ENCLOSURES FOR SELF-CONTAINED  

LP GAS SYSTEMS:

An enclosure for an LP-gas cylinder shall be ventilated by 
openings at both the upper and lower levels of the enclosure. This 
shall be accompanied by one of the following:
a.   One side of the enclosure shall be completely open; or
b.   For an enclosure having four sides, a top, and a bottom:

At least two ventilation openings shall be provided in the 
sidewalls of the enclosure, located within 217 mm / 5 in of the 
top of the enclosure, equally sized, spaced at a minimum of 90 
degrees (1.57 rad), and unobstructed. The opening(s) shall have 
a total free area of not less than 14.2 cm² per kg / 1 in² per lb of 
stored fuel capacity.

Ventilation opening(s) shall be provided at floor level of the 
enclosure and shall have total free area of not less than 7.1 cm² per 
kg / 0.5 in² per lb of stored fuel capacity. If ventilation openings 
at floor level area are in the side wall, there shall be at least two 
openings. The bottom of the openings shall be 25.4 mm / 1 in or 
less from the floor level and the upper edge no more than  
127 mm / 5 in above the floor level. The openings shall be 
equally sized, spaced at a minimum of 90 degrees (1.57 rad), and 
unobstructed.

Every opening shall have minimum dimensions so as to permit 
the entrance of a 3.2 mm / .125 in diameter rod. Ventilation 
openings in sidewalls shall not communicate directly with other 
enclosures of the appliance.

CONNECTION:

1.  

Be sure the cylinder valve and appliance valves  
are “off”.

2.  Place full LP gas cylinder on tank stabilizer ring.
3.   Center the nipple in the cylinder valve and hold in place. 
4.   Using the other hand, turn the hand wheel clockwise until 

there is a positive stop. Do not use tools. 

5.   Hand tighten only. When making the connection,  

hold the regulator in a straight line with the cylinder valve, so 
as not to cross thread the connection.

6.   Leak test the connection. See section named “LEAK TEST”.

 

 WARNING:

Ensure that the appliance is kept at a minimum distance of  
0.91m (36”) from the gas cylinder.

LP 

Cylinder

Tank Ring

2. Gas Hose 

Regulator

Heat Sensitive

Hand Wheel

Cylinder

Shut Off

Valve

Check Valve

Nipple with

Flow Limiting Device

1. Firebowl

  Valve Coupling

3. Cylinder Valve 

Coupling

Appliance

Tank Ring

Minimum 

36’’ (0.91m)

LEAK TEST: Apply the solution to the LP gas delivery 

system at points: 

1. Firebowl Valve Coupling 

2. Gas Hose Regulator 

3. Cylinder Valve Coupling

Caution:

Trip Hazard!

Содержание FMPPC2F

Страница 1: ...UTLAND Flame mark is a registered trademark of FMI Brands Inc Owner s Manual MANUFACTURED BY FMI BRANDS INC 107 19052 26 Avenue Surrey B C Canada V3Z 3V7 USA Canada Toll Free 1 888 514 1663 Tel 1 778...

Страница 2: ...d result in fire or explosion which could cause property damage personal injury or death WARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other...

Страница 3: ...t all adults and children which use or are near a unit in use are aware of the hazard of high surface temperatures present on the unit during use and should use caution and stay away to avoid burns or...

Страница 4: ...han 127 mm 5 in above the floor level The openings shall be equally sized spaced at a minimum of 90 degrees 1 57 rad and unobstructed Every opening shall have minimum dimensions so as to permit the en...

Страница 5: ...ance being put into operation if there is evidence of excessive abrasion or wear or if the hose is damaged Contact FMI Brands Inc should you require a replacement hose Inspect burner prior to each use...

Страница 6: ...one carry strap STEP 1 Remove plastic bags containing the rocks propane stabilizer ring and cover and carry kit STEP 2 Open the single bag containing mid sized rocks labelled conveniently for you M an...

Страница 7: ...T empty Close gas supply valve Open and then close the appliance gas knob valve to release pressure Be sure appliance valve is OFF Disconnect and reconnect the cylinder regulator connection Slowly ope...

Страница 8: ...trol setting to low for 5 10 minutes or replace the cylinder with a full one 3 Ensure that you clean the bowl of your Outland Firebowl after every use to keep it looking GREAT Simply wipe the outer ed...

Страница 9: ...use are aware of the hazard of high surface temperatures present on the unit during use and should use caution and stay away to avoid burns or clothing ignition Do not place any objects other than sup...

Страница 10: ...original retail packaging Please register your OUTLAND Living product for proof of purchase and warranty at http outlandliving com register products Registration in English only For more warranty info...

Страница 11: ...ASE VISIT WWW OUTLANDLIVING COM The owner s manual is available as a free download from www outlandliving com Should you have any questions or comments regarding this appliance please do not hesitate...

Страница 12: ...D 863 000 V4 En 11 Owner Safety Manual OUTLAND FIREBOWL CYPRESS OWNER SAFETY MANUAL...

Отзывы: