p5 FutureNow FNIP-4xSH-12 Скачать руководство пользователя страница 6

 

P5 Kft. 

2014 

www.futurenow.hu

 

_____________________________________________________________________________________________ 

 

FutureNow FNIP-4xSH Installation Manual rev 15.01.2014 

 

The inputs use low voltage signals. The inputs use low voltage signals. 

 

All  wires  used  and  the  way  they  are  run  must  be  in  accordance  with  the  local  electrical 
codes. 

 

Keep line voltage wiring physically separated from Ethernet and signal wiring. 

 
Power requirements 

 
The  module  must  be  powered  through  terminals  41  and  42.  by  12VDC  (FNIP-4xSH-12)  or 
24VDC (FNIP-4xSH-24). 
 

Please pay attention to the correct polarity. 

 
The  galvanic  isolation  of  the  inputs  is  only  effective  when  a  separate  power  supply  is  used 
for powering the inputs. The FNIP-4xSH has separate power input terminals (39 and 40) for 
this  purpose.  If  you  choose  not  to  use  the  extra  protection  the  isolated  inputs  offer  (not 
recommended),  you  can  use  the  same  power  to  supply  both  the  main  circuitry  and  the 
inputs. In that case, simply connect terminal 39 to terminal 41 and terminal 40 to terminal 
42. 
 

Ethernet connection 

 
Connect the module to the LAN via the RJ45 Ethernet socket. 

 
Outputs 

 
The module has four motor driver outputs each allows for connecting 230V or lower voltage 
four-wire  bidirectional  AC  motors.  Note  that  all  the  four  motors  have  to  have  the  same 
power requirement. The power for all the motors is the same, provided across terminals 13 
and  14.  For  example  the  module  can’t  be  used  to  drive  two  230V  AC  and  two  24V  AC 
motors,  but  can  drive  four  230V  AC  or  four  24V  AC  motors.  In  the  latter  case  24V  AC 
voltage must be applied across terminals 13 and 14. 
 

Local Inputs

 

 
For  each  output,  there  are  two  local  inputs  to  allow  for  manual  operations.  If  you  do  not 
wish to use local inputs, this section may be skipped. 

 

Connect momentary switches across the appropriate input terminals and the input common 
terminal for both the ‘up’ and the ‘down’ directions.

  

 

Содержание FutureNow FNIP-4xSH-12

Страница 1: ...torized window coverings such as shades shutters blind curtains awnings or projection screens and any other devices equipped with four wire bidirectional AC motors with built in limit switches either...

Страница 2: ...TURES Robust Operation Ideal for motorized window coverings projection screens awnings etc 4 outputs for controlling 4 four wire up down neutral bidirectional AC motors 4x2 up down galvanically isolat...

Страница 3: ...trollers from most major vendors Control4 AMX etc Interoperable with any momentary contact switches available on the market INSTALLATION WARNING Since the module is connected to line voltage the insta...

Страница 4: ...9 Motor 1 Down Input 4 Motor 2 Up Out 30 Motor 2 Up Input 5 Neutral 31 Inputs common 6 Motor 2 Down Out 32 Motor 2 Down Input 7 Motor 3 Up Out 33 Motor 3 Up Input 8 Neutral 34 Inputs Common 9 Motor 3...

Страница 5: ...cross terminals 13 and 14 motors with different power requirements can also be used but all four motor has to be have the same power requirement After making all connections check if the outputs work...

Страница 6: ...ts offer not recommended you can use the same power to supply both the main circuitry and the inputs In that case simply connect terminal 39 to terminal 41 and terminal 40 to terminal 42 Ethernet conn...

Страница 7: ...input terminals for this purpose See section Power Requirements if you don t want to use two separate power supply units To assure an additional level of safe and reliable operation the inputs are als...

Страница 8: ...The red LED indicates the direction of the movement It is off while the motor is moving up and on while the motor is moving down If the motor is not in motion this LED is off Input status LEDs Each ch...

Страница 9: ...face Use the FNIP Network Discovery Utility software to find all FutureNow IP devices on your network Connecting to the module s web site After the scan is over you can click on one of the modules fou...

Страница 10: ...and functions The default user name is admin The default password is futurenow Once logged in you will automatically be directed to the control page There is a menu on the top of each web page to navi...

Страница 11: ...users and setting up user rights Three different users can be defined each with three different user rights admin actor and observer Admins have access to all functionality including control of the o...

Страница 12: ...2014 12 Observers are allowed to monitor the status of inputs and outputs but not allowed to control the outputs nor can they change any settings To modify user settings click on User in the top menu...

Страница 13: ...___________________________________________ FutureNow FNIP 4xSH Installation Manual rev 15 01 2014 13 Board configuration Clicking on Board in the top menu takes you to the board configuration page wh...

Страница 14: ...nput modes and how they work see Operation via local inputs paragraph of this document below Updating the firmware is also possible via this page Logging out You can log out from the module s web page...

Страница 15: ...ermediate position Activating the input for the opposite direction while the motor is still moving will cause the motor to change its direction after a short delay You can also move the motor to the d...

Страница 16: ...ual rev 15 01 2014 16 Figure 9 Control Page Each input can either be active input terminals shorted or inactive input terminals open A grey icon means that the corresponding input is inactive An activ...

Страница 17: ...hieve the easiest integration with most controllers used in home and commercial applications the module can be controlled by raw TCP protocol using simple ASCII based commands The TCP IP communication...

Страница 18: ...al purpose controllers there are many applications for embedded industrial PC boards PCs and smartphones running Linux Windows Mac OS Firmware upgrade Upgrading the firmware of the module is possible...

Страница 19: ...Terminals Type Screw terminals for max 2 5 mm2 wires Communication 10Mb s Ethernet via RJ45 Ethernet connector Simple ASCII based TCP commands via port 7078 by default Number of socket connections tha...

Страница 20: ..._____________________________________________________________________________ FutureNow FNIP 4xSH Installation Manual rev 15 01 2014 20 REFERENCES FNIP Search Utility FNIP 4xSH TCP Communication Proto...

Отзывы: