Pump EcoVISE, EcoP01
MA25-06E
ENGLISH
Parameters and menu system
Menu: View parameters
Time
24 hours display
Weekday
Mon = 1 ... Sun = 7
Weekly Timer program
OFF = Timer not activated
Actual speed
Rpm
Actual power consumption
Watt
Run time
Hours
Motor temperature
Temp < 100C = Fine
Status Digital input 1
OFF = Input not activated
Status Digital input 2
On = Input activated
Status Analog output
Activated / Not activated
Error code
1 = Too low DC-voltage
2 = Too high DC-voltage
4 = Too high temperature
5 = Too high motor temperature
10 = Power current error
20 = Overload at startup
64 = Short circuit
97 = Multiple errors
98 = Communication error
Software version
8.013
Configuration: Parameters setting
SP1
Speed ”ECO”
SP2
Speed ”MED”
SP3
Speed ”HIGH”
CLoc
Time of day
ti1–9
Weekly timer
t1 on
Day/s, time, speed
t9 off
End time
rEL
Analogue output is open collector type and may be loaded
with max 100mA.
0 = Output off
1 = Output active at speed “ECO”
2 = Output active at speed “MED”
3 = Output active at speed “HIGH”
4 = Output active at error
5 = Output active at high motor temperature
6 = Pump effect limited due to high temperature
d1
Digital input 1
1 = Change to speed “ECO”
2 = Change the speed “MED”
3 = Change to speed “HIGH”
4 = Change to “HIGH” speed for 180 seconds
d2
Digital input 2
1 = Change to speed “ECO”
2 = Change the speed “MED”
3 = Change to speed “HIGH”
4 = Change to “HIGH” speed for 180 seconds
Priti
The time [s] the pump is running at speed "HIGH" at startup
rESEt
Reset factory settings
END
Exit the configuration menu