supervisions by the customer

a) Supervision and cleaning of heat radiant tubes.

  Clean the external surface of tubes from any dust by a brush and make sure that there is not any burnout or warping.

b) Check connection and sealing of burner tube and heat radiant tubes by a survey. In case there is lack of sealing, colouring shows it.

c)  Check the condition of reflectors if necessary clean them. Clean them by a soft cloth or diluted detergent.

d) Check the suspensions, make sure that the load is distributed smoothly at all mountings. You can check it moving each hanger a little.

e) Cleaning the flue pipes.

Remove the barrier by the combustion product and reset the original condition

Restart the device by interrupting and resetting the power supply.

It is advisable to make a maintenance contract for the proper maintenance or call our qualified service department for regular mainte

-

nance.

In case during 5 seconds sparking (ignition) the continuous flame shape is stabilized, - and stable electrical signal is come back from the 

electrode – the appliance operates and the green control lamp is lighting. During operation of appliance its automatic burner control con-

trols the condition of differential pressure switch and signals coming from the flame control continuously, and if the position of differential 

pressure switch is changed – it is switched over from work position to rest – or the signal from the ionization flame control is interrupted 

then it stops the gas supply of burner. The fan continues to rotate, none of control lamps is lighting.

In case during the burning process the pressure decrease under the permissible minimal value on the positive side of air pressure (from 

the fan side), then automation prohibits:

 

- gas supply and fan stops

The fan continues to rotate, none of control lamps is lighting.

In case during burning process the pressure increases above the permissible maximum value on the negative side of air pressure switch 

(from the burner tube side, eg. at combustion back),then it switches back to rest position and the automation prohibits.

-  gas supply and fan stops

The appliance stands into error position and red control lamp is lighting.

Restart is possible after the switching off and on of mains voltage

.

Following the switched on voltage the fan operates continuously assuring the 30 seconds pre-purge time. This time period ensures the 

three times air change of combustion volume in case of biggest appliance’s power.

When the pressure is suitable  - after 30 seconds – the sparking happens and the solenoid valve opens in this way the gas catches fire. 

The  flame sensor is self-monitoring and only performs an intervention on the burner it controls, insensitive to other environmental effects 

(eg.: external heat, light)

Содержание ZENIT 70+

Страница 1: ...EN www pakole com Zenit70_009_004 006_011_210601_V004_EN Appliance types ZENIT 70 12 48 kW PROPANE OR NATURAL GAS FIRED ZENIT TUBE RADIANT HEATER User s Manual...

Страница 2: ...9 Electrical connection scheme of SIT 579 DBC automatic burner control 9 Optional accessories 10 Control of appliance 11 Protective distances 12 Combustion air supply 14 6 Air supply and venting syst...

Страница 3: ...not play with devices ATTENTION Fire burning inhalation and explosion hazard Keep all flammable objects as follows building materials papers or carton unites away from heater according to the instruct...

Страница 4: ...larly worn or damaged in that case exchange it for a new one specified by manufacturer Preserve the equipment in genuine condition do not leave it to grow old Do not use seriously aged equipment any l...

Страница 5: ...fice or the closest dealer and ask for further informations ATTENTION COMPULSORY EARTHING ATTENTION ONLY QUALIFIED PERSON CAUTION DANGER CAUTION ELECTRIC SUPPLY According to the installation project i...

Страница 6: ...d board box The unpacking process of the appliance unload the burner the tubes and the accessories from the card board box do not remove the protection cap from the burners gas connection or from the...

Страница 7: ...tion Burner Combined hanger Radiant tube Reflector Isolation Spacer plate Isolation cover End cap Flue gas analyzer nozzle Lower clip Burner hanger Fresh air intake Burner fixing clamp Electric connec...

Страница 8: ...THING Electrical connection The combustion air supply centrifugal fan is fixed to the appliance burner head the automatic burner control is located in the burner head in this way the electrical supply...

Страница 9: ...re Connection points of SIT 579 DBC automatic burner control box Work out the electrical network system regarding to the diagram to the was attached to the appliance If the switcher position is 0 does...

