Operation and Maintenance Documentation
Diagram of connection of one ACR 100-150-200 E curtain (electric heater) to the COM-
FORT panel
• 400V/50Hz power supply; wire cross section; current protection circuit
• min. 5 x 2,5 mm˛ for G100E ; (B16)
• min. 5 x 2,5 mm˛ for G150E; (B20)
• min. 5 x 4 mm˛ for G200E; (B25)
• Control Panel COMFORT - 3-speed fan control with thermostat, (OMY 5x 1.0mm˛)
•
In the MASTER curtain between the L1-NC terminal, replace the factory-made fuse (C 3.15) with C 6.3
• 400V / 50Hz power supply; wire cross section; current protection of the system - should be selected according to the
•
parameters of the individual versions of the curtains
• COMFORT control panel - 3-speed fan control with thermostat (OMY 5x 1.0mm˛)