background image

Page

10 of 40

Number

PM820010

HVAC: SmartAir eHVAC System

E. Linear Power Module

This module controls the amount of voltage delivered to

 

the evaporator blower creating variable blower speeds. It 
is located in the return air in front of the evaporator coil.

Figure 5.

Linear Power Module

F. Discharge Temperature Sensor – Freeze 

Switch

This  sensor  monitors  the  evaporator  outlet  temperature 
as it enters the vehicle duct system.

Figure 6.

Discharge Temperature Sensor

G. Evaporator Blower

This  blower  pulls  air  through  the  evaporator  coil  and

 

blows conditioned air into the interior of the sleeper. 

H. Condenser Fan

This blower draws air through the condenser coil to cool 
the refrigerant flowing through the system. 

Figure 7.

Evaporator Blower and Condenser Fan

I. Battery Management System (BMS)

This  device  monitors  the  auxiliary  batteries  for  state  of 
charge, communicates with the EHVAC system and con-
trols  the  battery  separator  solenoid.  LED  light  on  this 
device  indicates  power  to  the  device  and  does  not  pro-
vide  diagnostics.  Power  inputs  to  this  device  are  fuse 
protected. 

If  one  of  the  BMS  fuses  blows,  the  solenoid  will  disen-
gage. 

Figure 8.

Battery Management System

J. Battery Separator 

This  device  connects  the  truck  batteries  to  the  EHVAC

 

batteries.  When  the  starting  batteries  are  at  or  above

 

13.2  volts,  the  battery  management  device  will  engage 
the solenoid to allow the alternator to charge the auxiliary 
batteries. When the voltage drops to or below 12.5 volts 
the battery management system will disengage the sole-
noid to prevent the truck starting batteries from being dis-
charged below the engine start level. 

Содержание SmartAir eHVAC System

Страница 1: ...ith the working components of the Peterbilt SmartAir eHVAC System and the proper steps and procedures to completely diagnose the Peterbilt SmartAir eHVAC System unit 2019 PACCAR Corporation Confidenti...

Страница 2: ...le 10 F Discharge Temperature Sensor Freeze Switch 10 G Evaporator Blower 10 H Condenser Fan 10 I Battery Management System BMS 10 J Battery Separator 10 INTERNAL COMPONENTS 12 A High Pressure Switch...

Страница 3: ...d Linear Power Module Testing 20 K Compressor Rubber Mounts 20 L Testing the Battery Management System BMS 21 M Can Bus 22 N Testing the Espar Heater Connected to the EHVAC Digital Controller 22 O Con...

Страница 4: ...box 11 Figure 10 High Pressure Switch 12 Figure 11 Compressor 12 Figure 12 Thermal Limit Switch on Compressor 12 Figure 13 Evaporator Inlet Filter 12 Figure 14 Relay Testing 18 Figure 15 Service Equip...

Страница 5: ...d oil manufacturers If accidental system discharge occurs ventilate work area before resuming service CAUTION The air conditioning system uses HFC134a R134a refrigerant and polyvinyl ether PVE refrige...

Страница 6: ...ttery negative cable from both battery boxes and dis charge any capacitors Disconnect the air starting motor if equipped to pre vent accidental engine starting Put a DO NOT OPERATE tag in the operator...

Страница 7: ...heavier than air and can accumulate near the floor in sumps and low lying areas Close the manual fuel valves prior to performing maintenance and repairs and when storing the vehi cle inside California...

Страница 8: ...and Relays Units built 8 1 2016 to Present F1 Fuse 10 Amp Mini This fuse provides short circuit protection for the System control NOTE Removing fuse F1 for 10 15 seconds will reset the sys tem contro...

Страница 9: ...ge to the compressor controller C Fan and Temperature Control Display LED Display Allows for temperature and Blower speed adjustment of the EHVAC Electrical Heating and Ventilation Air Condi tioning u...

Страница 10: ...Figure 7 Evaporator Blower and Condenser Fan I Battery Management System BMS This device monitors the auxiliary batteries for state of charge communicates with the EHVAC system and con trols the batt...

Страница 11: ...Figure 9 Battery Separator Solenoid located in the battery box Page 11 of 40 Number PM820010 HVAC SmartAir eHVAC System...

Страница 12: ...Compressor C Thermal Limit Switch on Compressor This is a normally closed auto reset switch to protect the compressor from high temperature Figure 12 Thermal Limit Switch on Compressor D Evaporator I...

Страница 13: ...d Unit has a low volt age disconnect of 11 2 volts 3 Check all fuses See Figure 17 Internal Wiring Diagram Before 8 1 2016 on page 28 and Figure 18 External Wiring Diagram on page 29 4 Check for 12 vo...

Страница 14: ...pressor Thermal Limit Switch on page 19 7 Check evaporator blower and linear power module See J Evaporator Blower Motor and Linear Power Module Testing on page 20 8 If all tests check OK a loss of ref...

Страница 15: ...d signal compressor or internal com ponent issue Amperage ranges 40 to 75 depending on settings and conditions 4 Check battery management device harness and sep arator 5 Same as 4 Unit is noisy or vib...

Страница 16: ...ires and battery cables 2 Check Aux batteries for Voltage Check for heater enable signal from EHVAC unit Heater unit has a low voltage disconnect of 10 6 volts See N Testing the Espar Heater Connected...

