Installation
To make the PV connections:
1.
Ensure the PV array is properly grounded.
2.
Route the PV (–) through the bottom of the DC enclosure and into the wiring compartment of the
FM80 charge controller. Connect the PV (–) conductor to the PV (–) terminal in the FM80 charge
controller. Torque to 35 in-lb (4 Nm).
3.
Connect the PV (+) to the top terminal of the PV Disconnect in the DC Enclosure. Torque
to 35 in-lb (4 Nm).
Internal components shown may vary from model to model. Factory wiring is not shown.
30
900-0095-01-00 Rev A
Figure 16
PV Connections with a FLEXnet DC Monitor