23/36
Setting of system parameters
"Regtronic RD-W"
Heat generator (modulating): Scaling of the 0-10 V characteristic line
Illustr. 25
The temperature to which the heating
water for storage cylinder loading shall be
heated by the modulating heat generator is
specified by the controller via the nominal
tempe offset (see above).
The 0-10 V/temperature characteristic line
of the heat generator and the 0-10 V output
signal of the controller have to be adapted for
this purpose. The different output voltages of
the controller correlate with a specific water
temperature provided by the heat generator.
Please proceed as follows:
1.
Determine the 0-10 V characteristic line
of the heat generator
(The instructions
of the manufacturer of heat
generator must be observed!)
2.
Select the lowest possible reference
point in the chart (instructions of the
manufacturer of the heat generator).
3.
Enter the values of the low reference point
in the controller menu and confirm you
entries.
4. Select the highest possible reference
point in the chart (manufacturer's
instructions).
5. Enter the values of the high reference
point in the controller menu and confirm
your entries.
Value entry analogue to illustr. 23
The output voltages entered in
the controller menu have to be
multiplied by 100.
Heat generator: Scaling of the 0-10V characteristic line
Note regarding the 0-10V request signal:
-Entry 200 corresponds to 2V
-Entry 950 corresponds to 9.5V
A13 : 0-10V