3” Air intake
4” Exhaust
Figure 10: 4 x 3 inch Flue adapter.
Depending on the amount of room available for the installation of the Tofino, the installer may want to remove
the flue adapter and attach it to the flex tubes which will have previously been inserted down the chimney.
The installer must make sure that the air intake vent and air exhaust vents attach to the correct ports on
both the flue adapter and the vent terminal. The vent terminal and the flue adapter are marked with an “I” (air
intake) and “E” (air exhaust).
Venting
10’ to 40’ Use the 3x4 Configuration
10’ to 28’ Use the 3x4 and the 4” to 3” adapter Configuration
The i30 comes from the factory with a 3” intake and a 4” exhaust configuration. Whenever possible, this
configuration should be used. However, a 4” to 3” optional reducer (Figure 11) can be used on the exhaust
for venting lengths between 10’ and 28’ if necessary. Be advised that using this optional adapter may have
an impact on flame appearance and is not recommended for use with the glass burner option while operat-
ing with propane gas.
Installation Advisory
Installation Tip
Figure 11: 4 inch to 3 inch
exhaust adapter.
Optional 4” to 3” exhaust adapter
Part number for the optional 4” to 3” exhaust adapter is 1227.0003.
12
130717-44 5055.990-A
i30 TOFINO