Installation
WARNING: Shock Hazard
Ensure there is only one Neutral-to-Ground Bond in the system.
The
FLEXpower ONE comes with a Neutral-to-Ground Bond installed. If a Neutral-
to-Ground bond exists elsewhere in the system (e.g., in the main panel, or a
generator), the Neutral-to-Ground Bond in the FLEXpower ONE AC Enclosure
will need to be removed. See Figure 18. Check local code for specific
requirements.
AC Enclosure
Factory-installed
Neutral-To-Ground
Bond
Internal components shown may vary from model to model.
Factory wiring is not shown.
The factory-installed
Neutral-to-Ground Bond
must be removed if
another Neutral-to-
Ground Bond exists
elsewhere in the
configuration.
See Table 5 on page 32 for recommended
conductor sizes and torque requirements.
Figure 18
AC OUT Connections
32
900-0095-01-00 Rev A