Owner & Safety Manual
D.863.000.V4
En-3
OUTLAND FIREBOWL
®
CYPRESS OWNER & SAFETY MANUAL
2
ENCLOSURES FOR SELF-CONTAINED
LP GAS SYSTEMS:
An enclosure for an LP-gas cylinder shall be ventilated by
openings at both the upper and lower levels of the enclosure. This
shall be accompanied by one of the following:
a. One side of the enclosure shall be completely open; or
b. For an enclosure having four sides, a top, and a bottom:
At least two ventilation openings shall be provided in the
sidewalls of the enclosure, located within 217 mm / 5 in of the
top of the enclosure, equally sized, spaced at a minimum of 90
degrees (1.57 rad), and unobstructed. The opening(s) shall have
a total free area of not less than 14.2 cm² per kg / 1 in² per lb of
stored fuel capacity.
Ventilation opening(s) shall be provided at floor level of the
enclosure and shall have total free area of not less than 7.1 cm² per
kg / 0.5 in² per lb of stored fuel capacity. If ventilation openings
at floor level area are in the side wall, there shall be at least two
openings. The bottom of the openings shall be 25.4 mm / 1 in or
less from the floor level and the upper edge no more than
127 mm / 5 in above the floor level. The openings shall be
equally sized, spaced at a minimum of 90 degrees (1.57 rad), and
unobstructed.
Every opening shall have minimum dimensions so as to permit
the entrance of a 3.2 mm / .125 in diameter rod. Ventilation
openings in sidewalls shall not communicate directly with other
enclosures of the appliance.
CONNECTION:
1.
Be sure the cylinder valve and appliance valves
are “off”.
2. Place full LP gas cylinder on tank stabilizer ring.
3. Center the nipple in the cylinder valve and hold in place.
4. Using the other hand, turn the hand wheel clockwise until
there is a positive stop. Do not use tools.
5. Hand tighten only. When making the connection,
hold the regulator in a straight line with the cylinder valve, so
as not to cross thread the connection.
6. Leak test the connection. See section named “LEAK TEST”.
WARNING:
Ensure that the appliance is kept at a minimum distance of
0.91m (36”) from the gas cylinder.
LP
Cylinder
Tank Ring
2. Gas Hose
Regulator
Heat Sensitive
Hand Wheel
Cylinder
Shut Off
Valve
Check Valve
Nipple with
Flow Limiting Device
1. Firebowl
Valve Coupling
3. Cylinder Valve
Coupling
Appliance
Tank Ring
Minimum
36’’ (0.91m)
LEAK TEST: Apply the solution to the LP gas delivery
system at points:
1. Firebowl Valve Coupling
2. Gas Hose Regulator
3. Cylinder Valve Coupling
Caution:
Trip Hazard!