Return preheating
The Return preheating function can be used for trans-
ferring heat from a heat source to the heating circuit
return.
The allocated relay is energised when both switch-on
conditions are fulfi lled:
• the temperature difference between the allocated
sensors has exceeded the switch-on temperature
difference
• the temperature at the outdoor temperature
sensor has fallen below the adjusted outdoor
temperature
With the summer switch-off option, the return pre-
heating can be suppressed outside the heating period.
Adjustment channel Description
Adjustment range / selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Return
Return sensor selection
system dependent
system dependent
Sen. HS
Heat source sensor selection
system dependent
system dependent
�Ton
Switch-on temperature difference
2.0 … 30.0 K
6.0 K
�Toff
Switch-off temperature difference
1.0 … 29.0 K
4.0 K
Summer off
Summer switch-off option
Yes, No
No
Sensor
Outdoor sensor selection
system dependent
system dependent
Toff
Switch-off temperature
10 … 60 °C
20 °C
Funct.
Activation / Deactivation
Activ. / Deactivated
Activated
Arrangement / opt. functions / Add new function / Return preheating
Sen. HS
Relay
Return
sensor