![OutBack Power Alino TL Series Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/outback-power/alino-tl-series/alino-tl-series_owners-manual_1660805036.webp)
Settings
36
900-0248-01-00 Rev A
Output Source Priority Timer
The Alino can switch between Output Source Priority settings (see
0 1
on page 31) on a timer.
Figure 27
Output Priority Timer Setting Items
When using multiple sources to support loads, the priority of the source usage (
U S b
,
S U b
, or
S b U
) can be set to change automatically by time of day. For example, during daylight hours
the system can be set to
S b U
. The inverter will run loads from PV or battery power only.
Utility is used only as a last resort. Then during night hours, the system can be set to
U S b
,
which runs loads primarily from utility power.
To set the Output Source Priority Timers:
1.
Press and hold button
2
for 3 seconds. Screen items
7
,
8
, and
9
will show these options.
U S b
(utility, solar, battery)
S U b
(solar, utility, battery)
S b U
(solar, battery, utility)
2.
The
U S b
,
S U b
, or
S b U
options are set independently for different blocks of time using
buttons
1
,
2
, and
3
. When each button is pressed, the results will appear in this format.
U S b
(selection)
0 0
(start time)
2 3
(end time)
3.
To change
U S b
settings, press button
1
. Once selected, the start and end times can be
set using buttons
4
and
5
. The setting range is from 00 to 23 in increments of one hour.
Press button
6
to confirm the setting.
4.
To change
S U b
settings, press button
2
. Once selected, the start and end times can be
set using buttons
4
and
5
. The setting range is from 00 to 23 in increments of one hour.
Press button
6
to confirm the setting.
5.
To change
S b U
settings, press button
3
. Once selected, the start and end times can be
set using buttons
4
and
5
. The setting range is from 00 to 23 in increments of one hour.
Press button
6
to confirm the setting.
2
7
8
9
1
3
4
5
6
Содержание Alino TL Series
Страница 1: ...Alino TL Power Conditioning Unit Owner s Manual...
Страница 45: ...Specifications 900 0248 01 00 Rev A 45 This page intentionally left blank...
Страница 46: ...Specifications 46 900 0248 01 00 Rev A This page intentionally left blank...
Страница 47: ...Specifications 900 0248 01 00 Rev A 47 This page intentionally left blank...