Страница 10: ...perature controllers for the appliance these can be purchased at the appliance manufacturer Optional accessories Thermostat 18 picture Temperature controllers FP 1D 2 point regulation thermostat FP 3D...

Страница 11: ...sensation of temperature be continuously served during an economical operation That the reduced input can be 50 or 60 it depend on the length of pipes and the temperature of exiting combustion product...

Страница 12: ...ust comply with the valid standards Disregard of these instructions can result in death injury or property damage Protective distances Protective distances to be kept considering flammable materials 2...

Страница 13: ...tch and maximum angle of combustion and radiant tubes always 0 Example for location of suspensions ZENIT Tube location Minimum installation height for input power 10 kW 15 kW 20 kW 25 kW 30 kW 35 kW 4...

Страница 14: ...ystem In this case the combustion air must be conducted to the device from the external space Example for outside combustion air supply Tube length for combustion air supply 6 meter with one elbow fro...

Страница 15: ...e longer flue gas pipe can also be employed In such cases the maximum equipment length the fume discharge can be 30 meters in aggregate but the flue gas pipe section above 6 meters must always be heat...

Страница 16: ...f the flame control of burner automation does not register flame during the safety time than repeats the all ignition procedure maximum two times If in this time there is not registered flame then it...

Страница 17: ...that the load is distributed smoothly at all mountings You can check it moving each hanger a little e Cleaning the flue pipes Remove the barrier by the combustion product and reset the original condi...

Страница 18: ...ion of combustion air fan Check whether the wheel of fan is able to revolve free and remove the possible contaminations from revolving blades Maintenance supervisions by a qualified service department...

Страница 19: ...x x ZENIT 70 18 18 7 x x x x ZENIT 70 20 20 x x x x ZENIT 70 22 22 7 x x x x ZENIT 70 24 24 2 x x x x ZENIT 70 26 26 x x x x x x ZENIT 70 28 28 2 x x x x x x ZENIT 70 30 30 3 x x x x x x ZENIT 70 32...

Страница 20: ...ENIT 70 18 11 18 7 11 6 x x x x ZENIT 70 20 12 20 12 6 x x x x ZENIT 70 22 12 22 7 12 8 x x x x ZENIT 70 24 14 24 2 14 8 x x x x ZENIT 70 26 15 26 15 9 x x x x x x ZENIT 70 28 16 28 2 16 3 x x x x x x...

Страница 21: ...4 09 3 95 Type Input power kW Gas consumption m3 h kg h Natural gas Propane Butane Propane ZENIT 70 12 12 6 8 9 1 32 0 93 1 05 0 74 1 02 0 72 ZENIT 70 14 14 8 9 9 1 55 1 04 1 24 0 83 1 2 0 8 ZENIT 70...

Страница 22: ...0 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 60 2 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 23: ...0 Minimum heat output as percentage of nominal heat output 61 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 61 6 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 24: ...0 Minimum heat output as percentage of nominal heat output 63 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 63 2 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 25: ...Minimum heat output as percentage of nominal heat output 61 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 64 3 Envelope insulation class U 0 0 W m2K Radiant factor at mi...

Страница 26: ...0 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 65 2 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 27: ...0 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 66 1 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 28: ...0 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 60 7 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 29: ...90 Minimum heat output as percentage of nominal heat output 61 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 62 1 Envelope insulation class U 0 0 W m2K Radiant factor at...

Страница 30: ...0 Minimum heat output as percentage of nominal heat output 63 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 63 7 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 31: ...20 Minimum heat output as percentage of nominal heat output 61 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 64 6 Envelope insulation class U 0 0 W m2K Radiant factor at...

Страница 32: ...0 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 65 8 Envelope insulation class U 0 0 W m2K Radiant factor at m...

Страница 33: ...10 Minimum heat output as percentage of nominal heat output 62 0 Radiant factor Envelop losses Radiant factor at nominal heat output RFnom 66 5 Envelope insulation class U 0 0 W m2K Radiant factor at...

Страница 34: ...y not authorized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caus...

Страница 35: ......

Страница 36: ...PAKOLE TRADE Ipari s Kereskedelmi Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 www pakole com mail pakole hu Tel 36 22 316 484 www pakole com...

Отзывы: