11. GENERAL SPECIFICATIONS
Table .
Item
Description
Type of operation
Pulse adding
Displays
7-segment 8-digit LCD × 2 (LCD 1 numerals 7mm high, LCD 2 numerals 12.7mm high)
Target batch setting readout
LCD 2 shows to the 8th digit (resettable with RESET key). Batch setting to the 6th digit.
Grand total
LCD shows 8 digits
Operating status indicators
RUN, SV, MV, END, TC, ALM: LCD segments light.
OPE (GRN), SET (ORG), STOP (RED): LED lights.
BATT: “BATT” mark in the LCD lights.
•
•
•
Input signal
Flow signal input
Pulse generator
Power to generator
Signal levels
Response speed
Contact-closure pulse
PG20
3.5VDC
Current
capacity
55mA
3.5VDC ON/OFF
(input load resistance:
10kΩ)
50Hz max.
2-wire open collector pulse
Corioli flowmeter
200Hz max.
Input pulse
frequency
reduction
/0…2kHz max.
/00…3kHz max.
3-wire open collector pulse FLOWPET-DG,
NPG60A (E3)
Voltage pulse
PG30, NPG60A(F),
Corioli flowmeter
“”: 5VDC min.
“0”: .5VDC max.
Current pulse
PA14, 15, 25. NPG60A(E)
24VDC
“”: 20mADC
“0”: 4mADC
(Input resist: 24Ω)
Remote
Start
Instant make, Form “a” contact
Contact-Closure signal or open collector signal
Contact current: 0mA max. at 5VDC
Instant signal width: sec.
Note: Provide 2 sec. min. between signals.
Stop
Instant make, Form “a” contact
Reset
Instant break, Form ”b” contact
Parameter setting
Batch setting
Any setting from 0 to 999999 counts
Preset by front-panel control keys (in the batch setup mode “RUN”).
Grand total setting
Any setting from 00000000 to 99999999 counts
Preset by front-panel control keys (in the setup mode “SET”).
Initial-and final-count setting
Any setting from 0 to 999 counts (default: 80) Set by front-panel control keys.
If set at “0,” the valve opens and closes in the single stage ( in the setup mode “SET”).
Missing pulse setting
Any setting from 1 to 15 sec. (default 10 sec.) Preset by front-panel control keys.
When set to “0,” the alarm is disabled (in the setup mode “SET”).
Overshoot setting
Any setting from 1 to 99 counts (default 10) preset by front-panel control keys.
If set to “0,” the alarm is disabled (in the setup mode “SET”).
Scaler setting
Any setting from 0.0001 to 1.9999 (default 1.0000) Preset by front-panel control keys (in the setup
mode “SET”).
Frequency divide setting
Software frequency division – 0:/, :/0, 2: /00
One chosen with front-panel control keys (in the setup mode “SET”).
Hardware frequency division – /, /0, /00
One chosen with internal jumper (in the setup mode “SET”).
•
•
Output signal
Valve operate
signal
Partial flow signal
(SV)
Holds from batch start to batch end.
“SV” area in the LCD lights. “S. VALVE” area in the LED lights.
•
Relay contact output
(Form “c” contact)
Contact capacity:
250VAC A
One set each
High-limit flow
signal (MV)
Holds from the end of initial partial flow to the start of final partial Flow
open.
“MV” area in the LCD lights. “M. VALVE” area in the LED lights.
•
End-of-batch output
Holds when the target batch setting is reached.
“End” area in the LCD lights. (Resettable with RESET key.)
•
Non-contact relay output
(Form “a” contact)
Contact capacity:
250VAC/DC 0.5A
One set each
Output to remote totalizer
Pulse width: 1ms (default) or 50ms
“TC” area in the LCD blinks in synchronism with the output.
•
Alarm output
➀
Missing pulse Operates when no pulse is accepted within preset time.
“ALM” area in the LCD lights. (Resettable with STOP key.)
•
Relay contact output
(Form “a” contact)
One set
Contact capacity: 250VAC, 1A
An alarm output is
produced when any of
alarms ① , ② , or ③ has
occurred.
➁
Overshoot
Operates when both target batch and this setting are exceeded.
“ALM” area in the LCD lights. (Resettable with RESET button.)
•
➂
Parameter
error
Operates upon detection of a parameter error.
A message “dAtA Err” appears. (Resettable with RESET key.)
•
Power failure back up
Parameters and variables retained in E²PROM when power is interrupted.
Power source
85 to 264VAC, 50/60HZ
Power consumption
25VA 0W max.
Ambient temperature
–0 to +50°C
Installation
Panel mount
Finish
Munsell N1.5 (standard)
Outline dimensions
96 × 96 × 70mm
Weight
.0kg approx.
NOTE: A surge protector is built in: do not make insulation resistance test and dielectric withstanding
voltage test across power terminals.