GS-IOB-230VAC Installation Instructions
6
900-0146-01-00 REV A
Basic AC Wiring
The GS-IOB-230VAC comes with six brown and one blue wire that are labeled
according to their intended electrical connection. It also comes with an
unlabeled green wire and two unlabeled short brown wires. If the preceding
steps are followed, as well as the drawing in Figure 5, these wires will have
sufficient length to make the intended connections.
It is recommended that the wires be connected to the circuit breakers prior to
re-installing the main circuit breaker bracket. To install the wires:
1.
Remove the nuts and washers from each circuit breaker, noting the
sequence of the washers.
2.
For each of the six wires, install the wire’s ring terminal on the
appropriate terminal post for each circuit breaker according to Figure 5.
Typically each post is equipped with two identical star washers. The
ring terminal on the wire should be installed between these star
washers. If there is only one star washer, install the ring terminal on the
post first, then the star washer and the remaining hardware.
3.
Install the two short wires between the input, output, and bypass circuit
breakers as shown in Figure 5.
4.
Torque the nuts on each circuit breaker to 4 Nm (35 in-lbs).
5.
Re-install the main circuit breaker bracket using the four screws and any
star washers that were previously removed. Use the illustrations in
Figure 3 on page 4 for reference.
6.
Connect the brown wires from each circuit breaker to the appropriate
bus bar as shown in Figure 5.
7.
Connect the blue AC Neutral wire to the neutral bus bar.
8.
Connect the green wire to the ground bus bar.
All wires from steps 6, 7, and 8 should be torqued to 2.8 Nm (25 in-lbs). It is
recommended to make 90-degree bends in the wires as shown, so that the layout
is easy to follow in the future. (The wires have been designed to be long enough.)
At this time, all wires should be connected to bus bars or circuit breakers. Certain
wires will only have one end connected, with the other end meant to be
connected to a 230 Vac Radian Series Inverter/Charger. (This is usually positioned
above the GSLC.) The disconnected wires should have these labels:
AC OUT HOT LEG 1
GRID IN HOT LEG 1
(Green Wire
—
No Label)
Before connecting these wires to the inverter, use a digital multimeter to check
that all electrical connections are correct and show continuity. Once confirmed,
connect the wires to the Radian inverter/charger, removing knockouts and
GEN IN HOT LEG 1
AC NEUTRAL