“Aktor M ST L 24V” Installation

9

101271784-V02.01.2020

5.2 

Configuration of the DIP switches

 

f

Remove the casing cover.

 

f

Configure the DIP switches according to the valve 
used (see section 

10 on page 12).

3
2

5

1

4

6

Illust. 4:  DIP switches

(1)

S1 ON/
OFF

Setting of the required stroke 

behaviour in accordance with 

the characteristic lines of the 

valve used.

(2)

S2 ON/
OFF

(3)

S3 ON/
OFF

(4)

S4 ON/
OFF

(5)

S5 ON/
OFF

(6)

Setting of the emergency end position
ON = Stem 
in retracted 
position

OFF = Stem  
in extended position

5.3  Connection of the power supply

NOTICE

Damage to the stem in unmounted state

If you operate the actuator electrically 

without valve, the stem may be damaged by 
exceeding the defined range of extension.

 

f

Only operate the product in mounted 
state

After having connected the power supply, the 
internal energy store will be charged first before 

the actuator reacts.

Charging of the energy store generally has pri-
ority over the actuator functions.

1 2 3 4 5

24 V AC/DC

0 V AC/DC

Y = 0 - 10 V DC  

0 V DC

U = 0 - 10 V DC 

Illust. 5:  Connection assignment

(1)

0 V AC/DC - blue (BU)

(2)

24 V AC/DC - brown (BN)

(3)

Control 0 - 10 V DC - grey (GY) 

(4)

Position feedback 0 V DC - yellow (YE)

(5)

Position feedback 0 -10 V DC - green (GN) 

 

f

Connect the power supply according to the desired 

assignment in Illust. 5 on page 9.

 

Z

The energy store will be charged.

 

Z

After about 2.5 minutes, the actuator will carry out 

an initialisation run and is ready for operation.

The supply voltage must not be interrupted 
during the initialisation run.

Содержание Aktor M ST L

Страница 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST L 24 V 0 10 V...

Страница 2: ......

Страница 3: ...isk of burns due to hot components and surfaces 6 2 3 3 Availability of the operating instructions 6 3 Technical description 7 3 1 Construction 7 3 2 Functional description 7 3 2 1 Normal operation 7...

Страница 4: ...Contents Aktor M ST L 24V 4 101271784 V02 01 2020...

Страница 5: ...s located on the bottom of the prod uct 1 3 Extent of supply Items included in the delivery Aktor M ST L 24 V modulating proportional actuator 0 10 V Operating instructions 1 4 Contact OVENTROP GmbH C...

Страница 6: ...to death or seri ous injury if not avoided CAUTION Indicates a possible danger with low risk It may lead to minor and reversible injury if the situation is not avoided NOTICE Indicates a situation wh...

Страница 7: ...oning 6 8 VA 24 V AC 3 3 W 24 V DC nominal 5 3 VA 24 V AC 2 7 W 24 V DC Start up load For short periods max 12 A Drive Steady control 0 10 V DC 0 5 mA Connection Fixed pre assembled cable 1 5 m 5 x 0...

Страница 8: ...or the installation of the actuator when installing the valve The actuator must only be connected to the power supply after installation CAUTION Risk of burns due to hot components An unprotected cont...

Страница 9: ...stem may be damaged by exceeding the defined range of extension f Only operate the product in mounted state After having connected the power supply the internal energy store will be charged first befo...

Страница 10: ...trol technology The emergency control function will only be available after successful completion of the initialisation run displayed by a constantly lit green LED 7 Maintenance The actuator is mainte...

Страница 11: ...ntal pollution Incorrect disposal for instance with the domestic waste may lead to environmental damage f Packaging material is to be disposed of in an environmentally friendly manner f Components are...

Страница 12: ...ON ON 2101 2500 l h OFF ON OFF OFF ON ON ON OFF ON ON DN 32 600 4800 l h 600 800 l h ON ON OFF OFF ON 801 2800 l h OFF OFF ON OFF ON OFF ON ON ON ON 2801 4800 l h ON OFF ON OFF ON ON ON ON ON ON Coco...

Страница 13: ......

Страница 14: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 101271784 V02 01 2020...

Отзывы: