Installation & initial operation
"R-Tronic" + "R-Con"
44
4.6.4 Factory settings control module "R-Con T 2P"
It might be useful to restore the factory settings of the control module "R-Con
T 2P" if, for instance, several wireless thermostats "R-Tronic" shall be re
-
placed and/or the channels shall be reassigned.
Proceed as follows:
1. Set the
lower rotary switch (A)
of the control module to "
1
" (turn
anticlockwise until stop). The LED of the upper rotary switch (B) will flash.
2. Turn the upper rotary switch (B)
5 times clockwise until stop within
8 seconds
. The LED will flash
red
for 10 seconds.
X
The factory settings were restored successfully, i.e. the assignments for
all 4 channels will become null and void.
(Illustration 36)
A
B
DELETE SLAVE at the "R-Tronic"
After a reset of the control module, the function DELETE SLAVE in the menu
INSTALLATION has to be carried out at all "teached in" "R-Tronic" devices.