Страница 17: ...rtAir eHVAC System Heater blows cold air but no heat 1 Fuel 2 Fuel pump 3 Connections 4 Glow pin screen 5 Sensors See Espar Manual Table 2 ESPAR Heating System Diagnostic Table PROBLEM POSSIBLE CAUSE...

Страница 18: ...turn the EHVAC unit on if all safety switches are okay such as the high pressure switch temperature sensor freeze switch and the compressor thermal limit switch the Main Compressor controller will con...

Страница 19: ...ation on Service Instructions for Ring Terminal Controller and Compressor on page 33 You must remove the cover Do not attempt to test the controller or compressor until you have completely eliminated...

Страница 20: ...tage will vary depending on requested speed approximately 1 6 for low 2 6 for high If all voltages are correct and the fan does not run it is defective and needs to be replaced Using a DC ammeter you...

Страница 21: ...wiring harness With aux voltage okay LED flashing and 12 volts across pins 8 and 1 start the truck or connect the start batteries to a battery charger and bring the voltage above 13 2 for at least 15...

Страница 22: ...ss still connected to control and unit back probe harness You should measure 120 ohms Reconnect the harness to the BMS With all harnesses connected you should measure 60 ohms N Testing the Espar Heate...

Страница 23: ...ce unit 3 recover holding charge 4 evacuate leak test 5 recharge proper refrigerant level WARNING Before doing any of the work below be aware of the dangers involved Working with refrigerant could lea...

Страница 24: ...y counterclockwise CCW 2 Connect the electronic vacuum gauge to the recov ery station at the vacuum manifold using a valve and T fittings 3 Connect the recovery stations blue hose to the ser vice port...

Страница 25: ...nter the system and cause compressor damage NOTE Although your service equipment may appear physi cally different from the equipment shown here the function of the equipment used to perform each servi...

Страница 26: ...ecified amount of refrigerant 2 On the recovery station set the high side valve to CLOSED and the low side valve to CHARGE 3 Press the CHARGE button to start the charge proce dure When the system is f...

Страница 27: ...Table 4 Discharge Sensor Freeze Switch Testing Chart Page 27 of 40 Number PM820010 HVAC SmartAir eHVAC System...

Страница 28: ...I T E GND BLACK COND SIG WHI T E HEATER CONDENSER FAN 12 VOLTS RED CANH YELLOW CANL GREEN HEATER_OPTION RED VEHICLE ACCESSORY INPUT WHI T E IGNITION INPUT WHI T E 12_VOLTS_COMP RED ACCESSORY INPUT WHI...

Страница 29: ...HOLE WIRE GAUGE 2AWG WIRE GAUGE 2AWG WEBASTO FUEL OPERATED HEATER GROUND BROWN WHITE ESPAR FUEL OPERATED GROUND HEATER GROUND WHITE HEATER_OPTION RED ESPAR OPTION HEATER_EN BLACK HEATER_LVL BLUE HEAT...

Страница 30: ...PLICE_SENSOR GND BLWR FUSED BLWR RLY SIG BLWR RLY SIG 12 VOLTS 12 VOLTS 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 A A B B C C D D E E F F THE INFORMATION HEREON IS CONFIDENTIAL AND PROPRIETARY PROPERTY OF BERGS...

Страница 31: ...PWM ground switched output to control condenser fan speed 0V fan off 1 6 2 6V cooling mode Condenser fan 3 way connector C8 C9 C10 C11 C12 C13 BLWR_CTL Blue PWM ground switched output to control blow...

Страница 32: ...11 14V Relay in electrical center D11 COND_RLY _SIG White Switch to Ground output to relay 1 Condenser fan power from AUX Batteries 0 5V if on otherwise 11 14V Relay in electrical center D12 BLWR_RLY...

Страница 33: ...connector pins identified in FIGURE 1 After the controller with phase harness has been removed from the unit follow the below instructions to replace the phase harness W 1 Remove and retain cover 4 c...

Страница 34: ...ls of new harness over threaded posts of PCB and route wires as shown Align each colored wire to specific threaded post identified only 5 Secure wire terminals with 3 nuts Torque to 12 to 14 in lbs Us...

Страница 35: ...o avoid potential property damage or personal injury Read Important Safety Warnings and ALL instructions before attempting to install or service product Page 35 of 40 Number PM820010 HVAC SmartAir eHV...

Страница 36: ...o avoid potential property damage or personal injury Read Important Safety Warnings and ALL instructions before attempting to install or service product Page 36 of 40 Number PM820010 HVAC SmartAir eHV...

Страница 37: ...SPEED press ENTER until display shows FAN and SPEED Press up or down arrows to select 1 2 3 speed After 5 seconds selection will be set See Figure 22 Figure 22 Changing Blower Speeds ENTER Changing TE...

Страница 38: ...1 02 etc Use up and down arrows to scroll through the Fault Codes See fault code chart for definitions Table 6 Fault Code List Code Failure Description Solution O1 Evaporator Sensor Shorted high or mi...

Страница 39: ...open or shorted high 2 Evaporator sensor shorted low 3 High pressure switch open or shorted high Figure 26 Enter Service Mode ENTER ON OFF 13 HMI Temperature Sensor Error BLUETOOTH Controller only Sys...

Страница 40: ...t Amperage draw Pressing ENTER arrow after viewing service screen will return you to the fault code screen Pressing the ON OFF button will return you to the Tem perature Display screen Figure 27 Servi...

Отзывы: